2

TABLE OF CONTENTS

TECHNICAL DATA
 

PHRVR 160 & PHRVR 210................................................................................ .3

 

PHRV 150 & PHRV 200 .................................................................................... 5

 

PHRVR 305 ....................................................................................................  7

 

PHRV 140, PHRVR 155 & PHRVR 205............................................................... 9

OPERATION............................................................................................................11
 

Modes Of Operation  ........................................................................................11

 

Optional Remote Controls ...............................................................................  12

 

Intellitek Multi-Function Controls EDF5 ...............................................................12

INSTALLATION........................................................................................................13
 

Mounting the Unit  .........................................................................................  13 

 

Location & Ducting .........................................................................................  14

 

Examples ....................................................................................................... 17

 

Air Flow Balancing  .........................................................................................  21

MAINTENANCE ..................................................................................................... 23

TROUBLESHOOTING............................................................................................... 24

ELECTRICAL CONNECTIONS  ............................................................................. ...  25

  The Best  

Limited Warranty  

in the Business

•  The heat recovery polypropylene core has 

a limited lifetime warranty.

•  The motors found in all Powrmatic HRV’s 

require no lubrication, and are factory 
balanced to prevent vibration and promote 
silent operation.

•  The limited warranty covers normal use. 

It does not apply to any defects, 
malfunctions or failures as a result of 
improper installation, abuse, mishandling,  
misapplication, fortuitous occurrence or 
any other circumstances outside 
Powrmatic’s control.

•  Inappropriate installation or  

maintenance may result in the 
cancellation of the warranty.

•  Any unauthorized work will result in  

the cancellation of the warranty.

•  Powrmatic is not responsible for any  

incidental or consequential damages 
incurred in the use of the ventilation system.

•  Powrmatic is not responsible for providing 

an authorized service centre near the 
purchaser or in the general area.

•  Powrmatic reserves the right to supply 

refurbished parts as replacements.

•  Transportation, removal and installation 

fees are the responsibility of the purchaser.

•  The purchaser is responsible to adhering 

to all codes in effect in his area.

•  The warranty is limited to 5 years on 

parts and 7 years on the motor from the 
date of purchase, including parts replaced 
during this time period. If there is no 
proof of purchase available, the date 
associated with the serial number will be 
used for the beginning of the warranty 
period.

* This warranty is the exclusive and only 

warranty in effect relative to the ventilation 
system and all other warranties either 
expressed or implied are invalid.

Sizing (Example) for maximum airflow normally required.

HRVs are typically sized to ventilate the whole house at a minimum of 0.35 air changes per 
hour. To calculate, simply take the square footage of the house (including basement) and multi-
ply by the height of the ceiling to get cubic volume. Then, divide by 60 and multiply by 0.35.
Example: 

SQFT of House 

1100

 

Basement 

1100

 

Total SQFT 

2200

 

Height of ceiling 

x   8

 

Cubic volume 

17600

 

 

/  60

 

Maximum airflow required (CFM) 

293

 

 

x  0.35

 

 

103

* Always consult your local code for sizing requirements in your area.

Room classification 

Number of rooms 

CFM (L/s) 

CFM Required

Master bedroom 

 

x 20 cfm (10 l/s) 

=

Basement 

yes or no 

 

=

Bedrooms 

 

x 10 cfm  (5 l/s) 

=

Living room 

 

x 10 cfm  (5 l/s) 

=

Others 

 

x 10 cfm  (5 l/s) 

=

Kitchen 

 

x 10 cfm  (5 l/s) 

=

Bathroom 

 

x 10 cfm  (5 l/s) 

=

Laundry room 

 

x 10 cfm  (5 l/s) 

=

Utility room 

 

x 10 cfm  (5 l/s) 

=

 

Total Ventilation Requirements

 (add last column ) 

=

Alternate Method

if yes add 20 cfm / 10 l/s 

if no = 0

1 cfm = 0.47189 l/s 
1 l/s = 3.6 m

3

/hr

***Illustrations & 

images in this  

manual may not be 

exactly like unit  

purchase, these 

illustrations & imag-

es are for examples 

only.***

Содержание PHRV 140

Страница 1: ...f the Heat Recovery Ventilators by using the balancing procedure found in this manual It is always important to assess how the operation of any HRV may interact with vented com bustion equipment i e Gas Furnaces Oil Furnaces Wood Stoves etc NEVER install a ventilator in a situation where its normal operation lack of operation or par tial failure may result in the backdrafting or improper functioni...

Страница 2: ...he purchaser The purchaser is responsible to adhering to all codes in effect in his area The warranty is limited to 5 years on parts and 7 years on the motor from the date of purchase including parts replaced during this time period If there is no proof of purchase available the date associated with the serial number will be used for the beginning of the warranty period This warranty is the exclus...

Страница 3: ...rings guarantee long life and maintenance free operation Seven 7 year warranty CORE A polypropylene heat recovery core configured for an efficient cross flow ventilation Core is 9 x 9 229 x 229 mm with a 15 380 mm depth PHRVR 160 or 12 x 12 305 x 305 mm with a 15 380 mm depth PHRVR 210 Cores are manufactured to withstand extreme temperature variations FILTERS Two 2 Washable Electrostatic Panel Typ...

Страница 4: ...ation defrost models only can be ducted or left open Airflow PHRVR 160 PHRVR 210 Series HRV Model A B C D E PHRVR 160 2 1 4 56mm 23 1 2 596mm 2 5 8 67mm 17 3 8 441mm 17 3 8 441mm PHRVR 210 2 1 4 56mm 27 7 8 707mm 2 5 8 67mm 17 3 8 441mm 20 1 2 520mm Fan Performance Performance Data Model PHRVR 160 72 69 PHRVR 210 71 76 Apparent Sensible Effectiveness at 32ºF 0ºC Apparent Sensible Effectiveness at ...

Страница 5: ...s with backward curved blades Motors come with permanently lubricated sealed bearings guarantee long life and maintenance free operation Seven 7 year warranty CORE A polypropylene heat recovery core configured for an efficient cross flow ventilation Core is 9 x 9 229 x 229 mm with a 15 380 mm depth PHRV 150 or 12 x 12 305 x 305 mm with a 15 380 mm depth PHRV 200 Cores are manufactured to withstand...

Страница 6: ...PHRV 150 PHRV 200 Series HRV Model A B C D E PHRV 150 2 1 4 56mm 23 1 2 596mm 2 5 8 67mm 17 3 8 441mm 16 1 8 413mm PHRV 200 2 1 4 56mm 27 7 8 707mm 2 5 8 67mm 17 3 8 441mm 20 1 2 520mm Fan Performance Performance Data 6 Model PHRV 150 72 69 PHRV 200 71 76 Apparent Sensible Effectiveness at 32ºF 0ºC Apparent Sensible Effectiveness at 13ºF 25ºC AIRFLOW CAP cfm L s 0 4 on High Speed Power Volts 120 V...

Страница 7: ...ermanently lubricated sealed bearings guarantee long life and maintenance free operation Seven 7 year warranty CORES Two 2 polypropylene heat recovery cores configured for an efficient cross flow ventilation Core is 12 x 12 305 x 305 mm with a 15 380 mm depth Cores are manufactured to withstand extreme temperature variations FILTERS Two 2 synthetic high quality filters for better indoor air qualit...

Страница 8: ...C Static Pressure Pa 200 00 240 00 280 00 320 00 360 00 19 00 0 00 38 00 57 00 76 00 94 00 114 00 123 00 142 00 162 00 5TH port for recirculation defrost models only can be ducted or left open Airflow PHRVR 305 Series HRV Performance Data Model PHRVR 305 92 91 Apparent Sensible Effectiveness at 32ºF 0ºC Apparent Sensible Effectiveness at 13ºF 25ºC AIRFLOW CAP cfm L s 0 4 on High Speed Power Volts ...

Страница 9: ...e heat recovery core configured for an efficient cross flow ventilation Core is 9 x 9 229 x 229 mm with a 15 380 mm depth PHRV 140 PHRVR 155 or 12 x 12 305 x 305 mm with a 15 380 mm depth PHRVR 205 Cores are manufactured to withstand extreme temperature variations FILTERS Two 2 Washable Electrostatic Panel Type Air Filters PHRV 140 PHRVR 155 is 8 5 216mm x 15 380mm x 0 125 3mm PHRVR 205 is 11 75 2...

Страница 10: ...V Model A B C D PHRV 140 23 3 4 604mm 17 1 4 438mm 16 1 4 413mm 2 1 4 56mm PHRVR 155 23 3 4 604mm 17 1 4 438mm 16 1 4 413mm 2 1 4 56mm PHRVR 205 28 711mm 17 1 4 438mm 20 1 2 521mm 2 1 4 56mm Fan Performance Performance Data Model PHRV 140 81 79 PHRVR 155 81 79 PHRVR 205 71 76 Apparent Sensible Effectiveness at 32ºF 0ºC Apparent Sensible Effectiveness at 13ºF 25ºC AIRFLOW CAP cfm L s 0 4 on High Sp...

Страница 11: ... controls the Intellitek 5MR An on board diagnostic LED helps find problems quickly and efficiently For example the LED can be used to signal a broken or shorted electronic wall control wire Electronic air temperature probe gives this board accurate readings in order to minimize unnecessary defrost operation and the on board jumpers provide the user with the option of adjusting defrost time and se...

Страница 12: ...ng season is higher than outdoor levels High humidity is a major cause of structure damage and IAQ problems such as mold and mildew 2 wire installation 4 wire installation 3 wire installation 2 wire installation 5MR INTELLITEK MULTI FUNCTION WALL CONTROL Control multiple func tions of your Powrmatic HRV with one slimline wall con trol Two wire connec tion simplifies installa tion Use one EDF5 per ...

Страница 13: ...g its defrost mode the HRV may produce some condensation This water should flow into a nearby drain or be taken away by a condensate pump The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point A P trap should be made in the drain line This will prevent odors from being drawn back up into the unit MOUNTING LOCATION The HRV must be ...

Страница 14: ...ain full and not be squished The outer liner which acts as a vapor barrier must be completely sealed to outer wall and the HRV using tape and or caulking A good bead of high quality caulk ing preferably acoustical sealant will seal the inner flexible duct to both the HRV port and the weatherhood prior to clamping To minimize air flow restriction the flexible insulated duct that connects the two ou...

Страница 15: ...sible Forty five degree are preferred to 90º elbows Use Y tees instead of 90º elbows whenever possible All duct joints must be fastened with screws or duct sealant and wrapped with a quality duct tape to prevent leakage Aluminum foil duct tape is recommended Galvanized ducting from the HRV to the living areas in the house is recommended whenever possible although flexible duct can be used in moder...

Страница 16: ...rilles be completely opened at first and then adjusted later as needed Dedicated Installation for Existing Home non forced air heating cooling system 1 Begin with the duct collar marked Exhaust Air In Slide a short piece 12 of flexible duct over the duct collar Using duct tape tape the flexible duct to the collar Run the flexible ducting to the main rigid duct trunk line which connects to the rema...

Страница 17: ...LATION EXAMPLES Example diagram only duct configuration may change depending on model It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended All air movement devices have a performance curve The amount of air CFM that an HRV will deliver is directly related to the total external static pressure E S P of the ...

Страница 18: ...drawn from key areas of home Exhaust Air from various parts of home i e bathrooms if required kitchens if required NOTES 1 Furnace blower may be required to operate when HRV is on to provide good air distribution 2 Weatherhood arrangement is for drawing purposes only 6 2m minimum separation recommended 18 460mm above grade minimum 3 Due to the differences in pressure between the HRV and the equipm...

Страница 19: ...inuously or interlocked with HRV 2 A minimum separation of 39 inches 1m is recommended between the two direct connections 3 The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air 4 Weatherhood arrangement is for drawing purposes only 6 2m minimum separation recommended 18 460 mm above grade minimum 5 Due to the differences in pressure between...

Страница 20: ...The furnace should be set to run continuously or interlocked with HRV 2 The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air 3 Weatherhood arrangement is for drawing purposes only 6 feet 2m minimum separation recommended 18 inches 460 mm above grade minimum 4 Due to the differences in pressure between the HRV and the equipment it is being c...

Страница 21: ...n may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or other manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube coming out of the top of the pitot is connected to the high pressure side of the gauge The tube com ing out of the side of the pitot is connected to the low pressure or refer ence side...

Страница 22: ...at the magnehelic gauge is level and at 0 Refer to the flow measuring station s chart to determine your unit s airflow velocity 3 Adjust the Supply Air Out damper until you reach the desired velocity Follow the previous steps to adjust the Exhaust Air Out damper if needed B Measure here Measure here 18 457 mm 18 457 mm To avoid airflow turbulence and incorrect readings the airflow velocity should ...

Страница 23: ...ing any repairs or maintenance a Open access door b Carefully grip ends of core and pull evenly out ward Core may be snug but will slide out of the channel c Once removed from the cabinet remove filters d Wash core in warm soapy water do not use dishwasher e Install the clean filters f Install clean core To Install the Clean Core and Filters a First mount the bottom flange of the core guide into t...

Страница 24: ... Locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant eg Over a sofa Turn down the HRV supply speed A small duct heater 1kw could be used to temper the supply air Placement of furniture or closed doors is restricting the movement of air in the home If supply air is ducted into furnace ret...

Страница 25: ...act Open Closes contact when HRV ERV is ON OFF Diagnostic LED U 15 minute timer up to 5 timers EDF5 or EDF2 not shown Dehumidistat 2 wires Dehumidistat On Off 4 wires Mechanical Crank Timer 2 wires and or and or 1 only Air Quality Sensor Wiring diagram of complete unit inside of access panel 2 wires 3 wires 5MR 2 wire ...

Страница 26: ...S CONT D Caution Never connect a 120 volt AC circuit to the terminals of the Accessory Control Contacts Only use the low voltage class 2 circuit of the furnace blower control For a Furnace Connected to a Cooling System On some older thermostats energizing the R and G termi nals at the furnace has the effect of energizing Y at the thermostat and thereby turn ing on the cooling system If you identif...

Страница 27: ...27 ...

Страница 28: ...708 F 418 683 8860 quebec powrmatic ca Toronto 1155 B Barmac Drive North York ON M9L 1X4 T 416 744 7206 F 416 744 7210 toronto powrmatic ca Halifax 3607 Strawberry Hill Halifax NS B3K 5A8 T 902 454 8684 F 902 453 5875 halifax powrmatic ca Ottawa 162 Elm Street Ottawa ON K1R 6N5 T 613 230 7160 F 613 230 0685 ottawa powrmatic ca If you want to know your local dealer contact powrmatic ...

Отзывы: