Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished, for example, by installing a dual dif-
ferential pressureless manifold.
The frost protection function of the heat pump manager is ac-
tive whenever the heat pump manager and the heat circulating
pumps are ready for operation. The system must be drained if
the heat pump is taken out of service or in the event of a power
failure. If heat pump systems are implemented in buildings
where a power failure cannot be detected (holiday homes etc.),
the heating circuit should be operated with suitable frost pro-
tection.
7.3 Heat source connection
The following procedure must be observed when making the
connection:
Connect the well pipes to the heat pump's flow and return.
ATTENTION!
!!
It is essential that the dirt trap included in the accessories
pack is installed in the return (inlet).
ATTENTION!
!!
The well water must comply with the required water quality
standards (see Cap. 9.4 on page 11).
ATTENTION!
!!
The flow rate switch available as an accessory must be
installed in the flow (outlet) of the heat source.
The hydraulic integration diagram must be adhered to.
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
Outside temperature sensor (R1) supplied (NTC-2)
Return temperature secondary circuit (R2) installed
(NTC-10)
Return temperature primary circuit (R24) installed (NTC-
10)
Flow temperature secondary circuit (R9) installed (NTC-10)
Flow temperature primary circuit (R6) installed (NTC-10)
7.4.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump
manager must correspond to the sensor characteristic curve il-
lustrated in Fig. 7.2 on page 7. The only exception is the outside
temperature sensor included in the scope of supply of the heat
pump (see Fig. 7.3 on page 7)
Fig. 7.2:Sensor characteristic curve NTC-10
Fig. 7.3:Sensor characteristic curve NTC-2 according to DIN 44574 Out-
side temperature sensor
Temperature in °C
-20 -15 -10
-5
0
5
10
NTC-2 in k
14.6
11.4
8,9
7.1
5.6
4.5
3.7
NTC-10 in k
67.7
53.4
42.3
33.9
27.3
22.1
18.0
15
20
25
30
35
40
45
50
55
60
2.9
2.4
2.0
1.7
1.4
1.1
1.0
0.8
0.7
0.6
14.9
12.1
10.0
8.4
7.0
5.9
5.0
4.2
3.6
3.1
0
10
20
30
40
50
60
70
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
External temperature in [°C]
Resistance value in
[kOhm]
0
2
4
6
8
10
12
14
16
18
20
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
External temperature in [°C]
Resistance value in
[kOhm]
Содержание WI 120TU
Страница 2: ......
Страница 38: ...EN 18 452237 66 53 FD 9912 www gdts one English WI 120TU WI 180TU...
Страница 56: ...FR 18 452237 66 53 FD 9912 www gdts one Fran ais WI 120TU WI 180TU...
Страница 66: ...A X 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU 3 3 Last Load Charge WI 120TU...
Страница 82: ...A XXVI 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU...
Страница 83: ...www gdts one 452237 66 53 FD 9912 A XXVII WI 120TU WI 180TU Anhang Appendix Annexes...