Cleaning / maintenance

9.1 Maintenance

To prevent faults due to sediment in the heat exchangers, care
must be taken to ensure that no impurities can enter either the
heat source system or the heating system. In the event that op-
erating malfunctions due to contamination occur nevertheless,
the system should be cleaned as described below.

9.2 Cleaning the heating system

The ingress of oxygen into the heating water circuit may result
in the formation of oxidation products (rust), particularly if steel
components are used. These enter the heating system via the
valves, the circulating pumps and/or plastic pipes. A diffusion-
resistant installation is therefore essential, especially with re-
gard to the piping of underfloor heating systems.

NOTE

º

We recommend the installation of a suitable corrosion
protection system to prevent the formation of deposits (e.g.
rust) in the condenser of the heat pump.

Residue from lubricants and sealants may also contaminate the
heating water.
In the event of severe contamination leading to a reduction in
the performance of the liquefier in the heat pump, the system
must be cleaned by a heating technician.
Based on current information, we recommend using a 5 %
phosphoric acid solution for cleaning purposes. However, if
cleaning needs to be performed more frequently, a 5 % formic
acid solution should be used.
In both cases, the cleaning  fluid should be at room tempera-
ture. We recommend flushing the heat exchanger in the direc-
tion opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating
system circuit, we recommend connecting the flushing device
directly to the flow and return of the liquefier of the heat pump.
It is then important that the system be thoroughly flushed using
appropriate neutralising agents to prevent any damage from
being caused by cleaning agent residue remaining in the sys-
tem.
Acids must be used with care and the regulations of the em-
ployers liability insurance associations must be adhered to.
The instructions of the cleaning agent manufacturer must al-
ways be observed.

9.3 Cleaning the heat source 

system

ATTENTION!

!!

The supplied dirt trap must be inserted in the heat source inlet
of the heat pump to protect the evaporator against the ingress
of impurities.

The filter sieve of the dirt trap should be cleaned one day after
start-up. Further checks must be set according to the level of
dirt. If no more signs of contamination are evident, the filter can
be removed to reduce pressure drops.

9.4 Water quality requirements

Irrespective of any legal regulations, the ground water should
not contain any substances that could form deposits. Iron
(< 0.2 mg/l) and Manganese (< 0.1 mg/l) limit values must be
adhered to to prevent iron ochre sedimentation from forming in
the heat source system.
The use of surface water or water containing salt is not permis-
sible. Your local water utility can provide you with general infor-
mation regarding the possible use of ground water. Water anal-
yses are carried out by specially-equipped laboratories. 
Irrespective of any legal regulations, a water analysis must be
carried out to establish conclusively whether the ground water
is compatible for the evaporator of a heat pump (see table).
If one characteristic is negative “-” or two characteristics are
“0”, the water quality is not sufficient for the heat pump.
If the necessary water quality is not achieved or if this cannot be
guaranteed long-term, we recommended installing a brine-to-
water heat pump equipped with an intermediate circuit.

Table:

Resistance of copper-soldered stainless steel plate heat ex-
changers to substances contained in the water
+

Normally good resistance

0

Corrosion problems can arise,
particularly if several factors receive an evaluation of “0”

-

Should not be used

[<: less than, >: greater than]

Evaluation characteristic

Approximate 

concentration 

range (mg/l)

Evaluation of 

the copper 

Substances that can settle (org.)

0

Ammonia NH

3

< 2

2 to 20

> 20

+

0

-

Chloride

< 300

> 300

+

0

Electrical conductivity

< 10 

 S/cm

10 to 500 

 S/cm

> 500 

 S/cm

0

+

-

Iron (Fe), dissolved

< 0.2

> 0.2

+

0

Free (aggr.) carbonic acid

< 5

5 to 20

> 20

+

0

-

Manganese (Mn), dissolved

< 0.1

> 0.1

+

0

Nitrate (NO

3

), dissolved

< 100

> 100

+

0

PH value

< 7.5

7.5 to 9

> 9

0

+

0

Oxygen

< 2

> 2

+

0

Hydrogen sulphide (H

2

S)

< 0.05

> 0.05

+

-

HCO

3

-/SO

4

2

-

> 1

< 1

+

0

Hydrogen carbonate (HCO

3

-)

< 70

70 to 300

> 300

0

+

0

Aluminium (Al), dissolved

< 0.2

> 0.2

+

0

Sulphate

< 70

70 to 300

> 300

+

0

-

Sulphite (SO

3

), free

< 1

+

Chlorine gas (Cl

2

)

< 1

1 to 5

> 5

+

0

-

Содержание WI 120TU

Страница 1: ...und Gebrauchsanweisung Wasser Wasser W rmepumpe f r Innenaufstellung Installation and Operating Instruction Water to Water Heat Pump for Indoor Installation Instuctionsd installation et d utilisation...

Страница 2: ......

Страница 3: ...eraturf hler DE 7 7 5 Elektrischer Anschluss DE 9 8 Inbetriebnahme DE 10 8 1 Allgemeine Hinweise DE 10 8 2 Vorbereitung DE 10 8 3 Vorgehensweise bei Inbetriebnahme DE 10 9 Pflege Reinigung DE 11 9 1 P...

Страница 4: ...salztem Wasser ist darauf zu achten dass der minimal zul ssige pH Wert von 7 5 minimal zul ssiger Wert f r Kupfer nicht unterschritten wird Eine Unterschreitung kann zur Zerst rung der W rmepumpe f hr...

Страница 5: ...chultes Personal zu ber pr fen und zu protokollieren N here Angaben dazu befinden sich im beiliegenden Logbuch 1 4 Energiesparende Handhabung der W rmepumpe Durch das Betreiben dieser W rmepumpe trage...

Страница 6: ...Au entempe ratur mit Befestigungsmaterial sowie ein Schmutzf nger liegen der W rmepumpe bei Die Zuleitung f r Last und Steuerspan nung ist bauseits zu verlegen Die Umw lzpumpen Heizungspumpe im Liefer...

Страница 7: ...folgende Netzwerkver bindungen m glich Modbus EIB KNX Ethernet ACHTUNG Bei einer externen Ansteuerung der W rmepumpe bzw der Umw lzpumpen ist ein Durchflussschalter vorzusehen der das Einschalten des...

Страница 8: ...zungsseitiger Installation ist die Heizungsan lage zu f llen zu entl ften und abzudr cken ACHTUNG Der maximale Pr fdruck betr gt heiz und prim rseitig 6 0 bar Dieser Wert darf nicht berschritten werde...

Страница 9: ...ist zwingend im Vorlauf Austritt der W rmequelle einzubauen Dabei ist das hydraulische Einbindungsschema zu beachten 7 4 Temperaturf hler Folgende Temperaturf hler sind bereits eingebaut bzw m s sen...

Страница 10: ...mit Schlauchschelle befestigen gut festziehen lose F hler f hren zu Fehlfunktionen und thermisch isolieren 7 4 4 Verteilsystem Hydraulik Kompaktverteiler und doppelt differenzdruckloser Verteiler fung...

Страница 11: ...stens 3 mm Kontakt ffnungsab stand z B EVU Sperrsch tz Leistungssch tz sowie ein allpo liger Sicherungsautomat mit gemeinsamer Ausl sung aller Au enleiter vorzusehen Ausl sestrom und Charakteristik ge...

Страница 12: ...und ein maximaler Anlaufstrom von 12 A der elektronisch geregelten Umw lzpumpe nicht berschritten wird oder es liegt eine ausdr ckliche Freigabe des Pumpenherstellers vor ACHTUNG Es ist nicht zul ssig...

Страница 13: ...egende Schmutzf nger zu montieren um den Verdampfer gegen Verunreinigungen zu sch tzen Im W rmequelleneintritt der W rmepumpe ist ein Schmutzf n ger montiert um den Verdampfer gegen Verunreinigungen z...

Страница 14: ...ndigen Kundendienst ACHTUNG Arbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden ACHTUNG Vor ffnen des Ger tes sind alle Stromkreise spannungsfrei...

Страница 15: ...essungen Gewicht und F llmenge 5 1 Ger teabmessungen2 H x B x L mm 1890 x 1350 x 750 5 2 Gewicht der Transporteinheit en inkl Verpackung kg 604 5 3 Ger teanschl sse f r Heizung Zoll Rp 2 5 4 Ger teans...

Страница 16: ...Leistungszahlen gelten mit den im Lieferumfang enthaltenen Umw lzpumpen 1 Typ und Verkaufsbezeichnung WI 180TU 2 Bauform W rmequelle Wasser 2 1 Ausf hrung Universal 2 2 Regler integriert 2 3 W rmemen...

Страница 17: ...4 5 bei W10 W35 kW 94 3 5 8 180 1 5 6 1 Der angegebene Schalldruckpegel entspricht dem Betriebsger usch der W rmepumpe im Heizbetreib bei 55 C Vorlauftemperatur Der angegebene Schalldruckpegel stellt...

Страница 18: ...x mg kWh Angegebenes Lastprofil Warmwasserbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qfuel kWh Kontakt Wird der Cdh Wert nicht durch Messung bestim...

Страница 19: ...asserbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qfuel kWh Kontakt Wird der Cdh Wert nicht durch Messung bestimmt gilt f r den Minderungsfaktor der...

Страница 20: ...ne Teile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert verg ten...

Страница 21: ...EN 7 7 4 Temperature sensor EN 7 7 5 Electrical connection EN 9 8 Commissioning EN 10 8 1 General Information EN 10 8 2 Preparation EN 10 8 3 Commissioning procedure EN 10 9 Cleaning maintenance EN 1...

Страница 22: ...o ensure that the minimum permissible pH value of 7 5 minimum permissible value for copper is complied with Failure to comply with this value can result in the heat pump being destroyed ATTENTION It i...

Страница 23: ...pections must be recorded More information can be found in the accompanying log book 1 4 Energy efficient use of the heat pump By operating this heat pump you are helping to protect our en vironment B...

Страница 24: ...n cluding fixing accessories and a dirt trap are supplied with the heat pump The supply for the supply voltage and the control voltage must be installed by the customer The circulating pumps included...

Страница 25: ...tions can be made on the heat pump manager Modbus EIB KNX Ethernet ATTENTION If the heat pump or circulating pumps are controlled externally a flow rate switch is required to prevent the compressor fr...

Страница 26: ...illed de aerated and pressure tested ATTENTION The maximum test pressure in the heating circuit and the primary circuit is 6 0 bar This value must not be exceeded The following points must be observed...

Страница 27: ...flow outlet of the heat source The hydraulic integration diagram must be adhered to 7 4 Temperature sensor The following temperature sensors are already installed or must be installed additionally Ou...

Страница 28: ...with a hose clip tighten firmly as loose sensors can cause malfunctions and thermally insulate 7 4 4 Hydraulic distribution system The compact manifold and the dual differential pressureless manifold...

Страница 29: ...l pole circuit breaker with common tripping for all external conductors must be installed in the power supply for the heat pump tripping current and characteristic in compli ance with the device infor...

Страница 30: ...of 2 A and a maximum starting current of 12 A are not exceeded in the electronically regulated circulating pump or if express approval has been is sued by the pump manufacturer ATTENTION It is not per...

Страница 31: ...bserved 9 3 Cleaning the heat source system ATTENTION The supplied dirt trap must be inserted in the heat source inlet of the heat pump to protect the evaporator against the ingress of impurities The...

Страница 32: ...nician ATTENTION Work on the heat pump must only be performed by authorised and qualified after sales service technicians ATTENTION Disconnect all electrical circuits from the power source prior to op...

Страница 33: ...ensions 2 H x W x L mm 1890 x 1350 x 750 5 2 Weight of the transportable unit s incl packaging kg 604 5 3 Device connections for heating inches Rp 2 5 4 Device connections for heat source Inches Rp 2...

Страница 34: ...integrated 2 3 Thermal energy meter Integrated 2 4 Installation location Indoors 2 5 Performance levels 2 3 Operating limits 3 1 Heating water flow C 20 to 62 2 3 2 Cold waterRC heat source C 7 to 25...

Страница 35: ...ents the free sound area level The measured value can deviate by up to 16 dB A depending on the installation location 2 Note that additional space is required for pipe connections operation and mainte...

Страница 36: ...m h Emissions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is...

Страница 37: ...mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen t...

Страница 38: ...EN 18 452237 66 53 FD 9912 www gdts one English WI 120TU WI 180TU...

Страница 39: ...FR 7 7 4 Sonde de temp rature FR 7 7 5 Branchements lectriques FR 9 8 Mise en service FR 10 8 1 Remarques d ordre g n ral FR 10 8 2 Pr paratifs FR 10 8 3 Proc dures suivre lors de la mise en service...

Страница 40: ...d eau enti rement d min ralis e ce que le seuil inf rieur admis pour la valeur pH minimale de 7 5 valeur minimale admise pour le cuivre ne soit pas d pass Un tel d passement peut entra ner la destruct...

Страница 41: ...crit par un personnel form Vous trouverez plus d informations ce sujet dans le journal de bord ci joint 1 4 Utilisation de la pompe chaleur pour conomiser de l nergie En utilisant cette pompe chaleur...

Страница 42: ...emp rature ext rieure et son mat riel de fixation ainsi qu un collecteur d impuret s sont livr s avec la pompe chaleur Le c ble d alimentation pour la tension de charge et de com mande doit tre pos pa...

Страница 43: ...les pour le gestionnaire de pompe chaleur sont les suivantes Modbus EIB KNX Ethernet ATTENTION En cas de commande externe de la pompe chaleur ou des circulateurs pr voir un commutateur de d bit servan...

Страница 44: ...rouv e la pression ATTENTION La pression d preuve maximale s l ve c t chauffage et circuit primaire 6 0 bars de surpession Cette valeur ne doit pas tre d pass e Respecter les consignes suivantes lors...

Страница 45: ...ie de la source de chaleur Suivre pour cela les indications du sch ma d int gration hy draulique 7 4 Sonde de temp rature Les sondes de temp rature suivantes sont d j mont es ou doivent tre install es...

Страница 46: ...couche La sonde doit tre fix e avec un collier serrer fond des sondes mal fix es engendrent des d fauts et isol e ther miquement 7 4 4 Syst me de distribution hydraulique Le distributeur compact et l...

Страница 47: ...blage est mal effectu la pompe chaleur ne peut pas d marrer Un avertissement correspondant s affiche sur le gestionnaire de pompe chaleur changer le c blage Sur l alimentation de puissance de la pompe...

Страница 48: ...onstances peuvent r duire la dur e de vie du gestionnaire de pompe chaleur C est la raison pour laquelle un relais de couplage est install doit tre install entre la sortie du gestionnaire de pompe cha...

Страница 49: ...ompe chaleur Il faut ensuite soigneusement rincer les tuyauteries l aide de produits neutralisants ad quats afin d viter tous dommages provoqu s par d ventuels restes de produit de nettoyage dans le s...

Страница 50: ...ent tre mis hors tension 11 Mise hors service limination Avant de d monter la pompe chaleur il faut mettre la ma chine hors tension et fermer toutes les vannes Le d montage de la pompe chaleur doit tr...

Страница 51: ...x 750 5 2 Poids de l unit ou des unit s de transport emballage compris kg 604 5 3 Raccordements de l appareil pour le chauffage pouces Rp 2 5 4 Raccordements de l appareil pour la source de chaleur po...

Страница 52: ...er 6 Les coefficients de performance s appliquent aux circulateurs contenus dans les fournitures 1 D signation technique et r f rence de commande WI 180TU 2 Design Source de chaleur Eau 2 1 Version Un...

Страница 53: ...4 4 5 pour W10 W35 kW 94 3 5 8 180 1 5 6 1 Le niveau de pression sonore indiqu correspond au bruit de fonctionnement de la pompe chaleur en mode chauffage avec une temp rature d part de 55 C Le niveau...

Страница 54: ...h Consommation journali re de combustible Qfuel kWh Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Exigences d...

Страница 55: ...l kWh Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Exigences d information pour les dispositifs de chauffage...

Страница 56: ...FR 18 452237 66 53 FD 9912 www gdts one Fran ais WI 120TU WI 180TU...

Страница 57: ...ma de connexion WI 120TU A XII 3 6 Legende Legend L gende WI 120TU A XIII 3 7 Steuerung Control Commande WI 180TU A XV 3 8 Steuerung Control Commande WI 180TU A XVI 3 9 Last Load Charge WI 180TU A XV...

Страница 58: ...g Lastleitung Netzspannung Aller eau de chauffage Sortie de la PAC R 2 1 2 Retour eau de chauffage Entr e dans la PAC R 2 1 2 Source de chaleur Entr e dans la PAC R 2 1 2 Source de chaleur Sortie de l...

Страница 59: ...scaldamento Uscita dalla pompa di calore R 2 1 2 Ritomo riscaldamento Ingesso nella pompa di calore R 2 1 2 Fonte di calore Ingresso nella pompa di calore R 3 Fonte di calore Uscita dalla pompa di cal...

Страница 60: ...ss in Pa Perte de pression en Pa Verdampfer Evaporator Evaporateur Druckverlust in Pa Pressure loss in Pa Perte de pression en Pa Leistungszahl incl Pumpenleistungsanteil Coefficient of performance in...

Страница 61: ...Pa Perte de pression en Pa Verdampfer Evaporator Evaporateur Druckverlust in Pa Pressure loss in Pa Perte de pression en Pa Leistungszahl incl Pumpenleistungsanteil Coefficient of performance incl po...

Страница 62: ...0 25 30 35 40 45 50 55 60 65 0 5 10 15 20 25 30 Heizwassertemperatur C Heating water temperature C Temp rature d eau chauffage C W rmequelleneintrittstemperatur C Heat source inlet temperature C Temp...

Страница 63: ...0 25 30 35 40 45 50 55 60 65 0 5 10 15 20 25 30 Heizwassertemperatur C Heating water temperature C Temp rature d eau chauffage C W rmequelleneintrittstemperatur C Heat source inlet temperature C Temp...

Страница 64: ...A VIII 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande WI 120TU...

Страница 65: ...www gdts one 452237 66 53 FD 9912 A IX WI 120TU WI 180TU Anhang Appendix Annexes 3 2 Steuerung Control Commande WI 120TU...

Страница 66: ...A X 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU 3 3 Last Load Charge WI 120TU...

Страница 67: ...www gdts one 452237 66 53 FD 9912 A XI WI 120TU WI 180TU Anhang Appendix Annexes 3 4 Anschlussplan Connection Plan Sch ma de connexion WI 120TU...

Страница 68: ...A XII 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU 3 5 Anschlussplan Connection Plan Sch ma de connexion WI 120TU...

Страница 69: ...t basse pression pompe chaleur eau glycol e eau F5 2 Niederdruckpressostat Wasser Wasser W rme pumpe Low pressure switch water to water heat pump Pressostat basse pression pompe chaleur eau eau F7 Hei...

Страница 70: ...me circuit de chauffage R24 R cklauff hler Prim rkreis Return sensor primary circuit Sonde retour circuit primaire R25 Drucksensor K ltekreis Niederdruck pO Pressure sensor for refrigerating circuit l...

Страница 71: ...www gdts one 452237 66 53 FD 9912 A XV WI 120TU WI 180TU Anhang Appendix Annexes 3 7 Steuerung Control Commande WI 180TU...

Страница 72: ...A XVI 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU 3 8 Steuerung Control Commande WI 180TU...

Страница 73: ...www gdts one 452237 66 53 FD 9912 A XVII WI 120TU WI 180TU Anhang Appendix Annexes 3 9 Last Load Charge WI 180TU...

Страница 74: ...A XVIII 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU 3 10 Anschlussplan Connection Plan Sch ma de connexion WI 180TU...

Страница 75: ...www gdts one 452237 66 53 FD 9912 A XIX WI 120TU WI 180TU Anhang Appendix Annexes 3 11 Anschlussplan Connection Plan Sch ma de connexion WI 180TU...

Страница 76: ...switch brin to water heat pump Pressostat basse pression pompe chaleur eau glycol e eau F5 2 Niederdruckpressostat Wasser Wasser W rme pumpe Low pressure switch water to water heat pump Pressostat ba...

Страница 77: ...regenerativ Raumf hler F hler 3 Heizkreis Renewable sensor room sensor sensor for heating circuit 3 Sonde mode r g n ratif sonde d ambiance sonde 3 me circuit de chauffage R24 R cklauff hler Prim rkre...

Страница 78: ...wasserbereitung Monovalent heat pump system with three heating circuits and domestic hot water preparation Installation monovalente de pompe chaleur avec trois circuits de chauffage et production d ea...

Страница 79: ...alent system with two heating circuits and domestic hot water preparation Installation bivalente avec deux circuits de chauffage et production d eau chaude sanitaire R1T DDV X3 R1 X2 M18 M18 K2 K21 E9...

Страница 80: ...tampon en s rie Warmwasserspeicher Hot water cylinder Ballon d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 2 l Gaskessel Oil gas boiler Chau...

Страница 81: ...ng Declaration of Conformity D claration de conformit Die aktuelle CE Konformit tserkl rung finden sie als Download unter You can find and download the current CE conformity declaration at Vous pouvez...

Страница 82: ...A XXVI 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU...

Страница 83: ...www gdts one 452237 66 53 FD 9912 A XXVII WI 120TU WI 180TU Anhang Appendix Annexes...

Страница 84: ...tschland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 9245...

Отзывы: