Dimplex SCx175sd Скачать руководство пользователя страница 8

 

8

 

 
7. Discharge arrangement. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
The T&P valve may be discharged vertically into the tundish, with the pressure relief valve T’d in from 
the side (see Fig 7.1 below). The Tundish must be installed in a position so that it is clearly visible by 
the user. In addition, the discharge pipe from the Tundish should terminate in a safe place where 
there is no risk to persons in the vicinity of the discharge, be of metal and: 
 

Fig 7.1 

(a) Be at least one pipe size larger than the normal outlet size of the safety device unless its total 
equivalent hydraulic resistance exceeds that of a straight pipe 9m long, i.e. discharge pipes between 
9m and 18m equivalent resistance length should be at least two sizes larger then the normal outlet 
size of the safety device, between 18m and 27m at least three sizes larger and so on. Bends must be 
taken into account in calculating the flow resistance. Refer to the diagram, tables and worked 
example detailed in Fig 7.3. 
(b) Have a vertical section of pipe at least 300mm long below the Tundish before any elbows or bends 
in the Pipework. 
(c) Be installed with a continuous fall. 
(d) Have discharges visible at both Tundish and the final point of discharge, but where this is not 
possible or practically difficult,

 

there should be clear visibility at one or other of these locations. 

Examples of acceptable discharge arrangements are:  

-

 

Ideally below a fixed grating and above the water seal in a trapped gully. 

-

 

Downward discharge at low level, i.e. up to 100mm above external surfaces such as car 
parks, hard standings, grassed areas, etc. providing that where children play or otherwise 
come into contact with discharges, a wire cage or similar guard is positioned to prevent 
contact whilst maintaining visibility. 

-

 

Discharge at high level, e.g. into a metal hopper and metal down pipe with the end of the 
discharge pipe clearly visible (Tundish visible or not) or onto a roof capable of withstanding 
high temperature discharges of water and being 3m from any plastic guttering system that 
would collect such discharges. 

-

 

Where a single pipe serves a number of discharges such as in blocks of flats, the number 
served should be limited to not more than six systems so that any installation discharging 
can be traced reasonably easily. The single common discharge pipe should be at least 
one pipe size larger than the largest individual discharge pipe to be connected. If unvented 
hot water stored systems are installed where discharges from safety devices may not be 
apparent i.e. in dwellings occupied by blind, or disabled people, consideration should be 
given to the installation of an electrically operated device to warn when discharge takes 
place. 

 

T&P Valve

Pressure 
Relief Valve

15mm

15mm

15mm

22mm

Tundish

Содержание SCx175sd

Страница 1: ...SOLAR UNVENTED WATER HEATERS Installation and Operation Manual Important This Manual Should Be Left With The Cylinder After Installation...

Страница 2: ...quirements 5 5 Primary circuit installation 6 6 Secondary circuit installation 6 7 Discharge arrangement 8 8 Electrical installation 10 9 Filling and commissioning 11 10 Servicing and maintenance 12 1...

Страница 3: ...42 542 542 542 542 542 Solar Return mm 380 380 380 380 380 380 380 380 Cold Inlet mm 300 300 300 300 300 300 300 300 solar Coil size sqm 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Aux Coil size sqm 0 75 0 75 0 7...

Страница 4: ...4 2 2 Connection 2 2 1 SOLAR Indirect 2 2 2 Single Coil Direct Electric...

Страница 5: ...it to function but flow from the outlets will be low if several outlets are used simultaneously Correct performance is achieved with supplies between 3bar and 12bar The cylinder control equipment is f...

Страница 6: ...nce with the solar installation instructions for connection to the primary flow and return 5 3 Two port Motorised valves The SCx Solar range of cylinders must only be connected to solar installations...

Страница 7: ...ve should be connected to the secondary return of the cylinder See fig 4 1 4 2 IMPORTANT If a secondary circulation circuit is installed then a larger expansion vessel may be required to handle the in...

Страница 8: ...lity at one or other of these locations Examples of acceptable discharge arrangements are Ideally below a fixed grating and above the water seal in a trapped gully Downward discharge at low level i e...

Страница 9: ...diameter temperature relief valve with a discharge pipe D2 having 4 elbows and a length of 7m from the tundish to the point of discharge From the table above the maximum resistance allowed for a strai...

Страница 10: ...the following should also be observed 8 2 1 Ensure the mains voltage corresponds to the voltage rating of the immersion heater as shown on the rating label on the terminal cover 8 2 2 Insert the imme...

Страница 11: ...3 8 4 The Power Supply to the pump station should be connected via the lower 9 Filling and commissioning 9 1 Check that the expansion vessel charge pressure is 3bar 9 2 Check that all connections are...

Страница 12: ...k that the immersion or boiler switches off when the cylinder reaches the desired temperature 10 Servicing and maintenance 10 1 Servicing and maintenance must only be carried out by a competent unvent...

Страница 13: ...ked 3 Pressure reducing valve PRV fitted the wrong way 1 Open stopcock 2 Turn water supply off remove strainer and clean see 10 6 3 Re fit with arrow pointing in direction of flow Water from hot taps...

Страница 14: ...ntrols supplied with the cylinder excluding the immersion for a period of 5 years from the date of purchase provided that they have been installed for their intended use by a competent person and have...

Страница 15: ...m straight tundish SC06004 3kW Immersion heater SC070011 or SC070012 22mm Pressure reducing valve kit SC07015 22mm 2 port motorised valve SC06005 Twin Cylinder Thermostat SC06006 For assistance please...

Страница 16: ...f practice It is recommended that your hot water system is serviced regularly and that your service engineer completes the appropriate Service Interval Record below SERVICE 1 DATE SERVICE 2 DATE ENGIN...

Отзывы: