MOUNTING

COMMISSIONING

6.3

Electrical Connection

The power connection of the heat pump is effected
via a commercially available 4-core cable.

The cable has to be supplied by the client and the
wire cross-section to be selected according to the
power consumption of the heat pump (see Equip-
ment Data in the appendix) as well as the relevant
VDE (EN) and VNB regulations.

T h e   p o w e r   s u p p l y   o f   t h e   h e a t   p u m p   m u s t   b e
equipped with an all-pole disconnecting device with
a contact gap of at least 3 mm (e.g. utility company
shut-off contactor, power contactor) as well as a 3-
pole circuit breaker with simultaneous tripping of all
external conductors (tripping current as stated on
the device data plate).

W h e n   m a k i n g   t h e   e l e c t r i c a l   c o n n e c t i o n ,   t h e
clockwise phase sequence of the power supply must
be ensured.

Phase sequence: L1, L2, L3.

Clockwise phase sequence to be

observed: Damage to the compressor may be
incurred if it is operated in the wrong sense of
rotation.

The control voltage is supplied via the heat pump
controller.

The 230V AC-50 Hz power supply of the heat pump
controller is effected as described in its instruction
manual (fusing 16 A).

The control lead (not included in the scope of
delivery) is connected to the heat pump controller
via a multi-pole plug connector. In the heat pump,
the plug connector located at the bottom of the unit
in the immediate vicinity of the line feed-through
t h r o u g h   t h e   b a s e   o f   t h e   u n i t .   M o r e   d e t a i l e d
instructions are contained in the instruction manual
of the heat pump controller.

For more detailed information refer to the wiring
diagrams in the appendix.

COMMISSIONING

7.1

General

To ensure proper commissioning it should be
carried out by an after-sales service authorized by
the manufacturer. Only then can an extended
warranty period of 3 years in total be granted (cf.
Warranty service).

7.2

Preparatory Steps

Prior to commissioning, the following items need to
be checked:

- All connections of the heat pump must have been

made as described in Chapter 6.

- In the heating circuit all valves that could impair

the proper heating water flow must be open.

- T h e   a i r   i n t a k e / d i s c h a r g e   p a t h   m u s t   b e

unobstructed.

- The sense of rotation of the fan must correspond

to the direction of the arrow.

- The settings of the heat pump controller must be

adapted to the heating installation in accordance
with the instructions contained in its instruction
manual.

- Proper condensate drainage must be ensured.

7.3

Procedure During Heating Season

The

 

start-up of the heat pump is effected via the heat

pump controller. The settings must be made in
accordance with its instruction manual.

Malfunctions during operation are displayed on the
heat pump controller and may be corrected as
described in the heat pump controller's instruction
manual.

n the case of outdoor temperatures below 10 

°

C

and heating water temperatures below 16 

°

C, the

b u f f e r   t a n k   h a s   t o   b e   h e a t e d   t o   a t   l e a s t
30 

°

C using the second heat generator.

The following procedure has to be observed so that
the commissioning activities can be carried out
without any problems:

a)

Close all heating circuits.

b)

Open the overflow valve all the way.

c)

Select the automatic mode on the controller.

d)

W a i t   u n t i l   t h e   b u f f e r   t a n k   h a s   r e a c h e d   a
temperature of 25-30 

°

C.

e)

Subsequently, slowly reopen the valves of the
heating circuits, one after the other, in such a
w a y   t h a t   t h e   h e a t i n g   w a t e r   f l o w   r a t e   i s
continually increased by slightly opening the
related heating circuit valve. When so doing, the
heating water temperature in the buffer tank
must not fall below 25 

°

C so that the heat pump

can be defrosted at any time.

CAUTION!

7

Содержание LA 16ASR

Страница 1: ...CE MOUNTING and OPERATING MANUAL Reversible Air to Water Heat Pump for Outdoor Installation LA16ASR Order No 452158 66 21 FD 8507...

Страница 2: ...N 6 5 1 General 5 2 Condensate Line 6 MOUNTING 6 7 6 1 General 6 2 Heating and Hot Water Connection 6 3 Electrical Connection 7 COMMISSIONING 7 8 7 1 General 7 2 Preparation 7 3 Procedure During Heati...

Страница 3: ...oling system all relevant regulations have to be complied wit 1 3 Energy Efficient Use of the Heat Pump By purchasing this heat pump you contribute to the protection of the environment A prerequisite...

Страница 4: ...us mode of operation a heating water return temperature of more than 18 C must be maintained in order to ensure proper defrosting of the evaporator The heat pump is not designed for any increased heat...

Страница 5: ...vices The external temperature sensor to be mounted by the customer incl fastening hardware is shipped with the controller Method of functioning and operation of the heat pump controller are described...

Страница 6: ...Heating and Hot Water Connection The connections on the heating side of the heat pump are provided with 1 external thread The hoses to be connected exit the unit through its bottom When carrying out t...

Страница 7: ...service authorized by the manufacturer Only then can an extended warranty period of 3 years in total be granted cf Warranty service 7 2 Preparatory Steps Prior to commissioning the following items nee...

Страница 8: ...ctions in the heat exchanger of the heat pump caused by dirt deposits care must be taken that the heat exchanger cannot become contaminated in the heating installation In the event that operating malf...

Страница 9: ...l and reinstallation of the panel assemblies to be performed as described in Chapter 4 When cleaning do not use any sharp or hard objects so as to prevent any damage to the evaporator and the condensa...

Страница 10: ...S 11 3 1 Heating Mode 13 11 3 2 Cooling Mode 14 11 4 WIRING DIAGRAMS 11 4 1 Control 15 11 4 2 Load 16 11 4 3 Terminal Diagram 17 11 4 4 Legend 18 11 5 HYDRAULIC BLOCK DIAGRAM 19 11 6 EC DECLARATION OF...

Страница 11: ...11 Dimension Drawing APPENDIX 11 1 DIMENSION DRAWING...

Страница 12: ...12 Equipment Data APPENDIX 11 2 EQUIPMENT DATA...

Страница 13: ...13 11 3 1 Heating Mode APPENDIX 11 3 SCHEMATICS...

Страница 14: ...14 11 3 2 Cooling Mode APPENDIX 11 3 SCHEMATICS...

Страница 15: ...N D X 7 2 X 7 6 X 7 8 X 5 A l l e Q u e r s c h n i t t e 0 7 5 m m 2 2 4 2 4 2 4 1 3 5 4 6 2 2 2 1 2 2 E 4 A 1 C 4 P 2 B 1 8 X 2 1 4 X 2 7 X 2 8 X 2 8 X 2 8 X 2 1 1 X 2 1 2 X 2 1 3 X 2 1 0 X 2 1 0 X...

Страница 16: ...n P E g e g n L 3 3 N e t z 2 1 L 2 L 1 4 3 2 1 L 3 L 1 L 2 X 1 P E P E V e r t e i l e r M 3 M 1 V U W 2 4 R S 6 T 1 3 5 F 2 3 1 2 3 M 2 M 4 3 N 3 K 1 1 4 2 1 6 K 2 1 5 5 A l l e Q u e r s c h n i t...

Страница 17: ...mern Ader und Pinnummern X5 7 7 8 8 9 6 5 6 3 4 5 4 3 2 1 2 1 X4 X7 1 5 1 4 1 6 1 3 1 0 1 4 1 2 1 3 1 2 1 1 1 0 9 1 1 1 7 1 8 1 9 1 8 1 7 1 6 1 5 X5 X6 2 1 2 0 2 2 2 0 2 3 2 4 2 4 2 3 2 2 2 1 1 9 X6 7...

Страница 18: ...1 Compressor M2 Fan N1 Heat pump controller N3 Soft start control R9 Frost protection sensor for heating water R10 Heating water return flow sensor R11 Coding resistor 5k6 X1 Terminal strip load termi...

Страница 19: ...ation Absperrventil mit Entw sserung M N1 N2 AUF EV HUP HUPR HPN KW MAN MZN NKF SUP WE WUP WW WWF W rmepumpe Pufferspeicher Warmwasserspeicher Pufferspeicher f r Abw rme W rmepumpenregler Elektroverte...

Страница 20: ...ents of the applicable EC directives This declaration becomes invalidated if any modifications are made to the product s without our prior authorization Designation of the product s EC Directives Air...

Страница 21: ...Notes 21...

Страница 22: ...Notes 22...

Страница 23: ...Notes 23...

Страница 24: ...KKW Kulmbacher Klimager te Werk GmbH Technical data subject to change without notice Gesch ftsbereich Dimplex Fax 49 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Отзывы: