Section 3: System controls in a domestic setting 

Boiler inter lock 

The Domestic heating compliance guide sets out the best 
practise  for  preventing  energy  wastage  by  preventing 
unnecessary  running  of  the  circulation  pump  and  heat 
pump. 

 

Figure 3: Extract from Domestic Heating compliance guide, 

V1 April 2006 

Horstmann PRT thermostat 

The  LA  MI  range  of  heat  pumps  achieves  boiler  interlock 
using the PRT thermostat. 

Supplied by Horstmann, the mains powered thermostat is 
designed  to  provide  an  economical  but  comfortable 
pattern  of  heating  without  the  need  for  complex 
adjustments  by  the  user.  With  built  in  minimum  room 
temperature protection this thermostat is ideal for use with 
heat pumps because it maintains a base level of heat. 

 

For day-to-day use only the 3 large buttons on the front of 

the  thermostat  are  required.  The  centre  „WARM/COOL‟ 

button,  complete  with  Braille  markings,  changes  the 
temperature  state  and  the 

„+‟  and  „

-

„ buttons provide  fine 

user  adjustment  as  well  as  audible  feedback.  Each  user 
adjustment  is  immediately  reflected  in  changes  to  the 
bright red and blue LED display. 

Using a variety of pre-installed heating profiles that can be 
easily  set  up by  the  installer, and  a  minimum  cool  setting 

of  15

C,  the  ThermoPlus  aims  to  provide  maximum 

comfort  to  the  user  and  prevent  hypothermia  and  keep  a 
level of background heat. Under the flap the blue standby 

button will put the control into „frost protection‟ mo

de until 

reactivated. 

Heat Pump Controller 

The heat pump‟s safe and efficient operation is regulated 

by  the  built  in  controller.  The  remote  panel  can  be 
connected via the 15m cable meaning allowing the user to 
adjust the heat pump settings.  

 

 

Weather compensation 

The highest flow temperatures are only required during the 
coldest  weather.  As  the  external  temperature  increases, 
the heat loss of the build decreases which means that the 
heat  emitters  no  longer  have  to  work  at  their  maximum 
output  in  order  to  keep  the  building  at  the  correct 
temperature.  

The LA MI is fitted with a weather compensation curve as 
shown  in  Figure  4.  The  curve  can  be  adjusted  depending 
on  the  system  characteristics.  By  activating  weather 
compensation  it  ensures  the  heat  pump  is  always 
operating  at  the  minimum  flow  temperature  and  therefore 
the maximum efficiency. 

 

Figure 4: Weather compensation curve on the LA MI

 

Recommended  controller  settings  can  be 
found  in  the  installation  instructions.  An 
explanation of how to set the controller can be 
found in the programming overview document.

 

 

 

 

External controls should include: 

  Room  thermostat  to  regulate  the  space 

temperature  and  interlocked  with  the  heat 
pump unit operation. 

  Timer  to  optimise  operation  of  the  heat 

pump 

An interlock is defined as “controls which are 

wired  so  that  when  there  is  no  demand  for 
either  space  heating  or  hot  water,  the  boiler 
and pump are switched off. 

The  use  of  Thermostatic  radiator  valves 
alone does not provide interlock. 

 

Содержание LA 12 MI

Страница 1: ...may be of use to you and is available 24 hours a day It includes Operating and installation instructions Easy How to use guides for storage heaters Service and repairs Where to buy our products Liter...

Страница 2: ...LA 6 MI LA 9 MI LA 12 MI LA 16 MI Inverter air to water heat pump for outdoor installation Technical planning manual 08 60393 0...

Страница 3: ...at pump system packages LA MI settings function programming overview EC eau cylinders SmartRad User guides Contains the necessary information for the user for operation and maintenance of the system A...

Страница 4: ...example 2 10 Section 3 System controls in a domestic setting 11 Boiler inter lock 11 Horstmann PRT thermostat 11 Heat Pump Controller 11 Weather compensation 11 Section 4 Selection of heat emitters an...

Страница 5: ...lushing the system 22 Filter 23 Filling the system 23 De aeration 23 Adjusting the water flow rate 23 Expansion vessel sizing 23 2 port valves 24 Controlling DHW temperature 24 Section 8 Electrical Co...

Страница 6: ...9 LA 6 MI performance 40 LA 9 MI performance 42 LA 9 MI performance continued 43 LA 12 MI performance 44 LA 16 MI performance 46 Product Dimensions LA 6 MI and LA 9 MI 48 Product Dimensions LA 12 MI a...

Страница 7: ...y due to their physical sensory or mental abilities or due to their inexperience or lack of knowledge must not operate this device without supervision or instruction by the person in charge Air as a h...

Страница 8: ...k in the optimum zone because it modulates its output to match the heat demand The over driving of an inverter compressor causes it efficiency to drop Since the output of both the fixed and inverter c...

Страница 9: ...ement the heat load Integration of another boiler such as gas oil or LPG is not possible with the LA MI but is possible with Dimplex s WPM range Accurately determining the building s heat loss It is e...

Страница 10: ...request this service a form can be downloaded from our website that should be sent in with the following information Plan and elevation drawings scale 1 50 or 1 100 Construction U values Type of schem...

Страница 11: ...14511 for the LA 6 MI for a heat loss of 4 5kW at a design temperature of 3 C Sizing example 2 Design temperature The property is in Birmingham England NHBC recommend 3 C and MIS 3005 recommend 3 4 C...

Страница 12: ...lap the blue standby button will put the control into frost protection mode until reactivated Heat Pump Controller The heat pump s safe and efficient operation is regulated by the built in controller...

Страница 13: ...h a flow temperature of 60 C as a flow temperature of 50 C would give the necessary output without causing the radiator to become excessively large Red areas show that this technology is not suitable...

Страница 14: ...ing benefits The buffer acts as an excellent air separator and putting at the top of the cylinder means it is likely to be one of the highest points in the system allowing air to easily be removed The...

Страница 15: ...hould be noted that the cylinder reheat times will be longer with a heat pump compared to a typical gas boiler This is because a gas boiler is often drastically oversized compared to the space heating...

Страница 16: ...r does not remain stagnant for long period of time If the property is not occupied for a long period upon reoccupation it would be prudent to raise the cylinder temperature to 60 C and open the water...

Страница 17: ...s that are capable of taking the unit s weight and draining the condensate To prevent tipping the heat pump must be suitably fixed The fixing should be strong enough to prevent the unit from tipping o...

Страница 18: ...d in Figure 9 should be observed For example if the unit is installed on a balcony there must be a space measuring 1000mm in front of the unit of maintenance Figure 9 Minimum clearances for maintenanc...

Страница 19: ...I 61 5 dB A 2m 3m 4m LA 12 MI 62 0dB A 2m 3m 4m LA 16 MI 64 0dB A 3m 4m 5m Table 10 Minimum distances to achieve 42dB if there is a wall between the heat pump and assessment position A weighted sound...

Страница 20: ...than the property The heat pump is installed above the level of the ground storey The heat pump is used solely for heating purposes external unit is greater than 0 6 m 3 in size all LA MI units pass...

Страница 21: ...conservation area or would be within a World Heritage Site or the curtilage of a listed building In addition before beginning the development the developer must apply to the planning authority to det...

Страница 22: ...on the pump should run of the lowest speed possible whilst still achieving the correct flow rate The resistance of all the pipe fittings filter heat emitters and condenser must be taken into account F...

Страница 23: ...perature and the installer should ensure the glycol is vented to a suitable place to prevent contamination of the environment or sewage system in the event the pressure relief valve activating Condens...

Страница 24: ...water flow around the system Every high point in the system should have a means of bleeding out air which is supplied by the installer The pressure relief valve shown in Figure 17 can be used to purg...

Страница 25: ...tion thermostat and high limit stat are wired in series To keep the contacts closed on the regulation stat the dial must be set to maximum The contacts on the high limit stat will remain closed during...

Страница 26: ...munication cable for 2 way valves high limit stat etc room thermostat 4 Domestic hot water sensor 5 Domestic hot water immersion heater booster heater Ducting should be used to ensure that the enclose...

Страница 27: ...inity of the heat pump The isolating device must have a contact gap of at least 3mm In addition to the maintenance isolator an automatic 2 pole automatic circuit breaker should be installed The maximu...

Страница 28: ...13A 47 50 34 50 LA 9 MI 23A 26A 13A 49 50 36 50 RCCD 1 RCCD 2 RCCD 3 MCB Compressor controller In line flow boiler DHW immersion switched by heat pump DHW immersion switched by a relay controlled by...

Страница 29: ...shown in Figure 23 This would mean that the cable from the heat pump to the cylinder could have a lower current rating and therefore could be combined with the multi core cable rather than run a separ...

Страница 30: ...the scope of supply The power for the controller is supplied from the heat pump Figure 24 Connection terminals on the controller cable to controller inside the property The controller cable is connect...

Страница 31: ...able is essential to provide boiler interlock to comply with building regulations Tank OLP If the heat pump is doing DHW the over load protection is connected to the manually resettable high limit sta...

Страница 32: ...mp efficiency Section 10 Standard packages To assist with the design and installation of a system Dimplex have collated wiring and hydraulic schematics for the following designs Package 1 and 2 Heatin...

Страница 33: ...PK2LA 12 MI 300 PK2LA 16 MI 250 PK2LA 16 MI 300 PK3LA 6 MI PK3LA 9 MI PK3LA 12 MI PK3LA 16 MI Component parts of kits LA 6 MI 1 1 1 1 LA 9 MI 1 1 1 1 LA 12 MI 1 1 1 1 1 1 LA 16 MI 1 1 1 1 1 1 PRT1 wal...

Страница 34: ...ng centre to heat pump 2 core cable for connection of DHW sensor No 3 core cable for connection of DHW immersion heater to heat pump Depends upon schematic Either cable or relay required Depends upon...

Страница 35: ...Page 34 Package 1 and 2 Plumbing Schematic...

Страница 36: ......

Страница 37: ...g circuit for efficient and safe operation Pressure relief valve A safety device that relieves the pressure in the heating circuit if it exceeds 3 bar Inline flow boiler Additional heating capacity fo...

Страница 38: ...8 61 5 3 4 Sound pressure level at 1m with Q 2 to MCS 020 dB A 54 54 3 5 Heating water flow rate m h 1 1 6 3 6 Air flow m h 2800 3100 3 7 Refrigerant total filling weight Type kg R410A 1 45 R410A 1 45...

Страница 39: ...cant total filling quantity Type Litre FV50S PVE 1 2 FV50S PVE 1 2 4 Dimensions connections and weight 4 1 Device dimensions without connections H x W x L mm 1410 x 1280 x 320 1410 x 1280 x 320 4 2 De...

Страница 40: ...Page 39 CE declaration of conformity...

Страница 41: ...Page 40 LA 6 MI performance...

Страница 42: ...Page 41 LA 6 MI continued...

Страница 43: ...Page 42 LA 9 MI performance...

Страница 44: ...Page 43 LA 9 MI performance continued...

Страница 45: ...Page 44 LA 12 MI performance...

Страница 46: ...Page 45 LA 12 MI performance continued...

Страница 47: ...Page 46 LA 16 MI performance...

Страница 48: ...Page 47 LA 16 MI performance continued...

Страница 49: ...Page 48 Product Dimensions LA 6 MI and LA 9 MI...

Страница 50: ...Page 49 Product Dimensions LA 12 MI and LA 16 MI...

Страница 51: ...Page 50 LA 6 MI and LA 9 MI Spare parts Note the non numbered parts are not kept as standard service parts...

Страница 52: ...Page 51 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 53: ...Page 52 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 54: ...Page 53 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 55: ...Page 54 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 56: ...Page 55 LA 12 MI and LA 16 MI Spare parts Note the non numbered parts are not kept as standard service parts...

Страница 57: ...Page 56 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 58: ...Page 57 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 59: ...Page 58 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 60: ...Page 59 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 61: ...Page 60 Information for DHW cylinder with buffer ECS125HP 580...

Страница 62: ...Page 61 Information for DHW cylinder with buffer ECS150HP 75 580...

Страница 63: ...Page 62 Information for DHW cylinder with buffer ECS210HP 75 580...

Отзывы: