background image

 

 

 

Page 38 

 

 

 

 

Performance Data 

1

 

Type and order code

 

 

 

 

 

 

 

 

 

 

 

 

 

LA 12 MI

 

LA 16 MI

 

2

 

Design

 

 

 

 

 

 

 

 

 

 

 

 

2.1 

Degree of protection according to EN 60 529 for a compact unit or heating element 

IP 24 

IP 24 

2.2 

Installation location  

Outdoors 

Outdoors 

3

 

Performance Data 

 

 

 

3.1 

Operating temperature limits:    

  

  

  

  

  

 

 

 

Heating water flow / return flow 

  

  

  

°C 

  

Max. 55 / min. 25 

Max. 55 / min. 25 

 

Air 

  

  

  

  

  

  

  

°C 

  

-20 to+35 

-20 to+35 

3.2 

Heating water temperature difference 

  

at A7 / W35 

 K 

  

 

Heat output / COP (defrost)  

  

at A7 / W35 

1

  

kW / --- 

  

11.9 / 4.6 

15.9 / 4.1 

 

  

  

  

  

  

  

  

at A2 / W35 

1

  

kW / --- 

  

10.6 / 3.5 

13.7 / 3.0 

 

  

  

  

  

  

  

  

at A-7 / W35 

1

  

kW / --- 

  

12.3 / 2.9 

13.8 / 2.7 

 

  

  

  

  

  

  

  

at A7 / W55 

kW / --- 

  

11.1 / 2.9 

12.9 / 2.5 

 

  

  

  

  

  

  

  

at A2 / W55 

kW / --- 

  

9.2 / 2.3 

10.6 / 1.9 

 

  

  

  

  

  

  

  

at A-7 / W55 

kW / --- 

  

9.93 / 1.9 

9.5 / 1.7 

 

Heat output / COP (peak)  

  

at A7 / W35  

kW / --- 

  

12 / 4.7 

16 / 4.2 

 

  

  

  

  

  

  

  

at A2 / W35   

kW / --- 

  

12 / 3.9 

16 / 3.5 

 

  

  

  

  

  

  

  

at A-7 / W35  

kW / --- 

  

11.7 / 2.9 

14.1 / 2.7 

 

  

  

  

  

  

  

  

at A7 / W55 

kW / --- 

  

12 / 2.9 

14.5 / 2.7 

 

  

  

  

  

  

  

  

at A2 / W55 

kW / --- 

  

12 / 2.5 

12.5 / 2.3 

 

  

  

  

  

  

  

  

at A-7 / W55 

kW / --- 

  

10.5 / 1.9 

10.5 / 1.9 

3.3 

Sound power level  

  

  

  

  

  

dB(A) 

  

62 

64 

3.4 

Sound pressure level at 1m with Q=2 to MCS 020 

dB(A) 

 

54 

56 

3.5 

Heating water flow rate 

  

  

  

  

m³/h 

  

2.1 

2.8 

3.6 

Air flow    

  

  

  

  

  

  

m³/h 

  

4800 

5400 

3.7 

Refrigerant; total filling weight 

  

  

  

Type / kg 

  

R410A / 2.3 

R410A / 2.3 

3.8 

Lubricant; total filling quantity 

  

  

  

Type / Litre    

FV50S (PVE)) / 1.2 

FV50S (PVE)) / 1.2 

4

 

Dimensions, connections and weight 

 

 

 

4.1 

Device dimensions without connections    

  

H x W x L mm

 

1410 x 1280 x 320 

1410 x 1280 x 320 

4.2 

Device connections to heating system    

  

Inch

 

 

 

1 1/4" ext. thread 

1 1/4" ext. thread 

4.3 

Weight of the transportable unit(s) incl. packaging 

kg

 

 

 

165 

165 

5

 

Electrical Connection (Heat Pump)

 

 

 

 

 

 

5.1 

Nominal voltage 

  

  

  

 

 

230 

230 

5.2 

Nominal power consumption 

2

     A7 W35 

  

kW 

 

 

2.6 

3.9 

5.3 

Starting current 

  

  

 

 

N/A (Inverter driven) 

N/A (Inverter driven) 

5.4 

Power factor MCCB 1 at  A7 W35 / cos



 

  

     

A / --- 

 

 

0.96 

0.96 

Back up heater nominal power 
consumption  

        

kW 

 

 

6.0 

6.0 

7

 

Heating Water Circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.1 

Expansion Vessel  

  

  

        

Litre  / Bar    

10 / 3 

10 / 3 

7.2 

Pressure Relief Valve    

  

        

Bar 

  

Open 3.0 / Close 2.65 

Open 3.0 / Close 2.65 

7.3 

Free pressure, heating circulating pump (max speed) 

kPa 

  

83 

83 

8

 

Other design characteristics 

 

 

 

 

 

8.1 

Defrosting 

  

  

  

 

 

 

 

 

 

 

 

 

 

Automatic 

Automatic 

 

Type of defrosting 

  

  

 

 

 

 

 

 

 

 

 

 

Reverse Cycle 

Reverse Cycle 

8.2 

Heating water in device protected against freezing  

 

 

 

 

Yes 

yes 

8.3 

Controller internal / external   

 

 

 

 

 

 

 

 

 

 

External 

External 

 

1)

 

Abbreviations have the following meaning, e.g. A2 / W35: outside temperature 2°C and heating water supply temperature 35°C.  A2 / W35 test, takes 
into account defrosting as per EN 14511. 
  

2)

 

According to EN 12102, EN ISO 3744. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  

  

 

 

 

Содержание LA 12 MI

Страница 1: ...may be of use to you and is available 24 hours a day It includes Operating and installation instructions Easy How to use guides for storage heaters Service and repairs Where to buy our products Liter...

Страница 2: ...LA 6 MI LA 9 MI LA 12 MI LA 16 MI Inverter air to water heat pump for outdoor installation Technical planning manual 08 60393 0...

Страница 3: ...at pump system packages LA MI settings function programming overview EC eau cylinders SmartRad User guides Contains the necessary information for the user for operation and maintenance of the system A...

Страница 4: ...example 2 10 Section 3 System controls in a domestic setting 11 Boiler inter lock 11 Horstmann PRT thermostat 11 Heat Pump Controller 11 Weather compensation 11 Section 4 Selection of heat emitters an...

Страница 5: ...lushing the system 22 Filter 23 Filling the system 23 De aeration 23 Adjusting the water flow rate 23 Expansion vessel sizing 23 2 port valves 24 Controlling DHW temperature 24 Section 8 Electrical Co...

Страница 6: ...9 LA 6 MI performance 40 LA 9 MI performance 42 LA 9 MI performance continued 43 LA 12 MI performance 44 LA 16 MI performance 46 Product Dimensions LA 6 MI and LA 9 MI 48 Product Dimensions LA 12 MI a...

Страница 7: ...y due to their physical sensory or mental abilities or due to their inexperience or lack of knowledge must not operate this device without supervision or instruction by the person in charge Air as a h...

Страница 8: ...k in the optimum zone because it modulates its output to match the heat demand The over driving of an inverter compressor causes it efficiency to drop Since the output of both the fixed and inverter c...

Страница 9: ...ement the heat load Integration of another boiler such as gas oil or LPG is not possible with the LA MI but is possible with Dimplex s WPM range Accurately determining the building s heat loss It is e...

Страница 10: ...request this service a form can be downloaded from our website that should be sent in with the following information Plan and elevation drawings scale 1 50 or 1 100 Construction U values Type of schem...

Страница 11: ...14511 for the LA 6 MI for a heat loss of 4 5kW at a design temperature of 3 C Sizing example 2 Design temperature The property is in Birmingham England NHBC recommend 3 C and MIS 3005 recommend 3 4 C...

Страница 12: ...lap the blue standby button will put the control into frost protection mode until reactivated Heat Pump Controller The heat pump s safe and efficient operation is regulated by the built in controller...

Страница 13: ...h a flow temperature of 60 C as a flow temperature of 50 C would give the necessary output without causing the radiator to become excessively large Red areas show that this technology is not suitable...

Страница 14: ...ing benefits The buffer acts as an excellent air separator and putting at the top of the cylinder means it is likely to be one of the highest points in the system allowing air to easily be removed The...

Страница 15: ...hould be noted that the cylinder reheat times will be longer with a heat pump compared to a typical gas boiler This is because a gas boiler is often drastically oversized compared to the space heating...

Страница 16: ...r does not remain stagnant for long period of time If the property is not occupied for a long period upon reoccupation it would be prudent to raise the cylinder temperature to 60 C and open the water...

Страница 17: ...s that are capable of taking the unit s weight and draining the condensate To prevent tipping the heat pump must be suitably fixed The fixing should be strong enough to prevent the unit from tipping o...

Страница 18: ...d in Figure 9 should be observed For example if the unit is installed on a balcony there must be a space measuring 1000mm in front of the unit of maintenance Figure 9 Minimum clearances for maintenanc...

Страница 19: ...I 61 5 dB A 2m 3m 4m LA 12 MI 62 0dB A 2m 3m 4m LA 16 MI 64 0dB A 3m 4m 5m Table 10 Minimum distances to achieve 42dB if there is a wall between the heat pump and assessment position A weighted sound...

Страница 20: ...than the property The heat pump is installed above the level of the ground storey The heat pump is used solely for heating purposes external unit is greater than 0 6 m 3 in size all LA MI units pass...

Страница 21: ...conservation area or would be within a World Heritage Site or the curtilage of a listed building In addition before beginning the development the developer must apply to the planning authority to det...

Страница 22: ...on the pump should run of the lowest speed possible whilst still achieving the correct flow rate The resistance of all the pipe fittings filter heat emitters and condenser must be taken into account F...

Страница 23: ...perature and the installer should ensure the glycol is vented to a suitable place to prevent contamination of the environment or sewage system in the event the pressure relief valve activating Condens...

Страница 24: ...water flow around the system Every high point in the system should have a means of bleeding out air which is supplied by the installer The pressure relief valve shown in Figure 17 can be used to purg...

Страница 25: ...tion thermostat and high limit stat are wired in series To keep the contacts closed on the regulation stat the dial must be set to maximum The contacts on the high limit stat will remain closed during...

Страница 26: ...munication cable for 2 way valves high limit stat etc room thermostat 4 Domestic hot water sensor 5 Domestic hot water immersion heater booster heater Ducting should be used to ensure that the enclose...

Страница 27: ...inity of the heat pump The isolating device must have a contact gap of at least 3mm In addition to the maintenance isolator an automatic 2 pole automatic circuit breaker should be installed The maximu...

Страница 28: ...13A 47 50 34 50 LA 9 MI 23A 26A 13A 49 50 36 50 RCCD 1 RCCD 2 RCCD 3 MCB Compressor controller In line flow boiler DHW immersion switched by heat pump DHW immersion switched by a relay controlled by...

Страница 29: ...shown in Figure 23 This would mean that the cable from the heat pump to the cylinder could have a lower current rating and therefore could be combined with the multi core cable rather than run a separ...

Страница 30: ...the scope of supply The power for the controller is supplied from the heat pump Figure 24 Connection terminals on the controller cable to controller inside the property The controller cable is connect...

Страница 31: ...able is essential to provide boiler interlock to comply with building regulations Tank OLP If the heat pump is doing DHW the over load protection is connected to the manually resettable high limit sta...

Страница 32: ...mp efficiency Section 10 Standard packages To assist with the design and installation of a system Dimplex have collated wiring and hydraulic schematics for the following designs Package 1 and 2 Heatin...

Страница 33: ...PK2LA 12 MI 300 PK2LA 16 MI 250 PK2LA 16 MI 300 PK3LA 6 MI PK3LA 9 MI PK3LA 12 MI PK3LA 16 MI Component parts of kits LA 6 MI 1 1 1 1 LA 9 MI 1 1 1 1 LA 12 MI 1 1 1 1 1 1 LA 16 MI 1 1 1 1 1 1 PRT1 wal...

Страница 34: ...ng centre to heat pump 2 core cable for connection of DHW sensor No 3 core cable for connection of DHW immersion heater to heat pump Depends upon schematic Either cable or relay required Depends upon...

Страница 35: ...Page 34 Package 1 and 2 Plumbing Schematic...

Страница 36: ......

Страница 37: ...g circuit for efficient and safe operation Pressure relief valve A safety device that relieves the pressure in the heating circuit if it exceeds 3 bar Inline flow boiler Additional heating capacity fo...

Страница 38: ...8 61 5 3 4 Sound pressure level at 1m with Q 2 to MCS 020 dB A 54 54 3 5 Heating water flow rate m h 1 1 6 3 6 Air flow m h 2800 3100 3 7 Refrigerant total filling weight Type kg R410A 1 45 R410A 1 45...

Страница 39: ...cant total filling quantity Type Litre FV50S PVE 1 2 FV50S PVE 1 2 4 Dimensions connections and weight 4 1 Device dimensions without connections H x W x L mm 1410 x 1280 x 320 1410 x 1280 x 320 4 2 De...

Страница 40: ...Page 39 CE declaration of conformity...

Страница 41: ...Page 40 LA 6 MI performance...

Страница 42: ...Page 41 LA 6 MI continued...

Страница 43: ...Page 42 LA 9 MI performance...

Страница 44: ...Page 43 LA 9 MI performance continued...

Страница 45: ...Page 44 LA 12 MI performance...

Страница 46: ...Page 45 LA 12 MI performance continued...

Страница 47: ...Page 46 LA 16 MI performance...

Страница 48: ...Page 47 LA 16 MI performance continued...

Страница 49: ...Page 48 Product Dimensions LA 6 MI and LA 9 MI...

Страница 50: ...Page 49 Product Dimensions LA 12 MI and LA 16 MI...

Страница 51: ...Page 50 LA 6 MI and LA 9 MI Spare parts Note the non numbered parts are not kept as standard service parts...

Страница 52: ...Page 51 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 53: ...Page 52 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 54: ...Page 53 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 55: ...Page 54 LA 6 MI and LA 9 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 56: ...Page 55 LA 12 MI and LA 16 MI Spare parts Note the non numbered parts are not kept as standard service parts...

Страница 57: ...Page 56 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 58: ...Page 57 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 59: ...Page 58 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 60: ...Page 59 LA 12 MI and LA 16 MI Spare parts continued Note the non numbered parts are not kept as standard service parts...

Страница 61: ...Page 60 Information for DHW cylinder with buffer ECS125HP 580...

Страница 62: ...Page 61 Information for DHW cylinder with buffer ECS150HP 75 580...

Страница 63: ...Page 62 Information for DHW cylinder with buffer ECS210HP 75 580...

Отзывы: