background image

 

7

 

If the ceiling is lower and no airducts are used, an air ducting elbow (90° NW 160)  must be used on the 
outlet air side 
(to ensure effective operation). When an air ducting elbow is used, care must be taken that it is 
slipped onto the flange collar of the discharge side in such a way that the discharge opening of the air ducting 
elbow is as far away from the intake opening of the unit as possible. Moreover, the minimum clearances shown in 
Figure 4 have to be complied with. The air connection fittings, i.e. "intake pipe" and "discharge pipe", of the 
HPCDW are identified by adhesive labels. 
 
 

 

 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

   

 

 

                             Fig. 4: Installation requirements 

 

 
 
 
 
4.2 Installation 

 

¾

  From the underside of the pallet, remove the three M12 bolts securing the pallet to the unit as a shipping safety 

measure. 

¾

  Remove the pallet and mount the three levelling feet (M12 bolts – contained in the polybag, secured to the 

storage tank pipe nipple).

 

¾

  Move the HPCDW into final position and adjust the unit so that it is perfectly perpendicular by adjusting the 

levelling feet! Subsequently, tighten the check nuts provided on the levelling feet. 

 

 
5.     Mounting 

5.1  Connection of Water Piping

 

 
The nominal pipe widths of the field-installed sanitary installations must be determined on the basis of the available 
water pressure and the expected pressure losses within the piping system.  
 
The water-side installation has to be executed in compliance with DIN 1988 (see appendix – in the case of 
excessive water pipe pressure, a pressure relief valve is to be provided, among other things !) 
The water pipes may be of the rigid or flexible type. To prevent corrosion damage, make sure that the materials 
used in the piping system are compatible (see section Commissioning).

 

 
Caution! 

When installing the pipework on the customer's site, any contamination of the piping system 
must be avoided (pipes may have to be flushed prior to the connection of the HPCDW)! 

 

* the minimum distance of 
the discharge opening of 
the air ducting elbow  
to the wall is 1.2 m 
  
The minimum ceiling 
height for "free blowing 
installation" is approx.  
2.5 m

angesaugte Luft

ausgeblasene 
Luft

1,2 * m

0,6 m

ca.

 2,

0 m

ca.

 2,

5 m

 (

o

hne Luf

tschl

ä

uche und Luf

tf

ühr

ungs

bogen)

 

discharged 
air

drawn-in air 

approx. 2.0 m 

approx. 2.5 m (without airducts and air ducting elbow) 

Содержание KWP 300

Страница 1: ...Installation and Operating Manual Heat Pump for Cooling of Domestic Water with Airduct Connection KWP 300 451902 67 39 FD8411...

Страница 2: ...Connection 8 6 Commissioning 8 6 1 Domestic Water Circuit 8 6 2 Operation of the Heat Pump for Cooling of Domestic Water 9 7 Maintenance Service 10 7 1 Water Circuit 10 7 2 Air Circuit 10 7 3 Sacrifi...

Страница 3: ...explosion hazard due to gases vapours or dust The operation of the unit is not permitted with empty storage tank during the construction phase In the design and construction of the HPCDW all relevant...

Страница 4: ...ted from the domestic water at a low evaporation temperature and transferred to the refrigerant The vaporous refrigerant is drawn in by an electrically driven compressor and compressed to a higher pre...

Страница 5: ...ing STL 2 3 3 Temperature controller for immersion heater TC The temperature controller for the immersion heater controls the temperature of the water for domestic use during the immersion heater mode...

Страница 6: ...d see Figure If transport in an inclined position cannot be avoided the HPCDW heat pump switch should be taken into operation one hour after it has been moved into final position at the earliest Cauti...

Страница 7: ...ently tighten the check nuts provided on the levelling feet 5 Mounting 5 1 Connection of Water Piping The nominal pipe widths of the field installed sanitary installations must be determined on the ba...

Страница 8: ...f there is a danger of the water being contaminated during operation 6 1 2 Commissioning of the domestic water system All installations at the water and air circuits as well as all electrical installa...

Страница 9: ...g panel Switch position O heat pump is OFF in switch position the heat pump is in operation Heat pump switch Temperature dial for domestic water setpoint trans mitter left stop lowest cooling temperat...

Страница 10: ...ontent is heated up to the maximum temperature of the immersion heater controller factory setting 65 C In switch position the immersion heater is switched off Note If the immersion heater switch is in...

Страница 11: ...eplaced if necessary The electrical check is to be conducted by means of a suitable ammeter without draining the water in the tank Procedure n Withdraw PE wire from tab of sacrificial anode o Connect...

Страница 12: ...he temperature of the intake air lies above the permissible limit value 45 C If the malfunction cannot be corrected based on the above questions please consult your installer or customer service 9 Dec...

Страница 13: ...mers heater 16 Insulation 3 Evaporator 10 Temperature display 4 Hot water tank 11 Filter drier 5 Immersion heater 12 Expansion valve 6 Corrosion protection anode 13 Condenser 7 Temperature controller...

Страница 14: ...ing valve 7 Diaphragm safety valve 3 Test valve to be mounted above tank edge 4 Check valve 8 Drain 5 Manometer connection Wasseranschlu nach DIN 1988 6 8 5 1 3 4 2 1 Wasserzulauf 7 8 1 Brauchwasseren...

Страница 15: ...t Verdichter Ventilator Schalter EIN AUS W rmepumpe Schalter EIN AUS El Heizung Netzstecker Klemmleiste intern B1 B3 C1 C2 E1 F1 F2 F3 K2 K3 M1 M2 S1 S2 X1 X3 Legende 2 S1 1 T B1 4 18 26 C Verdichter...

Страница 16: ...air C 20 to 45 Water temperature selectable heat pump mode C 16 to 25 Heat up time from 25 C to 65 C electr immersion heater h 9 2 Power consumption electric heating watt 1500 Average power consumpti...

Страница 17: ...17 KKW Kulmbacher Klimager te Werk GmbH Subject to technical changes Department Dimplex Fax 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Отзывы: