2.3    Safety and Control Devices

 

 

The HPCDW is equipped with the following safety features:

 

 
2.3.1  High-pressure pressostat (HD) 
 

The high-pressure pressostat protects the heat pump from excessive operating pressures in the refrigeration cycle. 
In the case of a malfunction, the pressostat switches off the heat pump; the heat pump is restarted automatically as 
soon as the pressure in the refrigeration cycle has dropped to an acceptable level. 

 
 
 
2.3.2 

Safety temperature limiter for immersion heater (STL) 

 
 

The STB protects the hot water installation from 
excessive temperature increases. 
When the preset switching value (99 °C) is exceeded, the 
immersion heater is switched off. 
The immersion heater cannot be restarted unless the hot 
water temperature has fallen to 

 90 °C and the reset 

button (Fig. 2) on the STB has subsequently been 
pressed (may be performed by qualified personnel only!).

 

 
 
 
    

Fig 2: Resetting STL

 

 

  

 
 
 
 
2.3.3    Temperature controller for immersion heater (TC) 
 

The temperature controller for the immersion heater controls the temperature of the water for domestic use during 
the immersion heater mode of operation. The maximum temperature of this controller has been factory-set to 65 °C 
(the controller is installed with the STL in a common casing). The temperature setting can be changed with the aid 
of a suitable tool (see Fig. 2). Changing this setting may be performed by qualified persons only!  
In the immersion heater mode, which can only be turned on manually, the domestic water is heated up to the 
preset maximum temperature of the immersion heater.  

 
 
 
2.3.4     Temperature controller of HPCDW 
 

Temperature control in the domestic water storage tank and the control of the compressor operation is taken over 
by the temperature controller. The latter senses the water temperature by means of a sensor and regulates it as a 
function of the preset setpoint. The desired temperature level (setpoint) can be adjusted via the dial on the 
operating panel. 

 

 

 

85°

30°

B3

F2

STB

Partition

Panel

Reset button

Содержание KWP 300

Страница 1: ...Installation and Operating Manual Heat Pump for Cooling of Domestic Water with Airduct Connection KWP 300 451902 67 39 FD8411...

Страница 2: ...Connection 8 6 Commissioning 8 6 1 Domestic Water Circuit 8 6 2 Operation of the Heat Pump for Cooling of Domestic Water 9 7 Maintenance Service 10 7 1 Water Circuit 10 7 2 Air Circuit 10 7 3 Sacrifi...

Страница 3: ...explosion hazard due to gases vapours or dust The operation of the unit is not permitted with empty storage tank during the construction phase In the design and construction of the HPCDW all relevant...

Страница 4: ...ted from the domestic water at a low evaporation temperature and transferred to the refrigerant The vaporous refrigerant is drawn in by an electrically driven compressor and compressed to a higher pre...

Страница 5: ...ing STL 2 3 3 Temperature controller for immersion heater TC The temperature controller for the immersion heater controls the temperature of the water for domestic use during the immersion heater mode...

Страница 6: ...d see Figure If transport in an inclined position cannot be avoided the HPCDW heat pump switch should be taken into operation one hour after it has been moved into final position at the earliest Cauti...

Страница 7: ...ently tighten the check nuts provided on the levelling feet 5 Mounting 5 1 Connection of Water Piping The nominal pipe widths of the field installed sanitary installations must be determined on the ba...

Страница 8: ...f there is a danger of the water being contaminated during operation 6 1 2 Commissioning of the domestic water system All installations at the water and air circuits as well as all electrical installa...

Страница 9: ...g panel Switch position O heat pump is OFF in switch position the heat pump is in operation Heat pump switch Temperature dial for domestic water setpoint trans mitter left stop lowest cooling temperat...

Страница 10: ...ontent is heated up to the maximum temperature of the immersion heater controller factory setting 65 C In switch position the immersion heater is switched off Note If the immersion heater switch is in...

Страница 11: ...eplaced if necessary The electrical check is to be conducted by means of a suitable ammeter without draining the water in the tank Procedure n Withdraw PE wire from tab of sacrificial anode o Connect...

Страница 12: ...he temperature of the intake air lies above the permissible limit value 45 C If the malfunction cannot be corrected based on the above questions please consult your installer or customer service 9 Dec...

Страница 13: ...mers heater 16 Insulation 3 Evaporator 10 Temperature display 4 Hot water tank 11 Filter drier 5 Immersion heater 12 Expansion valve 6 Corrosion protection anode 13 Condenser 7 Temperature controller...

Страница 14: ...ing valve 7 Diaphragm safety valve 3 Test valve to be mounted above tank edge 4 Check valve 8 Drain 5 Manometer connection Wasseranschlu nach DIN 1988 6 8 5 1 3 4 2 1 Wasserzulauf 7 8 1 Brauchwasseren...

Страница 15: ...t Verdichter Ventilator Schalter EIN AUS W rmepumpe Schalter EIN AUS El Heizung Netzstecker Klemmleiste intern B1 B3 C1 C2 E1 F1 F2 F3 K2 K3 M1 M2 S1 S2 X1 X3 Legende 2 S1 1 T B1 4 18 26 C Verdichter...

Страница 16: ...air C 20 to 45 Water temperature selectable heat pump mode C 16 to 25 Heat up time from 25 C to 65 C electr immersion heater h 9 2 Power consumption electric heating watt 1500 Average power consumpti...

Страница 17: ...17 KKW Kulmbacher Klimager te Werk GmbH Subject to technical changes Department Dimplex Fax 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Отзывы: