46
DOK4SVxxDEN · FD 9912
www.glendimplex.de
English
Domestic ventilation unit M Flex Air (Plus)
16 Installation checklist
HINWEIS
ºº
º
ºº
º
NOTE
This list does not replace the detailed descriptions with instal-
lation and safety notes in the instruction manuals. The instal-
lation instructions for the ventilation unit and its accessory
components must be observed.
Ventilation unit
Installation room dry and free from frost
Ventilation unit installed horizontally and vertically
aligned (spacers on the bottom corners)
Vibration-reducing wall mounting for lightweight con-
struction walls
Sufficient space for maintenance work
Power supply connected, all-pole power disconnec-
tion possible and accessible (plug, switch or fuse)
External control element and room air sensor (if fitted)
installed and connected
Outside air preheating register (if fitted) installed and
connected, installation position and direction of air
flow checked (observe the installation instructions for
the heating register)
Consultation with the district master chimney sweep if
fireplace present (fireplace function activated or nec-
essary ext. safety equipment installed)
Condensate pipe
Condensate pipe connected to the ventilation unit
without leaks, fixed in place with a fastening clip
Frost-free installation of the condensate pipe over the
entire distance and pipe installed with a slope (con-
densate hose not sagging and not buckled)
Negative pressure on the condensate connection! Si-
phon installed on the ventilation unit to prevent false
air intake (siphon can dry out, a ball siphon with nega-
tive pressure protection and dry running protection is
recommended!)
Siphon filled with water, entire condensate drainage
system checked for correct function (water filled in the
condensate tray)
Free inlet from the siphon on the unit in a funnel on the
drainpipe (no direct connection between the unit and
the drainpipe, intake of sewer gases must be reliably
prevented!)
Drainpipe fitted with another siphon to prevent odours
from the waste water pipe
Air duct system
Vibration transmission must be avoided, all air ducts
are connected flexibly to the ventilation unit
Vibration-reducing measures on mountings, brackets,
consoles (if required)
Sound absorbers or sound-absorbing ventilation
hoses installed (in the supply air and exhaust air duct
and in the outside air and extract air duct)
Wall or ceiling openings are closed
Air duct system inside the thermally insulated building
shell
Thermal insulation on the outside air and extract air
duct (steam-resistant, sufficiently strong, not dam-
aged or crushed)
Air duct connections and connection points masked
with additional thermal insulation strips
The air duct system must be installed air-tight! Con-
nections and connection points of the duct and ther-
mal insulation are air-tight and masked where applica-
ble (leaks in the air duct and leaking connections can
result in condensate formation - ensure that the out-
side air and extract air pipe connections in particular
are air-tight!)
Air pipes, in particular flexible ventilation hoses, must
not be crushed or heavily buckled (risk of increased
pressure drops or reduced thermal insulation!)
Outside air and extract air inlets/outlets protected
from leaves, soiling, odours, ingress of moisture, ex-
pected snow levels taken into account
Supply air and exhaust air valves (ventilation grilles) in-
stalled
Commissioning
Residential unit ready to move in, building work com-
plete, openings closed, interior fittings completely fin-
ished, no building dust
Internal doors in place, unhindered overflow from sup-
ply air areas to exhaust air areas is achieved with un-
dercut doors or ventilation grilles
Direction of air flow on air inlets and outlets checked,
air circuit not covered, obstructed, sealed
Outside air, exhaust air and bypass filters in the unit
and clean (replace if necessary)
External control unit and room air sensor registered in
the service menu
Volume flows set in the service menu
Ventilation system calibrated and set
Function check (display working correctly, operating
modes can be set, remote control, heating register)
Room air sensor (if fitted): Function checked in Auto-
matic operating mode (caution: response only after
approx. 15 min warm-up phase!)
Settings adapted in the user and service menu (e.g.
bypass, sensor sensitivity)
Instruction
Instruct operators and users in the operation and ex-
plain the proper use
Inform operators and users of the necessary mainte-
nance measures (filter change, restart the interval time
for the filter signal)
Reference to further maintenance measures to be car-
ried out by the engineer