Domestic ventilation unit M Flex Air (Plus)
English
* Message/fault only with active fireplace function
Fig. 11.1:Messages and faults
HINWEIS
ºº
º
ºº
º
NOTE
Note: Once the fault has been rectified, it is acknowledged
with a power reset (switch off the power supply for 5 s and
switch it on again).
11.1 Internal sensors
The ventilation unit is equipped with internal sensors (in the
outside air and exhaust air) for temperature, humidity and VOC
(air quality) and with two further sensors in the fans for measur-
ing temperature, humidity, speed and volume flow.
The outside air and exhaust air sensors must be completely re-
placed in the event of a malfunction. If the measured values
from the fans fail, the fans should also be completely replaced.
11.2 Replacing fans
Fig. 11.2:Left fan
Fig. 11.3:Right fan
If a fan has to be replaced, it can only be removed once the EPP
condensate plate has been carefully removed to the front and
the cable has been disconnected.
If the incorrect assembly is fitted, the retaining plate (installa-
tion on left or right) can be modified, see Fig. 11.2 and Fig. 11.3.
The assignment for control as an exhaust air of outside air fan is
defined by the colour of the connecting plug in the wiring har-
ness (outside air blue, exhaust air black).
To teach in the new fan, load the factory settings in the service
menu, carry out the fan configuration and re-enter the unit con-
figuration (for U/V see type plate).
11.3 Replacing the bypass
If the bypass has to be replaced, it can be directly disconnected
from the bypass motor and removed.
Insert the new bypass in the correct slot and connect.
It starts functioning and performs a trial run once the power has
been restored.
11.4 Replacing the heating register
For procedure, see chapter 4.3.
It starts functioning once the power has been restored.
E24
E24: Sensor4
Off
Sensor 4 extract air
Sensor or cable faulty
Check / replace extract air sensor
E25
E25: External Modbus
communication
In operation
No external Modbus communica-
tion
Modbus cable faulty, interface
parameter settings incorrect, CPU
card faulty
Check / replace Modbus cable,
correct interface parameter set-
tings, replace CPU card
E26
E26: No tacho signal
Off
No tacho signal from fan VM1 /
VM2
Sensor or cable faulty
Check / replace fan VM1 / VM2
E27
E27: Heater
Off
No control of preheating register Cable, PTC element or power card
faulty, temperature parameter set-
tings incorrect
Check / replace cable, PTC ele-
ment or power card, adjust tem-
perature parameter settings
E31
E31: Bypass start
In operation Bypass does not switch
No power consumption, bypass
motor, cable break
Check bypass cable,
check / replace bypass flap
Code
Display
Status
Fault
Cause
Action