2
Warning Device output
• Rated 12V
DC
, 700mA, (current limit 2.0A) supervised
(EOL resistor shall be used)
• Programmable as steady, pulsed or temporal three (as
per ISO 8201) output
• Fire alarm notification has priority over burglary alarm
notification
Memory
• CMOS EEPROM memory
• Retains programming and system status on AC and bat-
tery failure
• Data Retention: 200 years min.
Programmable Outputs (PGMs)
• Up to 14 programmable outputs (PGM) with 21 options
• PGM outputs are open collector type and switched to
ground
• Three low current (50mA) PGM outputs on main panel
(PGM1, PGM3, PGM4)
NOTE:
PGM3 and PGM4 available on PC1864 only.
• One high current (300mA) output with 2-wire smoke
detector capability on the main control board (PGM2)
• Eight additional low current outputs (50mA) available
using the Model PC5208
• Four high current outputs (1A) available using the Model
PC5204 (one configurable as a supervised bell output)
Power Supply
• 1.5A regulated (1.7A for UL/ULC), supervised and inte-
gral to the control unit
• Type A as per EN50131-6 Standard
• Input ratings: 120V, 60Hz Class II (220V-240Vac, 50/
60Hz, 200mA for European installations)
• Transformer required, mounted in the same enclosure,
permanently connected for European installations
• Transformer secondary ratings: 16.5Vac, 40VA min
• AUX Output Voltage: 12V
DC,
-15%/+10% when AC Input
Voltage is 85% to +110% of rated value and output cur-
rent is 500mA (700mA for UL/ULC) (550mA for IMQ)
• Output ripple voltage: 270mVp-p max.
• Storage device: Rechargeable battery, rated 12V
DC
• Battery capacity: 4Ah, 7Ah, 14Ah (2 x 7Ah) or 24 Ah (2 x
12Ah)
• Battery = One 12V 4Ah battery (For burglary applications)
• Battery = Two 12V 7Ah (min.) rechargeable sealed lead
acid for 24-hr backup (For fire monitoring applications)
• Maximum standby time 24Ah (when using 14Ah battery
capacity and AUX current limited to 480mA max.).
• Recharging time 48h
• Programmable recharging current: Low 400mA, High
700mA
• Low battery trouble indication threshold 11.5V
DC
• Battery deep discharge protection (cut-off at 9.5V
DC
)
• Main board current draw: 85mA (set and unset state)
• Resettable fuses (PTC) used on circuit board instead of
replaceable fuses
• Supervision for loss of primary power source (AC Fail),
battery fail or battery low voltage (Battery Trouble) with
indication provided on the keypad
• Internal clock locked to AC power frequency
Operating Environmental Conditions
• Temperature range: -10°C to +55°C (14°F to 131°F)
• Relative humidity: 93% non condensing
Keypad Specifications
• Each keypad has 5 fully programmable function keys
(see Section [000] in the programming section.
• “T” version keypads have tamper protection
• Connect up to 8 keypads
• Four wire (Quad) connection to Keybus
• Built in piezoelectric buzzer
Alarm Transmitter Equipment (ATE) Specification
• Digital dialer integral to the main control board
• Complies with TS103 021-1, -2, -3 Telecom equipment
requirements
• Supports the following communications formats:
• 10 BPS/20 BPS
• DTMF Contact ID
• SIA FSK
• Pager
• Residential Dial
• Private Line
• Scantronics 4-8-1
• Robofon
• CESA 200
• Split reporting of selected transmissions to each tele-
phone number
• 3 programmable telephone numbers
• 1 system account number
• Upto 8 partition account numbers
• Supports Skyroute™ Cellemetry Communication Trans-
ceiver
• GS3050 GSM Universal Wireless Alarm Communicator
• DTMF and pulse dialing
• DPDT line seizure
• Anti-jam detection
• Event-initiated personal paging
• T-Link/T-Link TL250/T-Link TL300 Ethernet Communica-
tions (using PC-Link) for Intranet/Internet connectivity.
System Supervision Features
The PC1616/PC1832/PC1864 continuously monitors a num-
ber of possible trouble conditions and provides audible and
visual indication at the keypad. Multiple signals are indicated
using scroll buttons on the LCD keypads (no priority
assigned) or by different lights on the LED’s keypads. Trou-
ble Conditions include:
• AC Power Failure
• Low Battery Condition
• AUX Power Supply Fault
• Bell Output Trouble
• Telephone Line Trouble
• Failure to Communicate
• Loss of Internal Clock
• Module Fault (Supervisory or Tamper)
• Trouble by Zone
• Fire Trouble
• Tamper by Zone
False Alarm Prevention Features
• Audible Exit Delay
• Audible Exit Fault
• Urgency on Entry Delay
• Quick Exit
• Swinger Shutdown
• Recent Closing Reporting Code
• Cross Zone/Police Code Alarm
• Burglary-Verified Timer
• Communication Delay
• Rotating Keypress Buffer
Additional Features
• Automatic inhibit (swinger shutdown) for Alarm, Tamper,
Trouble signals after 3 occurrences in a given set period