background image

Operation

3.1.3 Battery Unit Controls

The battery unit circuit breaker (see Figure 3–2), located on the rear panel of

the battery unit, must be ON before the UPS can charge the batteries or receive

battery back-up power. It opens and closes the circuit between the battery unit

and the battery circuit breaker on the UPS front panel.
When the battery unit circuit breaker is ON, battery voltage is applied to the

battery circuit breaker on the UPS front panel. When the battery unit circuit

breaker is tripped or turned OFF, all battery voltage is removed from the UPS.

3.2 Output Distribution

Output distribution for the 2T-HA10F-CD UPS is provided through a distribution

panel located on the rear panel of the UPS (see Figure 3–2). This distribution

panel contains six NEMA 6-15R (15 A, 208 V) receptacles.

3.3 Emergency Shutdown Plug

The 2T-HA10F-CD UPS is shipped with an emergency shutdown plug installed in

the emergency shutdown jack on the rear of the UPS (see Figure 3–2).
The UPS will not operate if the emergency shutdown plug is not installed or if

the circuit between the terminals of the emergency shutdown plug is broken.
Pulling the emergency shutdown plug out of the emergency shutdown jack shuts

down the UPS by tripping the ac input circuit breaker and the battery circuit

breaker on the front panel.
The emergency shutdown plug also provides the connections for a Remote

Emergency Power Off (REPO) device. The REPO device must have contacts that

are normally closed and rated for a minimum of 80 V and 10 mA.
Use the following procedure to connect a REPO device to the emergency shutdown

plug:
1. Turn the UPS OFF.
2. Remove the emergency shutdown plug from the emergency shutdown jack on

the back of the UPS (see Figure 3–2).

3. Disassemble the emergency shutdown plug and remove the metal strip that

connects the plug’s two terminals to each other.

4. Route the wire from the REPO device through the rubber grommet on the

back of the system cabinet.

5. Connect one wire per terminal from the REPO device to the plug’s terminals.
6. Reassemble the emergency shutdown plug and plug it into the emergency

shutdown jack on the back of the UPS.

3–6 Operation

Содержание 2T-HA10F-CD

Страница 1: ...2T HA10F CD 3 6 kVA UninterruptiblePowerSystem OperatingInformation Order Number EK HA10F OP B01 Revision Update Information Revised August 1992 Digital Equipment Corporation...

Страница 2: ...of FCC rules which are designed to provide reasonable protection against such interference in a residential installation However there is no guarantee that interference will not occur in a particular...

Страница 3: ...t 2 2 3 Operation 3 1 Controls and Indicators 3 1 3 1 1 UPS Controls 3 2 3 1 1 1 AC Input Circuit Breaker 3 2 3 1 1 2 Battery Circuit Breaker 3 3 3 1 1 3 Alarm Silence Button 3 4 3 1 2 UPS Indicators...

Страница 4: ...hooting 5 1 5 3 Digital Services Troubleshooting 5 1 5 4 Periodic Battery Check 5 4 5 5 Storage Procedures 5 4 Figures 1 1 2T HA10F CD UPS Functional Diagram 1 2 3 1 2T HA10F CD UPS Front Panel 3 2 3...

Страница 5: ...WARNING The UPS battery unit contains batteries that are wired together to produce a high voltage Even with no external connections hazardous voltage exists inside the UPS battery unit that can cause...

Страница 6: ...TES Calls attention to information in text that may be of special importance CAUTIONS Calls attention to information in text that is essential in avoiding system or equipment damage WARNINGS Calls att...

Страница 7: ...ractions of the major components to accomplish this task When power for the loads comes from an ac input the UPS uses the following components to improve the quality of the power before it reaches the...

Страница 8: ...on transformer for output to the load When the batteries feed the UPS the bidirectional converter changes dc to ac and feeds the ac voltage to the isolation transformer for output to the load 1 1 2 Ba...

Страница 9: ...ade to the UPS unit Addition of a metal distribution panel box containing six 240 V output receptacles Addition of wiring from the UPS unit to the output receptacles Addition of ac input power wiring...

Страница 10: ...s than 3 total harmonic distortion Overload Rating 150 of full load for 30 seconds 2 3 Environmental Operating Temperature 0 C to 40 C 32 F to 104 F safety agency tested at 25 C 77 F Relative Humidity...

Страница 11: ...ight 16 84 cm 6 63 in Depth 63 83 cm 25 13 in Battery Front Panel Dimensions Width 48 26 cm 19 00 in Height 17 78 cm 7 00 in Battery Weight 67 kg 148 lb 2 6 Assembly Requirements in an H9702 Cabinet W...

Страница 12: ...breaker Indicators Status lights Normal Bypass On Battery ac input failure Fault includes overtemperature and overload Low Battery Audio alarm All of the controls and indicators are mounted on the fr...

Страница 13: ...following sections describe the controls for the UPS unit 3 1 1 1 AC Input Circuit Breaker The ac input circuit breaker on the front panel must be ON before the UPS can receive power from an ac input...

Страница 14: ...the unit see Figure 3 2 can deliver an electrical shock This condition can occur even when the UPS is disconnected from an ac power source and the ac input circuit breaker is OFF These high voltages c...

Страница 15: ...ut is still available at the output receptacles The power available at the output receptacles is unconditioned and unregulated ac On Battery Status Light The yellow status light labeled On Battery is...

Страница 16: ...S with discharged batteries If the batteries are allowed to remain discharged for long periods their life will be significantly shortened Table 3 1 Summary of Status Lights Name of Indicator Color of...

Страница 17: ...PS will not operate if the emergency shutdown plug is not installed or if the circuit between the terminals of the emergency shutdown plug is broken Pulling the emergency shutdown plug out of the emer...

Страница 18: ...peration Figure 3 2 2T HA10F CD UPS Rear View with FCC Shielding Removed MKV 040000216 02 91 RAGS Battery Unit Circuit Breaker Emergency Shutdown Plug Distribution Panel UPS Battery Unit Operation 3 7...

Страница 19: ...s to the ON position 3 4 2 Normal UPS Powerdown Use the following procedure to power down the UPS 1 Turn the individual load s off by placing their power switches to the OFF position 2 Place the batte...

Страница 20: ...ery circuit breaker located on the front panel of the UPS see Figure 3 1 to the OFF position The yellow Bypass status light on the UPS front panel should light to indicate that the UPS is operating in...

Страница 21: ...panel of the battery unit see Figure 3 2 to the OFF position Access to the battery unit circuit breaker requires the removal of an access plate located in the lower left rear of the cabinet 5 Unplug...

Страница 22: ...nge of the UPS unit to its shelf b Remove the two 6 32 screws that secure the battery unit to the bracket on the rear edge of its shelf 11 At the front of the H9702 cabinet remove the six 10 32 screws...

Страница 23: ...g power from the UPS or if the audio alarm is sounding and the Fault status light is lit call Digital Services for service When calling for service check the status lights on the UPS front panel and b...

Страница 24: ...correctly wired and installed see Section 3 3 If the UPS still does not function properly Digital Services should call Deltec Customer Service When calling for service check the status lights on the...

Страница 25: ...dio alarm The battery backup is limited backup time is typically 10 minutes under full load If the UPS does not return to normal operation before the batteries reach a predetermined low battery cutoff...

Страница 26: ...e following guidelines must be followed to protect the batteries 1 Charge the batteries fully before the UPS is stored by connecting the UPS to an ac source and operating it for 12 hours with all thre...

Отзывы: