E-13
• To avoid an electric shock, prior to connecting the ST's power
cord confirm that the ST's power supply is completely turned OFF,
via a breaker, or similar unit.
• The ST400-AG41-24V/ST401-AG41-24V/ST402-AG41-24V /
ST403-AG41-24V units are designed to use only DC24V input.
Any other power level can damage both the ST and the power
supply.
• Since there is no power switch on the ST unit, be sure to attach a
breaker-type switch to its power cord.
• When the FG terminal is connected, be sure the cord is grounded.
• If the power cord is pulled strongly, the power plug may fall out.
• When the FG terminal is connected, be sure the wire is grounded.
Not grounding the ST unit will result in excess noise and vibration.
5
Wiring
WARNINGS
• The power cord should be equivalent to the specification shown above. Be
sure to twist the power cords together, up to the power plug. (See illustration
on next page)
• Recommended power plug is Phoenix Contact Co.'s MSTB2,5/3-ST-5,08.
Power Plug Specifications
Power Cord Specifications
7mm
+
-
FG
Insertion
Direction
Power Cord Diameter
0.2 to 2.5 mm
2
(24 – 12 AWG)
Conductor Type
Simple or Stranded Wire
Conductor Length
+ 24V
- 0V
FG Grounding Terminal connected to the ST chassis