4 - 9
PL-6900 Series User Manual
Installation and Wiring
• The grounding point must be as close to
the PL as possible, and the grounding
wires must be as short as possible. If the
wires must be long, use thick, insulated
wires and run them through conduits.
(a) Dedicated Ground *1
• Set up a dedicated ground when using
the rear panel’s FG terminal.
(b) Shared Ground - allowed *1
• If a dedicated ground is not possible, use
a shared ground, as shown in figure (b).
(c) Shared ground - not allowed
3
Grounding Cautions
PL
PL
Other
device
Other
device
4
Cautions When Connecting I/O Signal Lines
• I/O signal lines must be wired separately from the power circuit cable.
If the power circuit cable needs to be wired together with the input/output
(I/O) signal lines for any reason, use shielded cables and ground one end of
the shield to the PL’s FG terminal.
• To improve noise immunity, it is recommended to attach a ferrite core to the
power cord.
Other
device
PL
*1 Use a grounding resistance of 100
Ω
or less, and a 2mm
2
or thicker wire, or your
country’s applicable standard. For details, contact your local PL distributor.
.
Содержание Pro-Face PL-6900 Series
Страница 17: ...xvi Preface PL 6900 Series User Manual MEMO ...
Страница 23: ...1 6 PL 6900 Series User Manual Overview MEMO ...
Страница 51: ...3 14 PL 6900 Series User Manual Installing Optional Units and Expansion Boards MEMO ...
Страница 61: ...4 10 PL 6900 Series User Manual Installation and Wiring MEMO ...
Страница 81: ...6 4 PL 6900 Series User Manual OS Setup MEMO ...
Страница 91: ...7 10 PL 6900 Series User Manual Maintenance and Inspection MEMO ...
Страница 101: ...App 10 PL 6900 Series User Manual Appendix MEMO ...
Страница 105: ...Index IV PL 6900 Series User Manual ...