Page 25

The Outputs screen has three tabs:

1. Label

You can modify an output name by:

a)

  Select an output and select its label.

b)

  Enter the new preset name and select the OK button.

2. Control

You can activate, deactivate, or configure a selected output. The 

procedures differ depending on the CLC setting type, as follows:

Threshold Trigger

a)

  Activate or deactivate an output by selecting the 

ACTIVATE 

or 

DEACTIVATE

 button.

An orange rectangle is displayed for activated modes and a 

blue rectangle for deactivated modes.

b)

  Select the 

LOW LEVEL

 or 

HIGH LEVEL

 button to view 

the current 

Low Level Set Point

 or 

High Level Set Point

respectively. Adjust the set points by using the slider and 

selecting the 

Set

 button.

c)

  Select the 

MODIFY

 button to view or modify sensor 

parameters, as follows:

1.  Triggering Preset

 - display any of the CLC triggering 

presets associated with the output.

2.  Daylight Sensor

 - select the associated 

link

 to modify 

the controlling sensor. Next, select the new 

sensor

.

3.  CLC Function

 - select the associated 

link

 to modify the 

CLC type. Next, select the 

Open Loop

 or 

Closed Loop 

option and select the 

OK

 button.

4.  High Level Target

 - select the associated 

link

 to modify 

the high level target, which is the relay output that is 

turned on when the light levels exceed the High Level 

Set Point. Next, select the new 

output

.

5.  Test Mode

 - select the associated 

link

 to enable or 

disable the test mode. By default, this option is turned 

off. If this option is enabled, there is no delay time 

between light level readings.

Open Loop

a)

  Activate or deactivate an output by selecting the 

ACTIVATE 

or 

DEACTIVATE

 button.

An orange rectangle is displayed for activated modes and a 

blue rectangle for deactivated modes.

b)

  Select the 

DIMMER

 button to adjust the dimmer out dimming 

level Set Point. This is set as a percentage. Use the slider to  

adjust the level and select the 

Set

 button. In the case when 

the there are multiple dimmer outputs controlled by the same 

sensor, this value is the dimmer RATIO.

Constant Lighting Controller

24

Dialog® Lighting Control System

The Outputs screen has three tabs:

1. 

Label
You can modify an output name by:

 

a) 

Select an 

output

 and select its 

label

.

 

b) 

Enter the new preset name and select the 

OK

 button.

2. 

Control

You can activate, deactivate, or configure a selected output. The 

procedures differ depending on the CLC setting type, as follows:

Threshold Trigger

 

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or   

 

 

DEACTIVATE 

button.  

  An orange rectangle is displayed for activated modes and a blue 

 

 

  rectangle for deactivated modes. 

 

b) 

Select the 

LOW LEVEL

 or 

HIGH LEVEL

 button to view the current     

 

Low Level Set Point

 or 

High Level Set Point

, respectively. Adjust     

  the set points by using the slider and selecting the 

Set

 button. 

 

c) 

Select the 

MODIFY 

button to view or modify sensor parameters, as 

   

  follows:

   

1. Triggering Preset 

- display any of the CLC triggering presets 

 

 

    associated with the output.

   

2. Daylight Sensor

 - select the associated 

link

 to modify the   

 

    controlling sensor. Next, select the new 

sensor

 

  3. CLC Function

 - select the associated 

link

 to modify the CLC type.   

    Next, select the 

Open Loop

 or 

Closed Loop

 option and select the   

   

OK

 button. 

   

4. High Level Target

 - select the associated 

link

 to modify the high    

    level target, which is the relay output that is turned on when 

 

 

    the light levels exceed the High Level Set Point. Next, select 

 

 

    the new

 output.

 

   

5. Test Mode

 - select the associated 

link

 to enable or disable the test   

    mode. By default, this option is turned off. If this option is enabled, 

 

    there is no delay time between light level readings. 

  Open Loop

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or 

DEACTIVATE 

button.  

An orange rectangle is displayed for activated modes and 

a blue rectangle for deactivated modes. 

b)  

Select the 

DIMMER

 button to adjust the dimmer   

 

 out dimming level Set Point. This is set as a percentage. 

 

 Use the slider to   adjust the level and select the   

 

 

Set

 button. In the case when the there are multiple     

 dimmer outputs controlled by the   

   

 same sensor, this value is the dimmer RATIO. 

Constant Lighting Controller

C

M

Y

CM

MY

CY

CMY

K

24

Dialog® Lighting Control System

The Outputs screen has three tabs:

1. 

Label
You can modify an output name by:

 

a) 

Select an 

output

 and select its 

label

.

 

b) 

Enter the new preset name and select the 

OK

 button.

2. 

Control

You can activate, deactivate, or configure a selected output. The 

procedures differ depending on the CLC setting type, as follows:

Threshold Trigger

 

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or   

 

 

DEACTIVATE 

button.  

  An orange rectangle is displayed for activated modes and a blue 

 

 

  rectangle for deactivated modes. 

 

b) 

Select the 

LOW LEVEL

 or 

HIGH LEVEL

 button to view the current     

 

Low Level Set Point

 or 

High Level Set Point

, respectively. Adjust     

  the set points by using the slider and selecting the 

Set

 button. 

 

c) 

Select the 

MODIFY 

button to view or modify sensor parameters, as 

   

  follows:

   

1. Triggering Preset 

- display any of the CLC triggering presets 

 

 

    associated with the output.

   

2. Daylight Sensor

 - select the associated 

link

 to modify the   

 

    controlling sensor. Next, select the new 

sensor

 

  3. CLC Function

 - select the associated 

link

 to modify the CLC type.   

    Next, select the 

Open Loop

 or 

Closed Loop

 option and select the   

   

OK

 button. 

   

4. High Level Target

 - select the associated 

link

 to modify the high    

    level target, which is the relay output that is turned on when 

 

 

    the light levels exceed the High Level Set Point. Next, select 

 

 

    the new

 output.

 

   

5. Test Mode

 - select the associated 

link

 to enable or disable the test   

    mode. By default, this option is turned off. If this option is enabled, 

 

    there is no delay time between light level readings. 

  Open Loop

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or 

DEACTIVATE 

button.  

An orange rectangle is displayed for activated modes and 

a blue rectangle for deactivated modes. 

b)  

Select the 

DIMMER

 button to adjust the dimmer   

 

 out dimming level Set Point. This is set as a percentage. 

 

 Use the slider to   adjust the level and select the   

 

 

Set

 button. In the case when the there are multiple     

 dimmer outputs controlled by the   

   

 same sensor, this value is the dimmer RATIO. 

Constant Lighting Controller

C

M

Y

CM

MY

CY

CMY

K

24

Dialog® Lighting Control System

The Outputs screen has three tabs:

1. 

Label
You can modify an output name by:

 

a) 

Select an 

output

 and select its 

label

.

 

b) 

Enter the new preset name and select the 

OK

 button.

2. 

Control

You can activate, deactivate, or configure a selected output. The 

procedures differ depending on the CLC setting type, as follows:

Threshold Trigger

 

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or   

 

 

DEACTIVATE 

button.  

  An orange rectangle is displayed for activated modes and a blue 

 

 

  rectangle for deactivated modes. 

 

b) 

Select the 

LOW LEVEL

 or 

HIGH LEVEL

 button to view the current     

 

Low Level Set Point

 or 

High Level Set Point

, respectively. Adjust     

  the set points by using the slider and selecting the 

Set

 button. 

 

c) 

Select the 

MODIFY 

button to view or modify sensor parameters, as 

   

  follows:

   

1. Triggering Preset 

- display any of the CLC triggering presets 

 

 

    associated with the output.

   

2. Daylight Sensor

 - select the associated 

link

 to modify the   

 

    controlling sensor. Next, select the new 

sensor

 

  3. CLC Function

 - select the associated 

link

 to modify the CLC type.   

    Next, select the 

Open Loop

 or 

Closed Loop

 option and select the   

   

OK

 button. 

   

4. High Level Target

 - select the associated 

link

 to modify the high    

    level target, which is the relay output that is turned on when 

 

 

    the light levels exceed the High Level Set Point. Next, select 

 

 

    the new

 output.

 

   

5. Test Mode

 - select the associated 

link

 to enable or disable the test   

    mode. By default, this option is turned off. If this option is enabled, 

 

    there is no delay time between light level readings. 

  Open Loop

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or 

DEACTIVATE 

button.  

An orange rectangle is displayed for activated modes and 

a blue rectangle for deactivated modes. 

b)  

Select the 

DIMMER

 button to adjust the dimmer   

 

 out dimming level Set Point. This is set as a percentage. 

 

 Use the slider to   adjust the level and select the   

 

 

Set

 button. In the case when the there are multiple     

 dimmer outputs controlled by the   

   

 same sensor, this value is the dimmer RATIO. 

Constant Lighting Controller

C

M

Y

CM

MY

CY

CMY

K

24

Dialog® Lighting Control System

The Outputs screen has three tabs:

1. 

Label
You can modify an output name by:

 

a) 

Select an 

output

 and select its 

label

.

 

b) 

Enter the new preset name and select the 

OK

 button.

2. 

Control

You can activate, deactivate, or configure a selected output. The 

procedures differ depending on the CLC setting type, as follows:

Threshold Trigger

 

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or   

 

 

DEACTIVATE 

button.  

  An orange rectangle is displayed for activated modes and a blue 

 

 

  rectangle for deactivated modes. 

 

b) 

Select the 

LOW LEVEL

 or 

HIGH LEVEL

 button to view the current     

 

Low Level Set Point

 or 

High Level Set Point

, respectively. Adjust     

  the set points by using the slider and selecting the 

Set

 button. 

 

c) 

Select the 

MODIFY 

button to view or modify sensor parameters, as 

   

  follows:

   

1. Triggering Preset 

- display any of the CLC triggering presets 

 

 

    associated with the output.

   

2. Daylight Sensor

 - select the associated 

link

 to modify the   

 

    controlling sensor. Next, select the new 

sensor

 

  3. CLC Function

 - select the associated 

link

 to modify the CLC type.   

    Next, select the 

Open Loop

 or 

Closed Loop

 option and select the   

   

OK

 button. 

   

4. High Level Target

 - select the associated 

link

 to modify the high    

    level target, which is the relay output that is turned on when 

 

 

    the light levels exceed the High Level Set Point. Next, select 

 

 

    the new

 output.

 

   

5. Test Mode

 - select the associated 

link

 to enable or disable the test   

    mode. By default, this option is turned off. If this option is enabled, 

 

    there is no delay time between light level readings. 

  Open Loop

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or 

DEACTIVATE 

button.  

An orange rectangle is displayed for activated modes and 

a blue rectangle for deactivated modes. 

b)  

Select the 

DIMMER

 button to adjust the dimmer   

 

 out dimming level Set Point. This is set as a percentage. 

 

 Use the slider to   adjust the level and select the   

 

 

Set

 button. In the case when the there are multiple     

 dimmer outputs controlled by the   

   

 same sensor, this value is the dimmer RATIO. 

Constant Lighting Controller

C

M

Y

CM

MY

CY

CMY

K

24

Dialog® Lighting Control System

The Outputs screen has three tabs:

1. 

Label
You can modify an output name by:

 

a) 

Select an 

output

 and select its 

label

.

 

b) 

Enter the new preset name and select the 

OK

 button.

2. 

Control

You can activate, deactivate, or configure a selected output. The 

procedures differ depending on the CLC setting type, as follows:

Threshold Trigger

 

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or   

 

 

DEACTIVATE 

button.  

  An orange rectangle is displayed for activated modes and a blue 

 

 

  rectangle for deactivated modes. 

 

b) 

Select the 

LOW LEVEL

 or 

HIGH LEVEL

 button to view the current     

 

Low Level Set Point

 or 

High Level Set Point

, respectively. Adjust     

  the set points by using the slider and selecting the 

Set

 button. 

 

c) 

Select the 

MODIFY 

button to view or modify sensor parameters, as 

   

  follows:

   

1. Triggering Preset 

- display any of the CLC triggering presets 

 

 

    associated with the output.

   

2. Daylight Sensor

 - select the associated 

link

 to modify the   

 

    controlling sensor. Next, select the new 

sensor

 

  3. CLC Function

 - select the associated 

link

 to modify the CLC type.   

    Next, select the 

Open Loop

 or 

Closed Loop

 option and select the   

   

OK

 button. 

   

4. High Level Target

 - select the associated 

link

 to modify the high    

    level target, which is the relay output that is turned on when 

 

 

    the light levels exceed the High Level Set Point. Next, select 

 

 

    the new

 output.

 

   

5. Test Mode

 - select the associated 

link

 to enable or disable the test   

    mode. By default, this option is turned off. If this option is enabled, 

 

    there is no delay time between light level readings. 

  Open Loop

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or 

DEACTIVATE 

button.  

An orange rectangle is displayed for activated modes and 

a blue rectangle for deactivated modes. 

b)  

Select the 

DIMMER

 button to adjust the dimmer   

 

 out dimming level Set Point. This is set as a percentage. 

 

 Use the slider to   adjust the level and select the   

 

 

Set

 button. In the case when the there are multiple     

 dimmer outputs controlled by the   

   

 same sensor, this value is the dimmer RATIO. 

Constant Lighting Controller

C

M

Y

CM

MY

CY

CMY

K

24

Dialog® Lighting Control System

The Outputs screen has three tabs:

1. 

Label
You can modify an output name by:

 

a) 

Select an 

output

 and select its 

label

.

 

b) 

Enter the new preset name and select the 

OK

 button.

2. 

Control

You can activate, deactivate, or configure a selected output. The 

procedures differ depending on the CLC setting type, as follows:

Threshold Trigger

 

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or   

 

 

DEACTIVATE 

button.  

  An orange rectangle is displayed for activated modes and a blue 

 

 

  rectangle for deactivated modes. 

 

b) 

Select the 

LOW LEVEL

 or 

HIGH LEVEL

 button to view the current     

 

Low Level Set Point

 or 

High Level Set Point

, respectively. Adjust     

  the set points by using the slider and selecting the 

Set

 button. 

 

c) 

Select the 

MODIFY 

button to view or modify sensor parameters, as 

   

  follows:

   

1. Triggering Preset 

- display any of the CLC triggering presets 

 

 

    associated with the output.

   

2. Daylight Sensor

 - select the associated 

link

 to modify the   

 

    controlling sensor. Next, select the new 

sensor

 

  3. CLC Function

 - select the associated 

link

 to modify the CLC type.   

    Next, select the 

Open Loop

 or 

Closed Loop

 option and select the   

   

OK

 button. 

   

4. High Level Target

 - select the associated 

link

 to modify the high    

    level target, which is the relay output that is turned on when 

 

 

    the light levels exceed the High Level Set Point. Next, select 

 

 

    the new

 output.

 

   

5. Test Mode

 - select the associated 

link

 to enable or disable the test   

    mode. By default, this option is turned off. If this option is enabled, 

 

    there is no delay time between light level readings. 

  Open Loop

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or 

DEACTIVATE 

button.  

An orange rectangle is displayed for activated modes and 

a blue rectangle for deactivated modes. 

b)  

Select the 

DIMMER

 button to adjust the dimmer   

 

 out dimming level Set Point. This is set as a percentage. 

 

 Use the slider to   adjust the level and select the   

 

 

Set

 button. In the case when the there are multiple     

 dimmer outputs controlled by the   

   

 same sensor, this value is the dimmer RATIO. 

Constant Lighting Controller

C

M

Y

CM

MY

CY

CMY

K

24

Dialog® Lighting Control System

The Outputs screen has three tabs:

1. 

Label
You can modify an output name by:

 

a) 

Select an 

output

 and select its 

label

.

 

b) 

Enter the new preset name and select the 

OK

 button.

2. 

Control

You can activate, deactivate, or configure a selected output. The 

procedures differ depending on the CLC setting type, as follows:

Threshold Trigger

 

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or   

 

 

DEACTIVATE 

button.  

  An orange rectangle is displayed for activated modes and a blue 

 

 

  rectangle for deactivated modes. 

 

b) 

Select the 

LOW LEVEL

 or 

HIGH LEVEL

 button to view the current     

 

Low Level Set Point

 or 

High Level Set Point

, respectively. Adjust     

  the set points by using the slider and selecting the 

Set

 button. 

 

c) 

Select the 

MODIFY 

button to view or modify sensor parameters, as 

   

  follows:

   

1. Triggering Preset 

- display any of the CLC triggering presets 

 

 

    associated with the output.

   

2. Daylight Sensor

 - select the associated 

link

 to modify the   

 

    controlling sensor. Next, select the new 

sensor

 

  3. CLC Function

 - select the associated 

link

 to modify the CLC type.   

    Next, select the 

Open Loop

 or 

Closed Loop

 option and select the   

   

OK

 button. 

   

4. High Level Target

 - select the associated 

link

 to modify the high    

    level target, which is the relay output that is turned on when 

 

 

    the light levels exceed the High Level Set Point. Next, select 

 

 

    the new

 output.

 

   

5. Test Mode

 - select the associated 

link

 to enable or disable the test   

    mode. By default, this option is turned off. If this option is enabled, 

 

    there is no delay time between light level readings. 

  Open Loop

a) 

Activate or deactivate an output by selecting the 

ACTIVATE

 or 

DEACTIVATE 

button.  

An orange rectangle is displayed for activated modes and 

a blue rectangle for deactivated modes. 

b)  

Select the 

DIMMER

 button to adjust the dimmer   

 

 out dimming level Set Point. This is set as a percentage. 

 

 Use the slider to   adjust the level and select the   

 

 

Set

 button. In the case when the there are multiple     

 dimmer outputs controlled by the   

   

 same sensor, this value is the dimmer RATIO. 

Constant Lighting Controller

C

M

Y

CM

MY

CY

CMY

K

a)

1.

a)

b)

2.

3.

4.

5.

b)

c)

Threshold Trigger

Open Loop:

Содержание WLC-4150-C

Страница 1: ...Field Guide Centralized Lighting Control System For WLC 4150 C WLC 4150 L...

Страница 2: ...WLC 4150 C Lighting Control Unit 3 Touchscreen Navigation 4 Menus Outputs 5 Groups 7 Presets 10 Modes 14 Behaviours 20 Constant Lighting Controller 22 Schedules 36 Setings 39 Event Logs 44 Notes 45 Co...

Страница 3: ...Page 3 WLC 4150 C L Lighting Control Unit USB Port Power 24VAC Ethernet 2 LCD Touchscreen Display Dialog Network Power Data Power 24VAC WLC 4150 C L...

Страница 4: ...ntinue The default password is dlc Enter the password and select on the OK button You can change the default password to a unique password for your facility using the Settings options 4 On the Main sc...

Страница 5: ...b Select the communication bus you are configuring The default communication bus is Dialog c Select the output type Relay or Dimmer If the selected output type is a dimmer you can adjust the brightnes...

Страница 6: ...bmenu group Row lists the row where it is located Col list s the column where it is located is screen allows you to list new panels installed after initialization of the stem edit panel labels and ass...

Страница 7: ...y outputs to panels Dialog Lighting Control System Output Menu 1 To add a new panel a Scroll through the panel list to the unlabeled relays and select the relay Select Add Panel b Enter the new panel...

Страница 8: ...enu group Total number of outputs in the group Rel number of relays in the group D number of dimmers in the group Groups Menu 7 Dialog Lighting Control System The Groups screen has four tabs 1 Label T...

Страница 9: ...manufacturer and type of the contact input ufacturer is Douglas and the default value gle Also set the delay OFF time by using The default value is 30 seconds the manufacturer of the occupancy sensor...

Страница 10: ...select OK header name der name select the rename link w header and select OK eader association for the header delete link re prompted to confirm the deletion eaders en displays all headers used for t...

Страница 11: ...the associated outputs If you selected Mode Trigger select the associated modes Presets Menu Dialog Lighting Control System The Local Presets screen has four tabs 1 Label To modify a preset name a Sel...

Страница 12: ...r and selecting Set The default value is 30 seconds Occupancy Sensor select the manufacturer of the occupancy sensor input The default value is Douglas Also set the sensitivity of the occupancy sensor...

Страница 13: ...for deactivated presets A black rectangle indicates the preset has not been assigned 3 LOGs You can view the historical activity for a selected preset by selecting the LOGs tab 4 Setup a Select a pre...

Страница 14: ...b continued If a selected preset is a relay you specify if it is turned on or turned off when the preset is activated If a selected output is a dimmer adjust the dimmer levels to percentage of brightn...

Страница 15: ...t Modes Astro utput Modes Timeout utput Modes Flick utput Modes Perm Block des Menu 14 Dialog Lighting Control System 1 Astro The Astro screen displays all Astro Modes An Astro Mode triggers outputs d...

Страница 16: ...e and select OK to modify this value 3 LOGs You can view the historical activity for a selected mode by selecting the LOGs tab Modes and select the OK button ecting the Select button elect the OK butt...

Страница 17: ...rical activity for a selected mode by selecting the LOGs tab Modes nd select the OK button cting the Select button el elect the OK button y a mode electing the ACTIVATE or DEACTIVATE or activated mode...

Страница 18: ...ontrol You can activate deactivate or modify a mode by a Activate or deactivate a mode by selecting the ACTIVATE or DEACTIVATE button An orange rectangle is displayed for activated modes and a blue re...

Страница 19: ...e occupancy sensors associated with a specific group for a set me This mode is used to prevent outputs from switching off when ed or no activity in a room but continues to be occupied new Quiet Mode...

Страница 20: ...utton e or modify a mode e a mode by selecting the ACTIVATE or DEACTIVATE is displayed for activated modes and a blue rectangle es cal activity for a selected mode by selecting the LOGs Control Functi...

Страница 21: ...activate or deactivate in a or is activated When a behavior is deactivated n of outputs groups presets modes and ate in a specified order r link The new behavior appears on the list bs e t its label m...

Страница 22: ...roup preset mode or schedule and select the OK button Next select the target and specify if it is on or off ehaviors etup Select the behavior from the list and select the ON ACTIONS button Select the...

Страница 23: ...global sensors which are photosensor y other LCUs in the network Global sensors which are ng Controller Menus s Menu wo menus Daylight Sensors and Constant Lighting ach of these menus has multiple su...

Страница 24: ...nd select the OK button d Select the controlling output and select the OK button e The new output mode is displayed Use the buttons on the screen to adjust the configuration Constant Lighting Controll...

Страница 25: ...ring Preset display any of the CLC triggering presets associated with the output 2 Daylight Sensor select the associated link to modify the controlling sensor Next select the new sensor 3 CLC Function...

Страница 26: ...ntrolling nsor ociated link to modify the CLC type Next sed Loop option and select the OK button he associated link to modify the value ning process First select the Interior or to set the new value a...

Страница 27: ...the new value and select the OK button 3 LOGs You can view the historical activity for a selected mode by selecting the LOGs tab 2 Control continued Closed Loop a Activate or deactivate an output by...

Страница 28: ...of CLC setting in the order of the controlling put type is also displayed with r relay and d dimmer Groups d to sensors when a new Group Mode is created te a new Group Mode the Add Mode link You may h...

Страница 29: ...lling sensor Next select the new sensor 3 CLC Function select the associated link to modify the CLC type Next select the Open Loop or Closed Loop option and select the OK 4 High Level Target select th...

Страница 30: ...t the OK button 8 Max Electric Light select the associated link to modify the value which is the brightness stable light level value in the area controlled by the CLC Use the slider to set the new val...

Страница 31: ...rcentage when the ambient brightness changes Use the slider to set the new value and select the OK button nstant Lighting Controller ghting Control System trol continued ed Loop ctivate or deactivate...

Страница 32: ...nsor has three types of settings rigger triggers a preset of only relays to ON when the t level goes below the Low Level Set Point and triggers the F when the light level goes above the High Level Set...

Страница 33: ...tton te or configure a selected preset The procedures LC setting type as follows a preset by selecting the ACTIVATE or n displayed for activated preset and a blue ated preset EL or HIGH LEVEL button t...

Страница 34: ...to adjust the dimmer out dimming level Set centage Use the slider to adjust the level and the case when the there are multiple dimmer e same sensor this value is the dimmer RATIO ON button to initiate...

Страница 35: ...the commissioning process Use the slider to set the nd select the OK button me select the associated link to modify the value which is m time required for the dimmer to go from a lower to a higher rce...

Страница 36: ...Page 36 3 LOGs You can view the historical activity for a selected preset by selecting the LOGs tab Constant Lighting Controller...

Страница 37: ...ule by selecting the DISABLE or E button w the historical activity for a selected mode by selecting the s menu has two menus Time Schedules and Setup The as two submenus Y selecting the corresponding...

Страница 38: ...button ys screen lists screen lists the schedules in order of their grouping Grouping is he same area or function with the default being Global served U When a new schedule is created it is assigned...

Страница 39: ...dd Grouping link c Enter the grouping name and select the OK button 1 To change a schedule s grouping a Select the Change Grouping link b Select the new grouping by selecting the Select button Schedul...

Страница 40: ...ices You can specify to discover f devices or perform a full system discovery has ten submenus You access the configuration for each of lecting the corresponding button t DIALOG al Web Server OG Disco...

Страница 41: ...tware It does not apply to the creen version of the software tings stem Diagnostics screen provides information on memory mption and storage consumption ent Log Functions screen allows you to configur...

Страница 42: ...screen displays the most recent 100 system events and actions in chronological order You can refresh the list by clicking the Refresh List icon Event Logs recent 100 system events and esh the list by...

Страница 43: ...LIT DWLC 4150M071818 toll free 877 873 2797 direct 604 873 2797 lighting douglaslightingcontrols com www douglaslightingcontrols com Your Douglas Lighting Controls representative...

Отзывы: