RS485 shall be connected throughout the system per the simplified diagram below.
Both the Controller and Power Supply enclosures house the same RS485 junction
board. Beginning at the Controller; it is always connected from the Output (J5) to the
Input (J1) of the next enclosure.
RS485 SYSTEM DIAGRAM
Flash Head Connection
The connection between the Flash Head and the Power Supply requires an 8 conductor
cable.
NOTE:
This is the only connection to the Flash Head that is required.
WARNING:
If the cable is not color coded or numbered the instructions state the
installer must take notes of wiring to ensure that both the Flash Head and Power supply
get wired the same. If for example wire 1 is inserted in to location 4 by mistake severe
damage could result to the LED’s in the flash head. This will VOID all warranties.
Pin 1 or RED in the flash head must go to Pin1 RED in the power supply and so
on.
NOTE: The installer should provide this information to the site manager upon
completion for future reference when required
Controller
P/S 1
P/S 2
P/S 3