System Installation Requirements for EMC and Lightning Immunity:

 

 
1: Ensure the shield of the cable that connects the Flash head to the power supply is 
grounded at both ends. Make 360-degree ground connections around the braid or foil 
(avoid pigtails).  
 
2: For increased lightning protection adding a lightning rod that extends up 3 feet above 
the fixture and 18 inches away from the light is recommended. 
 
3: The drain-wire in the Flash Head cable must be connected to ground at both ends. 
Ensure that the wire is short as possible and avoid loops.  
 
4: Ensure the Flash Head is electrically bonded to the tower. Scrape away access paint/ 
powder coating as necessary. 
 
5: Minimize loop areas by tying all cables against the tower or passing through conduit. 
 
6: Ensure the Power Supply enclosure is electrically bonded to the tower. Scrape away 
access paint/ powder coating as necessary. 
 
7: Ground any spare/unused conductors in the Flash Head connection cable at both 
ends. 
 
8

: It is recommended that a minimum of ¾” conduit is used for all wiring ways. 

 
9: RS485 connections must be secure and shield or braiding must be grounded 
securely. 
 

Power Supply Specifications & Electrical Parameters: 

 
Flash Rate for L864/L865
 

 
The Red Beacon factory setting is 30FPM (Flash per minute).   
 
The White Strobe factory setting is 40 FPM (Flash per minute).  
 
 

Fault / Alarm Connections  

 
There are NO additional fault connections required in the Power Supply enclosure. All 
faults are sent to the Base controller via the RS485 communications. 

NOTE:

 It is vitally important that the RS485 connections are checked and secured. 

 
 

Содержание SafeSite D564B13001

Страница 1: ...fixture ratings DO NOT mount near gas or electric heaters Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel The use of acces...

Страница 2: ...less than the ignition temperature of the Hazardous Atmosphere Do not operate in ambient temperatures above those indicated on the Products label Do not operate if the fasteners are not properly tigh...

Страница 3: ...ISQUE D EXPLOSION LA SUBSTITUTIOND E COMPOSANTSP EUTR ENDRE CE MATERIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I DIVISION 1 Warning DO NOT mount near gas or electric heaters Equipment should be...

Страница 4: ...ument No 9100 127 2044 99 Rev C Release Date August 2020 Dialight Corporation 1501 Route 34 South Farmingdale NJ 07727 Tel 732 919 3119 Fax 732 751 5778 Web www dialight com Page 4 of 21 System Overvi...

Страница 5: ...ll VOID all warranties and could cause premature failures 1 Mains connection using a 3 conductor Power Cable 14AWG minimum to 10AWG maximum 2 An RS485 communications cable This is required to be a 3 c...

Страница 6: ...ute 34 South Farmingdale NJ 07727 Tel 732 919 3119 Fax 732 751 5778 Web www dialight com Page 6 of 21 Maximum cable diameter is 47 inches NOTE Liquid tight Conduit and TECK armored cable are acceptabl...

Страница 7: ...ed and tapped for all wiring connections WARNING No additional holes can be added to the enclosure NOTE Multiple grounding points are provided in the enclosure for protective and functional Earth Grou...

Страница 8: ...eb www dialight com Page 8 of 21 SIDE VIEW OF THE POWER SUPPLY ENCLOSURE Installation and Wiring WARNING Before any service or wiring is conducted ensure the DC at the breaker is off SYSTEM BLOCK DIAG...

Страница 9: ...NG Ground connection is required to provide safety and proper operation of the system WARNING There can be no more than 305Vac measured from Live to Earth ground on TB1 NOTE The load and voltage loss...

Страница 10: ...ble with RS 485 communication cable as purchased from Dialight part number CAB 183BFD Where represents the cable length in feet Option 2 When 2 Conductors a drain wire and either a shield or braid is...

Страница 11: ...Translator must be set to a unique address for each Power Supply connected to the Controller NOTE If ordered as a system typically SW1 will be factory set per this table i e JB4 xxxxxxxxxx would have...

Страница 12: ...ction between the Flash Head and the Power Supply requires an 8 conductor cable NOTE This is the only connection to the Flash Head that is required WARNING If the cable is not color coded or numbered...

Страница 13: ...ead and Power supply have the same protection board Two conductors are required for the Red Beacon and six for the White Strobe Red L864 Connections Terminal block J2 pins 1 and 2 White L865 Connectio...

Страница 14: ...ash head and Power supply have the same protection board Two conductors are required for the Red Beacon and two for the White Strobe Red L864 Connections Terminal block J2 pins 1 and 2 White L865 Conn...

Страница 15: ...d to the tower Scrape away access paint powder coating as necessary 5 Minimize loop areas by tying all cables against the tower or passing through conduit 6 Ensure the Power Supply enclosure is electr...

Страница 16: ...are factory set to the off position and positions 2 3 4 should be checked that they are set in the off position Micro Filter Assembly Image Capacitor Voltage Indication Safety Warning This unit holds...

Страница 17: ...Driver Diagnostic LED LED 1 Indicates more than 50V is present on the output and gives a good indication that the Beacon Driver module is working Microcontroller Board Diagnostic LED s LED 1 Red on th...

Страница 18: ...e incoming RS485 cable ports B Pin1 and A Pin3 can be seen The Common connection point is the center pin 2 Translator Indicators Translator Communications LED s Once communication has begun LED s labe...

Страница 19: ...nt No 9100 127 2044 99 Rev C Release Date August 2020 Dialight Corporation 1501 Route 34 South Farmingdale NJ 07727 Tel 732 919 3119 Fax 732 751 5778 Web www dialight com Page 19 of 21 Translator Indi...

Страница 20: ...ev C Release Date August 2020 Dialight Corporation 1501 Route 34 South Farmingdale NJ 07727 Tel 732 919 3119 Fax 732 751 5778 Web www dialight com Page 20 of 21 Mechanical Dimensions of Power Supply E...

Страница 21: ...Route 34 South Farmingdale NJ 07727 Tel 732 919 3119 Fax 732 751 5778 Web www dialight com Page 21 of 21 Replacement Part Numbers Exploded view REV ECO No DRN CKD APP QA CM DATE A 14911 SA DW JLM JP J...

Отзывы: