32
BASIC PARAMETERS
The basic parameters for the configuration of the inverter must necessarily be set during installation
Param.
description
m.u. Default Min Max Step
BASIC
P 3.5
SET
PRESSURE
(bar)
Sets the constant
working pressure
in the
system.
bar
3,5
1
10
0,1
psi
50
15
130 1,5
2P 2.5
SECOND SET
PRESSURE
(bar)
Sets a second working
pressure.
To activate
configure parameter EI in
ADV. parameters.
bar
2,5
1
10
0,1
psi
35
15
130 1,5
A 6.0
MOTOR
CURRENT
(A)
Sets the motor rated current
at the inverter output (rated
current of the motor)
At
low supply voltages,
the current set should leave a margin
(eg. + 15%) to compensate for the low voltage.
m.u.
Default
Min
Max Step
M/M 8.5
A
8.5
1
8,5
0,1
M/M 11
A
11
1
11
0,1
M/M 16
A
16
1
16
0,1
M/T 7
A
7
1
7
0,1
M/T 12
A
12
1
12
0,1
T/T 6
A
6
1
6
0,1
T/T 8
A
8
1
8
0,1
RO
MOTOR DIRECTION
OF ROTATION
ONLY FOR THREE-PHASE OUTPUT - Set the direction
of rotation
of the three-phase motor (CW / CCW)
Set pressure quick adjustment
To increase 0,1 bar press
SIMULTANEOUSLY
To decrease 0,1 bar press
SIMULTANEOUSLY
display the firmware version (FW)
To display the FW version of the
CONTROL BOARD (FWI) and the
POWER BOARD (FWP)
Bring
STEADYPRES out
of service (OFF)
Press
simultaneously
P_3.2
P_3.3
ENTER
P_3.1
ENTER