5.6 Battery Setup Menu
5.4 System Setup Menu
5.5 Basic Setup Menu
System Work Mode
Battery
Setting
Grid Setting
Gen Port
Use
Basic
Setting
System Setup
Device Info.
Advanced
Function
Basic
Set
Time Syncs
Beep
Auto Dim
24-Hour
Basic Setting
Year
Month
Day
Hour
Minute
Lock out all changes
Factory Reset
2019
03
09
15
17
Batt Mode
Lithium
Use Batt V
Battery Setting
Activate Battery
Max A Charge
Batt Capacity
Max A Discharge
40A
40A
400Ah
Batt
Mode
Use Batt %
No Batt
Lithium Battery
Max A charge-------- 0-185A
Max A Discharge-----0-185A
Activate Battery------Enable
AGM Battery
Max A charge-------- 0-185A
Max A Discharge-----0-185A
Activate Battery ------Enable
Batt Mode-------- Lithium
Batt Mode-------- Use Batt V or Use Batt V%
Batt Capacity-------- 50-2000Ah
No Batt --- No need to set other parameters,
keep the default value.
This is Basic Setup page.
This is System Setup page.
Lithium Mode
Shutdown
Low Batt
Restart
80%
30%
10%
00
Battery Setting
Set3
Batt
Grid Charge
Gen Charge
Grid Signal
Gen Signal
Gen Max Run Time
0.0 hours
Gen Down Time
0.5 hours
Battery Setting
Start
A
30%
30%
40A
40A
Batt
Set2
①
②
ʑ
This is Battery Setup page.
Start =30%---It indicates that the Generator will start when
the Battery capacity is less than 30% in the condition of
Off-grid mode.
A = 40A---It indicates the Current that the Generator
charges the Battery after started.
Gen Charge---The Switch that the Generator charges the
Battery.
Gen Signal ---It indicates whether the Generator's ATS
signal is on.
Max RunTime(x.xhous)Indicates that the generator is the
longest in a day,The time x.xhours can be run, and the
generator will be turned off when the time is up.
24.0hours (default) means that It keeps running without
shutting down.
DownTime(x.xhours)It indicates the delay of the
Generator to shut down after it has reached the run time.
ʏʑ
Start =30%---no use,for customization.
A = 40A--- It indicates the Current that the Grid charges
the Battery.
Grid Charge---The Switch that the Generator charges the
Battery.
Grid Signal ---Disable.
This is Grid Charge, you need select.
ʐ
Lithium Mode--This is BMS protocol.default is 0 please
reference the document(Approved Battery-Deye).
Shutdown 10%--the inverter will shutdown if the SOC is
below this.
Low Batt 20% --the inverter will shutdown if the SOC is
below this.
Restart 40% --Restart level when inverter shutdown.