12
DRYER CONTROLLER FACTORY DEFAULT PROGRAM SETTINGS
DRY
CYCLE
COOL
DOWN TIME
(MINUTES)
TOTAL
CYCLE TIME
(MINUTES)
DRYING
TEMPERATURE
(
0
F) (
0
C)
DRYER LOAD
1
5
35
180
82
Towels, pads, heavy cotton
2
2
20
170
77
Sheets, blended materials
3 5
25
180
82
Cotton
4 2
20
130
54
Synthetic
materials
5 2
25
175
79
Blended
materials
DRYER FAULT CODES
FAULT#
FAULT
DESCRIPTION
ACTION
F1
Shorted thermostat
sensor.
Dryer stops and “F1” flashes on the 4-digit display. When
short circuit on sensor input is removed, “LOAd” appears on
the 4-digit display and the remaining dry time is reset.
F2
Open thermostat
sensor.
Dryer stops and “F2” flashes on the 4-digit display. When a
good sensor is connected to sensor input, “LOAd” appears on
the 4-digit display and the remaining dry time is reset.
F3
EEPROM
corrupted.
Dryer will not start and “F3” appears on the 4-digit display.
The power to the dryer must be cycled to reset the controller.
Fault should only occur when starting a dry cycle.
F4
Gas valve on fault.
The drying temperature did not increase 1
º
F. in 15 minutes.
“F4” will flash on the display and the dry cycle will finish
without calling for heat (energizing gas valve). Opening the
door or pressing the STOP key will reset the fault and clear the
remaining time in the dry cycle.
F5 Temperature
fault.
The drying temperature is at least 25
º
F. above the temperature
setting. “F5” will flash on the 4-digit display and the dry cycle
will finish without calling for heat (energizing the gas valve).
The power to the dryer must be cycled to reset the controller.