![Devatec ElectroVap CMC Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/devatec/electrovap-cmc/electrovap-cmc_technical-manual_2488613007.webp)
Electro
V
ap
C
MC
S
team outlet
Use only factory supplied high temperature steam hose.
For distances up to
3 m.
(10 ft.) steam hose
alone
may be used
.
For distances greater than 3 m.
(10 ft.)
use insulated rigid copper tubing.
All steam lines
must
pitched and drained.
a -
The vertical rise should be
a minimum of 0.5 m (18 in.)
b -
The hose should be
properly supported to eliminate
c -
Steam hose
(radius of bend superior to 300 mm
- 12 ft.
)
d -
Duct work.
e - Obstacle.
f -
A condensate separator is needed at this point to
drain condensate.
g -
Steam hose
.
connection
h -
Condensate hose
important
: fill
trap
with water before
starting-up.
Unit installation
g = ø
25
Steam hose radius bend :
ø25 mm = 250 mm minimal
Number of steam outlet :
CMC 1-2-3
-4
= 1
outlet
ø 25 mm
5
Pho
tos non-contractuelles
CMC with filling cup plateform
j - Height of humidifier (s.a. page 4)
Duct applications :
To get a correct functionning of the CMC
humidifier in duct applications, the following
conditions must be fulfilled :
- duct pressure less than 100 mm (4 in.) of water
column
- in case the duct pressure is between 100 mm (4 in.)
and 250 mm (10 in.) of water column, a filling cup
plateform must be installed as per the left hand photo.
Содержание ElectroVap CMC
Страница 1: ......
Страница 22: ...ELMC 1 2 internal wiring Electrical installation 20 ElectroVap CMC Special US wiring scheme ...
Страница 23: ...ELMC 3 4 internal wiring Electrical installation 21 ElectroVap CMC Special US wiring scheme ...
Страница 24: ...ELMC 1 5 2 5 internal wiring Electrical installation 22 ElectroVap CMC Special US wiring scheme ...
Страница 28: ...ElectroVap CMC MAINTENANCE LIST TYPE CMC DETAILED MAINTENANCE WORK DATE NEXT DATE ON Maintenance 26 ...
Страница 29: ...ElectroVap CMC MAINTENANCE LIST TYPE CMC DETAILED MAINTENANCE WORK DATE NEXT DATE ON Maintenance 27 ...
Страница 30: ...ElectroVap CMC Drilling template for steam pipe ...