11
Installation
The steam from the cylinder enters the duct via a steam
distribution pipe. In order to obtain an optimum
performance of the humidifier, it is recommended that
these instructions be adhered to as far as possible.
Steam distribution pipe
selection
This table shows the number and the diameter of the
pipe(s) per unit.
For the optimum steam distribution, the longest pipe
should be prefered.
For duct of width inferior to 300 mm (12in), our B110 or
our special 6” steam pipes can be used.
For the CMC 1-2-3-4, install the pipes as indicated
below :
L
= length 290 – 590 – 790 – 1000 – 1250 – 1500 mm
(11.4 – 23.23 – 31.10 – 39.37 – 49.21 – 59.05 in.)
S
= end of pipe hole Ø 5 mm
R
= 4 holes of Ø 5 mm (0.20 in.)
H1
= 140 mm mini. (5.50in.)
H2
= 300 mm mini. (12in.) (IMPERATIVE)
8
Содержание ElectroVap CMC
Страница 1: ......
Страница 22: ...ELMC 1 2 internal wiring Electrical installation 20 ElectroVap CMC Special US wiring scheme ...
Страница 23: ...ELMC 3 4 internal wiring Electrical installation 21 ElectroVap CMC Special US wiring scheme ...
Страница 24: ...ELMC 1 5 2 5 internal wiring Electrical installation 22 ElectroVap CMC Special US wiring scheme ...
Страница 28: ...ElectroVap CMC MAINTENANCE LIST TYPE CMC DETAILED MAINTENANCE WORK DATE NEXT DATE ON Maintenance 26 ...
Страница 29: ...ElectroVap CMC MAINTENANCE LIST TYPE CMC DETAILED MAINTENANCE WORK DATE NEXT DATE ON Maintenance 27 ...
Страница 30: ...ElectroVap CMC Drilling template for steam pipe ...