The current measurement accuracy of the power supply modules is 10 %. I.e.
do not be alarmed if a power supply modules displays a current of e.g. 10 A
without a load attached.
The following table provides an overview on the maximum possible output
current for the DEV 5072 considering the AC input voltage range, the output
voltage setpoint, and the type and number of installed power supply modules.
It may be useful for adjusting the current alarm level of the device (via Web
Interface and/or via SNMP). Please note that the default value for the current
alarm level is defined as ~90 % of the absolute maximum possible output
current.
AC Input Voltage Range
(Module Output Power)
Output
Voltage
with
1 module
with
2 modules
with
3 modules
with
4 modules
12 V Power Supplies
Maximum Possible Output Current:
170…265 V AC (2400 W)
9.6 V
200.0 A
380.0 A
570.0 A
760.0 A
170…265 V AC (2400 W)
12.0 V
200.0 A
380.0 A
570.0 A
760.0 A
170…265 V AC (2400 W)
13.2 V
181.8 A
363.6 A
545.5 A
727.3 A
100…170 V AC (1500 W)
9.6 V
156.3 A
312.5 A
468.8 A
625.0 A
100…170 V AC (1500 W)
12.0 V
125.0 A
237.5 A
356.3 A
475.0 A
100…170 V AC (1500 W)
13.2 V
113.6 A
227.3 A
340.9 A
454.5 A
24 V Power Supplies
Maximum Possible Output Current:
170…265 V AC (2496 W)
19.2 V
104.0 A
197.6 A
296.4 A
395.2 A
170…265 V AC (2496 W)
24.0 V
104.0 A
197.6 A
296.4 A
395.2 A
170…265 V AC (2496 W)
29.0 V
86.1 A
172.1 A
258.2 A
344.3 A
100…170 V AC (1500 W)
19.2 V
78.1 A
156.3 A
234.4 A
312.5 A
100…170 V AC (1500 W)
24.0 V
62.5 A
118.8 A
178.1 A
237.5 A
100…170 V AC (1500 W)
29.0 V
51.7 A
103.4 A
155.2 A
206.9 A
48 V Power Supplies
Maximum Possible Output Current:
170…265 V AC (2496 W)
38.4 V
52.0 A
98.8 A
148.2 A
197.6 A
170…265 V AC (2496 W)
48.0 V
52.0 A
98.8 A
148.2 A
197.6 A
170…265 V AC (2496 W)
58.0 V
43.0 A
86.1 A
129.1 A
172.1 A
100…170 V AC (1500 W)
38.4 V
39.1 A
78.1 A
117.2 A
156.3 A
100…170 V AC (1500 W)
48.0 V
31.3 A
59.4 A
89.1 A
118.8 A
100…170 V AC (1500 W)
58.0 V
25.9 A
51.7 A
77.6 A
103.4 A
4.3.2
Factory Network Settings
The factory network settings of the device are:
IP-Address:
192.168.0.11
Netmask:
255.255.255.0
Gateway:
192.168.0.99
For changing the network setup, please refer to chapters 4.4.2.2 & 5.4.6.2.1.
4.3.3
Factory SNMP Settings
The factory SNMP settings are configured as follows:
Read Community:
public
Write Community:
private
Local/Remote changeable via SNMP:
Additionally, the default community for all four
Trap Destination IP Address
es is set
to
public
and all configurable traps are
disabled
. If an address is defined without the
explicit port assignment, the standard SNMP trap port
162
is assigned implicitly.
For changing the SNMP setup, please refer to chapter 5.4.6.2.2.