User Manual DEV 5072
58
Copyright DEV Systemtechnik GmbH 2016-2017
5.5.4.3.13
.application.upsBatteryTemperature
OID:
.1.3.6.1.4.1.21035.34.2.12.
0
Syntax:
INTEGER32
Access:
read-only
Description:
The UPS battery temperature in [°C/10]
"
9999
" means not available or not present
5.5.4.3.14
.application.upsBatteryTest
OID:
.1.3.6.1.4.1.21035.34.2.13.
0
Syntax:
INTEGER {inactive (1), active (2), notApplicable (3)}
Access:
read-write
Description:
The UPS battery test (please refer to chapter 5.4.4.2) status can be
read or set, possible values:
"
1
" inactive: the battery test is inactive
"
2
" active:
the battery test is active (read) or
is to be started (write)
"
3
" not applicable: An UPS battery test is not available, i.e. this
value is returned for devices without applied
UPS functionality
5.5.4.4
.surveillance
Содержание 5072
Страница 52: ...User Manual DEV 5072 52 Copyright DEV Systemtechnik GmbH 2016 2017 5 5 4 3 application ...
Страница 68: ...User Manual DEV 5072 68 Copyright DEV Systemtechnik GmbH 2016 2017 This Page Intentionally Left Blank ...
Страница 71: ...User Manual DEV 5072 Copyright DEV Systemtechnik GmbH 2016 2017 71 12 Notes ...