Implemented protocols in UNIGATE® EL
15.3.8 Universal Modbus TCP (client)
Modbus Timeout: 0 (not allowed)
The [EL] TCP response time is adjustable from 1 to 65 Sekunden (0 = without Response Time).
It is recommended to set a time.
Note:
If an incorrect read response occurs, the data is automatically set to 0xFF gesetzt.
15.3.8.1 Data structure Fieldbus side (e.g. PROFIBUS):
Applies to In and Out
1.
Byte: Trigger byte, optional (see chapter 15.5, Trigger Byte)
2.
Byte: Fieldbus length byte, optional (see chapter 15.6, Length Byte)
3.
Process data
Data structure
15.3.8.2 Data structure Ethernet side:
According to Modbus RTU Master Definition.
Supported functions:
Read coil status FC1
(No. of Points = Bit)
Read input status FC2
(No. of Points = Bit)
Read multiple register FC3
(No. of Points = Word)
Read input registers FC4
(No. of Points = Word)
Force single coil FC5
(No. of Points – not used = fix 1 Bit)
Preset single register FC6
(No. of Points – not used = fix 1 Word)
Force multiple coils FC15
(No. of Points = Bit)
Preset multiple register FC16
(No. of Points = Word)
Note:
status and coil = 1 Bit, register = 16 Bit.
FC 1 + 2 as well as FC 3 + 4 are the same in principle, the only difference being the definition of
the start address.
At FC1 it starts at,Zero, at FC2 at 10 000.
At FC3 it begins at 40 000, at FC4 at 30 000
Note FC5:
There is only 1 Bit set, even if you can adjust NoOfPoints in WINGATE.
Содержание UNIGATE EL-DeviceNet