Implemented protocols in UNIGATE® EL
Deutschmann Automation GmbH & Co. KG
49
UNIGATE
®
fieldbus gateway UNIGATE
®
EL - DeviceNet
™
V. 1.0
22.6.17
Storage division at Universal Modbus TCP (Server)
Example: Description of last Reg.Adr. (511)
FC16: [Slv ID] [FC] 01 FF 00 01 02 xx yy ...
Note: In configuration tools (e.g. Modscan) or descriptions, the address
is provided with an Offset of +1, i.e.: 0200. 01FF is transmitted as real raw
value for the address, and will also be evaluated in the script.
There is a "Exception Response 2"
if a register address from and inclu-
ding 512 (raw value) is described
.
If you try to write over the memory space of 1024 Byte, it is automatically
limited to 1024. There is no Exception Response.
Transferred to Little Endian Format
Note: FC1 (Coil status):
Client reads Coil
As start address you have to take a multiple of 8. Starting with 0. Thus 0, 8,
16, 24, ... 120 (raw value) are permitted.
This also applies to the write command „Force Coils“.
FC17 (user-specific)
Byte 1 ... 4 Fieldbus State of the UNIGATE
®
CL base
Byte 5 +6 Script Error (see Protocol Developer Help)
Byte 7 + 8 System Error (see Chapter 10).