Technical data
Deutschmann Automation GmbH & Co. KG
48
Fieldbus-Gateway UNIGATE
®
CX C4Map - PROFIBUS V. 1.0
28.9.20
15 Technical data
15.1 Device data
The technical data of the module is given in the table below.
No
.
Parameter
Data
Explanations
1
Location
Switch cabinet
DIN-rail mounting
2
Enclosure
IP20
Protection against foreign bodies and
water to IEC 529 (DIN 40050)
4
Service life
10 years
5
Housing size
46 x 117 x 111 mm
(screw-plug-connector included)
46 x 117 x 100 mm
(screw-plug connector not inclu-
ded))
W x D x H
6
Installation position
Any
7
Weight
246 g
8
Operating temperature
-40°C... +85°C
The negative temperatures are only
valid for the usual conditions (not con-
densing)
9
Storage/transport
temperature
-40ºC ... +85ºC
10 Atmospheric pressure
during operation
during transport
795 hPa ... 1080hPa
660 hPa ... 1080hPa
11 Installation altitude
2000 m
4000 m
Unrestricted
Restricted -
Ambient temperature
40ºC
12 Relative humidity
Max. 80 %
No condensation,
no corrosive atmosphere
14 External
power supply
10...33V DC
Standard power supply unit to DIN
19240
15 Current consumption at 24
VDC
Typ. 111 mA
max 134 mA
At 10V. typ. 200 mA
16 Supply at the Profibus-inter-
face
5V DC / max. 50 mA
(Max. 50 mA at < 30°C ambient tem-
perature)
17 Reverse voltage protection Yes
But does not function!
18 Short-circuit protection
Yes
19 Overload protection
Poly-Switch
Thermal fuse
20 Undervoltage detection
(USP)
9V DC
21 Emergency power supply
5 ms
Device fully operable
Table: Technical data of the module