background image

 

PART 3 

MAINTENANCE 

 

 

3.1) 

MAINTENANCE 

 

 

The  power  venter  must  be  inspected  bi-annually  by  a 
qualified technician. The points of inspection are listed 
below. 
 
 

3.1.1)  Motors 

 
Both  motors  must  rotate  freely.  Oil  at  the  beginning 
and the middle of the heating season with four drops of 
special  exterior  oil  suitable  for 

–35

o

  C  (-30

o

  F).  To 

access  the  motor,  remove  the  cover  of  the  fan-motor 
assembly. 
 
 

3.1.2)  Blower wheel 

 
Both blower wheels must be clean of soot, ash or any 
other  coating  which  might  inhibit  the  flow  of  air. 
Remove  all  foreign  material  from  the  vent  before 
operation.  To  access  the  blower  wheels,  remove  the 
fan-motor  assembly  cover  and  remove  the  blower 
wheels by unscrewing the attachment to the blower. 

3.1.3)  Pressure switch 

 
The  pressure  switch  must  operate  freely.  Ensure  that 
the  thermostat  is  on  and  the  oil  burner  is  running. 
Block  the  outlet  of  the  vent-hood  and  check  if  the 
burner  stops  immediately.  If  not,  the  proving  switch  is 
defective and should be replaced. See Section 2.2.2. 
 
 

3.1.4)  Back-flow damper 

 
The  back-flow  damper  must  be  clean  of  soot,  ash  or 
any coating which might inhibit the flow of air. Remove 
all  foreign  material  from  the  damper  before  operation. 
To  access  the  damper,  simply  remove  it  from  the 
connecting  pipe.  Be  sure  to  replace  it  in  the  proper 
position. 

 
 
 

 

Содержание SMH-1-BR

Страница 1: ...ied service technician Save these instructions for future reference Printed in Canada Printed on 100 recycled paper SIDEWALL VENTER Models SMH 1 DE SMH 6 DE SMH 3 DE SMH 4 DE SMH 5 DE SMH 1 BR SMH 4 B...

Страница 2: ......

Страница 3: ...reech of the heating unit and the power venter inlet This distance is the linear sum of all vertical and horizontal connecting pipes with a maximum of 4 90o elbows See Figure 1 Therefore the maximum e...

Страница 4: ...ed between two buildings where their use is common to both buildings The vent terminal shall be installed such a way that the flue gases do not jeopardize people overheat combustible structures or ent...

Страница 5: ...1 50 SWV 2M 2S SMH 4 DE Beckett or Riello HMS 027 to 035 6 0 65 to 0 85 SWV 1M 2S SMH 1 DE Beckett or Riello HMS 041 to 062 6 1 00 to 1 50 SWV 2M 2S SMH 4 DE Beckett or Riello AMP 075 to 105 5 0 50 to...

Страница 6: ...inside wall as closely as possible to the location where the vent pipe enters this wall Secure the junction box to the wall with two screws ensuring that the pressure switch is vertical If the wall i...

Страница 7: ...specified in Figures 5A to 5M With this arrangement the command to the power venting system will come from the heating unit through its operational control to the power venter motor When a steady stat...

Страница 8: ...st The installer must verify if the ignition of the burner is smooth when the heating unit operation is interrupted by means of the thermostat limit control or the power venter proving switch If the i...

Страница 9: ...m the vent before operation To access the blower wheels remove the fan motor assembly cover and remove the blower wheels by unscrewing the attachment to the blower 3 1 3 Pressure switch The pressure s...

Страница 10: ...DNS 0225 Rev A DNS 0226 Rev A FIGURE 1 SMH system General arrangement FIGURE 2 Main system dimensions...

Страница 11: ...11 DNS 0229 Rev A DNS 0227 Rev A DNS 0228 Rev A FIGURE 3 Location of the SMH system on the wall Installation on a COMBUSTIBLE wall FIGURE 4A Installation on a NON COMBUSTIBLE wall FIGURE 4B...

Страница 12: ...12 DNS 0230 Rev C DNS 0397 Rev C FIGURE 5A AMI AMT IM and OLS 2 speeds Beckett or Riello AMT SM and OLS 2 speeds Beckett FIGURE 5B...

Страница 13: ...13 DNS 0231 Rev C DNS 0232 Rev C FIGURE 5C AMI and HE 1 speed Beckett FIGURE 5D AMI and HE 1 speed Riello...

Страница 14: ...14 DNS 0407 Rev C FIGURE 5E AMT SM and OSR 2 speeds Riello...

Страница 15: ...15 FIGURE 5F AMP and OMB Riello...

Страница 16: ...16 FIGURE 5G AMP and OMB Beckett DNS 0622 Rev A...

Страница 17: ...17 FIGURE 5H FIGURE 5I DNS 0238 Rev B LO 1MQH LO 2M FBR 1 LO 1M3M MBP MBP F MBP 2 CCC and MBP U BRF and BFF DNS 0239 Rev B...

Страница 18: ...18 FIGURE 5J FIGURE 5K DNS 0233 Rev D DNS 0234 Rev D FIGURE 5J HMT HML HMI and HMD with triple aquastat Beckett or Riello HMR HML HMT HMI and HMD with double aquastat Beckett...

Страница 19: ...19 FIGURE 5L DNS 0235 Rev B DNS 0240 Rev C AME and HME Beckett FIGURE 5M Water heater CMO32 CMO50 30RB 32E2 50E2 IB 30 IB32 R and IB50 O Beckett...

Страница 20: ...0 For SMH 4 SMH 5 and SMH 6 12 Cover support insulation B00733 13A Cover support B00705 For SMH 1 and SMH 3 13B Cover support B01074 For SMH 4 SMH 5 and SMH 6 14 Gasket outlet pipe B01150 Brown 1 15 G...

Отзывы: