Air-to-water Heat Pump Split Versati
50
SPLIT TYPE
No.
Full Name
Displayed
Name
Range(°C)
Range(°F)
Default
14
Upper limit water-out
temperature at the
Weather-dependent
Mode for heating
Upper WT-
Heat
46~55°C[High temp.]
30~35°C[Normal temp.]
115~131°F[High temp.]
86~95°F
[Normal temp.]
48°C/118°F[High temp.]
35°C/95°F[Low temp.]
Set to default value when
the Weather-dependent
Mode setting changes.
15
Lower limit water-out
temperature at the
Weather-dependent
Mode for heating
Lower WT-
Heat
36~45°C[High temp.]
25~29°C[Normal temp.]
97~113°F[High temp.]
77~84°F
[Normal temp.]
40°C/104°F[High temp.]
29°C/84°F[Low temp.]
Set to default value when
the Weather-dependent
Mode setting changes.
16
Lower limit ambient
temperature at the
Weather-dependent
Mode for cooling
Lower AT-
Cool
10~25°C
50~77°F
25°C/77°F
Set to default value when
the Weather-dependent
Mode setting changes.
17
Upper limit
temperature at the
Weather-dependent
Mode for cooling
Upper AT-
Cool
26~48°C
79~118°F
40°C/104°F
Set to default value when
the Weather-dependent
Mode setting changes.
18
Upper limit room
temperature at the
Weather-dependent
Mode for cooling
Upper RT-
Cool
24~30°C
75~86°F
27°C/81°F
Set to default value when
the Weather-dependent
Mode setting changes.
19
Lower limit room
temperature at the
Weather-dependent
Mode for cooling
Lower RT-
Cool
18~23°C
64~73°F
22°C/72°F
Set to default value when
the Weather-dependent
Mode setting changes.
20
Upper limit water-out
temperature at the
Weather-dependent
Mode for cooling
Upper WT-
Cool
15~25°C[Without Floor]
22~25°C[With Floor]
59~77°F
[Without Floor]
72~77°F
[With Floor]
15°C/59°F[Without Floor]
23°C/73°F[With Floor]
Set to default value when
the Weather-dependent
Mode setting changes.
21
Lower limit water-out
temperature at the
weather-dependent
mode for cooling
Lower WT-
Cool
7~14°C[Without Floor]
18~21°C[With Floor]
45~57°F[Without Floor]
64~70°F[With Floor]
7°C/45°F[Without Floor]
18°C/64°F[With Floor]
Set to default value when
the Weather-dependent
Mode setting changes.
22
Temperature deviation
for cooling
ΔT-Cool
2~10°C
36~50°F
5°C/41°F
23
Temperature deviation
for heating
ΔT-Heat
2~10°C
36~50°F
10°C/50°F
24
Temperature deviation
for heating water
ΔT-hot water
2~8°C
36~46°F
5°C/41°F
25
Room temp variation
ΔT-Room
temp
1~5°C
36~41°F
2°C/36°F
26
Run time
Run time
1~10min
/
3min[Without Floor]
/
5min[With Floor]
27
Solar kit-start temp
variation
T-Solar start
10~30°C
50~86°F
15°C/59°F
28
Reserved
Reserved
0:00~24:00
/
8:00
29
Reserved
Reserved
0:00~24:00
/
18:00