5. Replace upper door and turn on electrical power.
See tables 9, 10, 11 and 12 for more details.
9.4
NORMAL OPERATION
The control will display codes under normal operation.
Please refer to table 14. The number displayed after
the codes represent the heat demand or CFM demand.
The number displayed with no letter before represent the
CFM. For exemple, «H4» followed by «3» means heating
at 40% with 300 CFM. Or code «F5» means Fan on at
500 CFM.
9.5
FAULT CODE RESET
To clear the fault code memory, push and hold the Fault
Recall Button for more than 5 seconds and less than 10
seconds. The display will energize horizontal upper and
lower segments for four seconds. This will clear faults in
the buffer displayed at power-up.
9.6
DIAGNOSTIQUE FEATURES
The control continuously monitors its own operation and
the operation of the system. If the failure is internal to
the control, the entire control should be replaced, as the
control is not field repairable.
If the sensed failure is in the system (external to control),
the control will show error codes. Refer to Section 12 for
diagnostic.
9.7
SEQUENCE OF OPERATION
The heating cycle is always initiated by a 24 volt signal
on W of the thermostat. When the controller senses 24
volts on W or the communicated message for heat call,
the following sequence occurs:
• High and low pressure switches are checked to in-
sure contacts are open.
• Pre-purge.
There are two different types of pre-purge; a normal
pre-purge and a learning-sequence pre-purge. During
a learning-sequence pre-purge, the inducer motor will
incrementally increase in RPM (stepping) until the low
and high pressure switches are both closed. After both
switches are sensed to be closed, the inducer motor will
continue to run for an additional 30 seconds before the
ignition trial.
A learning sequence pre-purge will be initiated under the
following conditions:
• First heat call after power reset.
• Every 25th heat call.
• Next heat attempt after a failed pre-purge (pressure
switch (es) does not close).
• Next heat attempt after a pressure switch has
opened unexpectedly during normal heating oper-
ation.
A normal pre-purge will not go through the incremen-
tal stepping process of the inducer motor and should be
much quicker. The inducer will start at a pre-determined
RPM (determined during learning-sequence pre-purge)
and this should close both pressure switches quickly.
Once both pressure switches are sensed to be closed,
the inducer will run for 25 seconds before the ignition trial
starts.
• Hot-surface igniter is energized during the pre-
purge period.
• The modulating gas valve is set to the highest pos-
sible rate (no flow yet).
• The main solenoids on the gas valve are energized
allowing gas to flow to the burners.
• When flame is proven, the ignition control is de-
energized - 8 second maximum trial times.
• The gas valve maintains 90% rate through the
warm-up period - 20 seconds (aka «Blower On De-
lay»).
9.8
SETTING INPUT RATE
Checking furnace input is important to prevent over fir-
ing beyond its design-rated input. Prior to checking the
furnace input, make certain that all other gas appliances
are shut off, with the exception of pilot burners. Refer to
section 6.
The furnace is shipped from the factory with #48 orifices.
They are sized for natural gas having a heating value of
1030 BTU/cu. ft. and a specific gravity of .64.
Since heating values vary geographically, the manifold
pressure may need to be changed. Consult the local gas
utility to obtain the yearly average heating value.
34
Содержание Chinook C105-M-V
Страница 24: ...Figure 10 Typical gas pipe arrangement 23...
Страница 27: ...Figure 11 Wiring Diagram 26...
Страница 39: ...Figure 14 Wiring Diagram Modulating t stat 38...
Страница 53: ...Table 17 CFM 52...
Страница 54: ...Figure 15 Dimensional Drawing 53...
Страница 55: ...14 PART LIST 54...
Страница 56: ...Figure 16 Exploded view 1 55...
Страница 57: ...Figure 17 Exploded view 2 56...
Страница 59: ...Table 19 Parts list continued 58...
Страница 60: ...Table 20 Parts list MS 59...
Страница 61: ...Table 21 Parts list MS continued 60...