Table 4 – Electrical Data
Unit size
Volts-Hertz-Phase
Operating
Operating
Maximum
Unit
Maximum fuse
range Min
range Max
unit amp
ampacity
CKT BRK amp
15,000
120-60-1
127
104
10.7
12.6
15
30,000
120-60-1
127
104
10.7
12.6
15
45,000
120-60-1
127
104
10.7
12.6
15
60,000
120-60-1
127
104
13.1
15.6
20
75,000
120-60-1
127
104
13.1
15.6
20
105,000
120-60-1
127
104
15.8
19
20
120,000
120-60-1
127
104
15.8
19
20
Table 5 – Thermostat Choice VS System
Heating
Cooling
Thermostat
HRV interlock
Interface
Smart Duct
system
system
at low CFM
board needed
compliant
Modulating
Alizé
Communicating
Yes
Yes
Yes
chinook
R02P032
Modulating
1 stage Non-Alizé
Communicating
Yes
Yes
No
chinook
Cooling unit
R02P032
Modulating
1&2 stage Non-Alizé
Modulating
No
No
No
chinook
Cooling unit/Heat pump
R02P030
25
Содержание Chinook C105-M-V
Страница 24: ...Figure 10 Typical gas pipe arrangement 23...
Страница 27: ...Figure 11 Wiring Diagram 26...
Страница 39: ...Figure 14 Wiring Diagram Modulating t stat 38...
Страница 53: ...Table 17 CFM 52...
Страница 54: ...Figure 15 Dimensional Drawing 53...
Страница 55: ...14 PART LIST 54...
Страница 56: ...Figure 16 Exploded view 1 55...
Страница 57: ...Figure 17 Exploded view 2 56...
Страница 59: ...Table 19 Parts list continued 58...
Страница 60: ...Table 20 Parts list MS 59...
Страница 61: ...Table 21 Parts list MS continued 60...