5

 

Figure 3:  Thermostat Wiring- Heating & Air Conditioning - 

With ECM Variable Speed Motor 

 

Figure 4:  Thermostat Wiring-Heating &Air 

Conditioning/HeatPump - With ECM Variable Speed Motor 

 

2.4 

INSTALLATION OF THE BURNER 

Also refer to the burner manufacturer’s instructions. 

1.  Position the mounting gasket between the mounting 

flange and the burner mounting plate. Align the holes in 
the burner mounting plate with the studs on the mounting 
flange and bolt securely in place. 

2.  Remove the burner drawer assembly or the air tube 

assembly; 

3.  Install the nozzle (refer to Technical Specifications, p.13); 
4.  Check the electrode settings; 
5.  Make the electrical connections; 
6.  Complete oil line connections. 

2.4.1 Nozzles 

The burner comes equipped with an appropriate nozzle. 
However, if another size or a replacement nozzle is required, 
use the manufacturer’s recommended spray angle and type a 
shown in Table 1 and based on a pump pressure of 100 psi.

 

Always select nozzle sizes by working back from the desired 
flow rate at operating pressure and not the nozzle marking. 

2.4.2  Air and Turbulator Settings 

Before starting the burner for the first time, adjust the air 
and turbulator settings to those listed in this manual. Once 
the burner becomes operational, final adjustments will be 
required. Refer to section 3 of this manual. 

2.4.3  Post purge delay adjustment 

The post purge delay on the oil-fired burners is factory set 
to zero second. This delay is applicable for all installations 
with chimney venting. For heating units installed with side 
wall venting and burners equipped with this feature, the 
post purge delay must be set to 15 seconds. No delay is 
required for Riello burners. Refer to the burner control 
instruction manual and markings for proper adjustment of 
the post purge delay. 

2.5 VENTING 

WARNING

 

Poisonous carbon monoxide gas hazard. 

Never install a hand operated damper in the vent pipe. 

However, any Underwriters Laboratories listed, 

electrically operated automatic type vent damper may 

be installed if desired. Be sure to follow the 

instructions provided with vent damper. Also, read 

and follow all instructions in this section of the 

manual. 

Failure to properly vent this furnace or other 
appliances can result in death, bodily injury and/or 
property damage. 

To ensure the safe and proper functioning of an oil 
furnace, it must always be connected to a flue with 
sufficient draft or to an approved side-wall venting system. 
In addition, it is strongly recommended to perform a 
complete inspection of all the existing venting systems. 

2.5.1 Masonry 

chimney 

This furnace can be vented into an existing masonry 
chimney. However, the unit must not be vented into a 
chimney into which a solid fuel burning furnace is already 
being vented. 

Before venting this furnace into a chimney, its condition 
must be checked and repairs made, if necessary. Also, 
the chimney lining and dimensions must conform to local 
and national codes. 

2.5.2  Factory Built Chimneys 

Oil fired furnaces are approved for use with “L” type vents. 
The unit may also be used with an approved chimney of 
proper dimensions and temperature ratings as specified in 
the installation code. Refer to chimney manufacturer’s 
instructions for proper installation. 

2.5.3 Draft 

Regulator 

This unit may be installed with or without a draft regulator. 
However, it is recommended that a draft regulator be 
installed in cases where the draft is either high or variable 
due to external conditions. Follow the instructions 
provided with the regulator. 

Содержание AMT154SDMA

Страница 1: ...ke Qu bec www dettson ca Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION...

Страница 2: ...ply air Temperature Rise Test 10 3 3 8 Limit Control Check 10 3 3 9 Restart after burner failure 10 4 MAINTENANCE 10 4 1 CLEANING THE HEAT EXCHANGER 10 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BV...

Страница 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Страница 4: ...re the ambient and return air temperatures are above 15 C 60 F In addition the furnace should be installed as closely as possible to the vent so that the connections are direct and kept to a minimum T...

Страница 5: ...ired for Riello burners Refer to the burner control instruction manual and markings for proper adjustment of the post purge delay 2 5 VENTING WARNING Poisonous carbon monoxide gas hazard Never install...

Страница 6: ...equate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace However home improvements su...

Страница 7: ...ated the return air must be sealed and also be directed to the space other than where the furnace is located 2 9 1 Air filter A properly sized air filter must be installed on the return air side of th...

Страница 8: ...heating or air conditioning mode This signal can be used to activate an electronic air cleaner that is not equipped with an air flow switch If the cleaner is equipped with an air flow switch the S te...

Страница 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted according to the Technical Specifica...

Страница 10: ...burner should restart after a few minutes The time required for the restart also depends on the adjustment of the blower OFF delay 3 3 9 Restart after burner failure 1 Set the thermostat lower than r...

Страница 11: ...uction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed in step 4 8 Re attach the assembly cover with the screws removed in step 2 9 Re establish powe...

Страница 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Страница 13: ...n 87 5 86 2 87 5 86 2 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse size Amps Control transformer VA External control power available Heating VA Cooling VA Heatin...

Страница 14: ...Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 90 13 45 sec 44 30 sec 38 3 min B 1 ON 2 OFF 1 10 13 30 sec 44 30 sec 38 3 min C 1 OFF 2 ON 1 10 13 30 sec 50 30 sec 38...

Страница 15: ...WITH AIR FILTER Table 10 Minimum clearances from combustible material LOCATION APPLICATION CLEARANCES combustible materials RECOMMANDED ACCESS FOR SERVICE FURNACE 2 54 cm 1 0 6 m 24 SUPPLY PLENUM WIT...

Страница 16: ...16 Figure 7 Furnace Dimensions...

Страница 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Страница 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Страница 19: ...19 Figure 10 Parts List With 4 Speed motor PSC B50095B...

Страница 20: ...TERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 GASKET SMOKE OUTLET 37 B03765 CLEAN OUT ASSEMBLY Item 36 included 38...

Страница 21: ...21 Figure 11 Parts List With variable speed motor ECM B50096C...

Страница 22: ...ELECTRICAL BOX COVER Panel only 32 B03118 01 ELECTRICAL KIT BVSO EXTERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 G...

Отзывы: