background image

 

11

Models: AMT1 and AMT2

75

90

105

120

140

155

RATING AND PERFORMANCE

Firing rate (USGPH)

0.50

0.65

0.75

0.85

1.00

1,10

Input (BTU/h)

70 000

91 000

105 000

119 000

140 000

154 000

Heating capacity (BTU/h)

57 000

74 000

85 000

97 000

115 000

126 000

Heating temperature rise
Flue draft minimum (W.C.)  (chimney)
Overfire pressure (W.C.) (chimney)
Flue draft minimum (W.C.)  (direct vent)
Overfire pressure (W.C.) (direct vent)

BECKETT BURNER; MODEL AFG (3450 rpm )

AFG-F6(2 7/8")

Low  firing rate baffle

APPLICABLE

Static disc, model

2 3/4" # 3383

Nozzle (Delavan)

0.50 - 70W

0.55 - 70B

0.65 - 70B

0.75 - 70B

0.85 - 70B

0.85 - 70B

Pump pressure (PSIG)

100

140

130

130

140

170

Combustion air adjustment (band/shutter)

0 / 5

0 / 7

0 / 8

1 / 8

4 / 4

2 / 8

AFUE %  (From CSA B212 standard and Canadian r

82,4%

80,9%

81,1%

81.4%

80.3%

80.1%

RIELLO BURNER 40-F (Chim ney vent)

Nozzle (Delavan)

0.40 - 70A

0.50  - 70W

0.65 - 70W

0.75 - 70B

0.85 - 70W

1.00 - 70W 

Pump pressure (PSIG)

155

170

135

130

140

125

Combustion air adjustment (turbulator/damper)

0 / 3

0 / 3.5

0 / 4

0 / 3

0 / 3.5

0 / 4

AFUE %  (From CSA B212 standard and Canadian r

84,4%

82,9%

83,1%

84.7%

83.9%

83.1%

RIELLO BURNER 40-BF (Direct vent)

Nozzle (Delavan)

0.75 - 70B

0.85 - 70W

1.00 - 70W 

Pump pressure (PSIG)

130

140

125

Combustion air adjustment (turbulator/damper)

0 / 3.75

1/4

1.5/5

AFUE %  (From CSA B212 standard and Canadian regulation)

84.7%

83.9%

83.1%

ELECTRICAL SYSTEM

Volts - Hertz - Phase

Operating voltage range

Rated current (Amps)

Minimum ampacity for w iring sizing

Max. w ire lenght

Max. fuse size (Amps)

Control transformer

External control pow er available     Heating

                                                         Cooling

BLOWER DATA

Blow er speed at 0.50" W.C. static pressure

MED-LOW

MED-HIGH

HIGH

MED-LOW

MED-HIGH

HIGH

Blow er speed at 0.25" W.C. static pressure

MED-LOW

MED-HIGH

HIGH

LOW

MED-LOW

MED-HIGH

Motor HP / Speeds

Blow er w heel size

GENERAL INFORMATION

Overall dimensions (w idth x depth x height)
Supply air opening
Return air opening
Filter quantity and size
Shipping w eight
Air conditioning, maximum output

(-0.06" to -0.025")

2 3/4" # 3383

26'

F3     (tube insertion 3 9/16")

F5     (tube insertion 3 9/16")

3 3/8" # 31646

(+0.12" to +0.27")

BF5 (tube insertion 2 3/4")

15

115 - 60 - 1

104 - 132

12.2

13 - 29°C (55 - 85°F)

APPLICABLE

AFG-F3 (tube insertion 2 7/8")

(-0.06" to -0.025")

13 - 29°C (55 - 85°F)

AFG-F3 (ins. 2 7/8")

(+0.010" to 0.025")

(max +0.025")

APPLICABLE

(+0.10" to +0.25")

40 VA

40 VA

30 VA

18.1

26'

20

40 VA

40 VA

30 VA

13.7

3 tons

5 tons

104 - 132

15.7

1/3 - 4

10" x 8"

(2)  12" x 20"

86 kg (190 lbs)

21¼" x  61½" x 35¼"

24" x 20"

(2)  16" x 20"

97 kg (215 lbs)

21¼" x 55" x 32"

20" x 20"
20" x 20"

3/4 - 4

12" x 10"

20" x 22"

115 - 60 - 1

Table 3: Technical specifications for models AMT1/AMT2 (with 3/4 motor) 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Table 4: Technical specifications for model AMT2 (with 1/3 HP motor) 

 
 
 
 
 
 
 
 
 
 
 
 

Models: AMT1 and AMT2

120

140

155

Blow er speed at 0.50" W.C. static pressure

MED-LOW

MED-HIGH

HIGH

Blow er speed at 0.25" W.C. static pressure

LOW

MED-LOW

MED-HIGH

Motor HP / Speeds

Blow er w heel size

1/3 - 4

10" x 10"

RATING AND PERFORMANCE     (SEE TABLE 3)

ELECTRICAL SYSTEM     (SEE TABLE 4 WITH 1/3 HP MOTOR)

BLOWER DATA

Содержание AMT100B34-IM2

Страница 1: ...lified service technician Printed in Canada Printed on 100 recycled paper AMT AMT S DNS 0537 Rev B AMiT AMT I Models AMT100B34 SM1 AMT100B34 IM2 AMiT AMT200B34 SM3 AMT200B34 IM2 AMiT INSTALLER SERVICE...

Страница 2: ...ment and blower regulator 8 Figure 2 Model AMT1 1M2 13 Figure 3 Model AMT1 SM1 13 Figure 4 Model AMT2 IM2 14 Figure 5 Model AMT2 SM3 14 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2 15 Figure 7 Wiring...

Страница 3: ...follow this caution may result in environmental pollution Remove and recycle all components or materials i e oil electrical and electronic components insulation etc before unit final disposal CAUTION...

Страница 4: ...nt of the furnace Table 1 indicates the minimum ventilation opening dimensions required Table 1 Minimum ventilation openings dimensions required in a closet or enclosure Input BTU h Width Height 75 00...

Страница 5: ...ly inspected This inspection should include the following a Inspection for any deterioration in the chimney or vent If deterioration is discovered the chimney must be repaired or the vent must be repl...

Страница 6: ...e primary relay When installing optional accessories on this appliance follow the manufacturer s installation instructions included with the accessory Other than wiring for the thermostat wire with a...

Страница 7: ...oper procedure for performing this operation is as follows a Start the appliance and from the test port near the BREACH PLATE VTK location or on the flue pipe just before the draft regulator chimney p...

Страница 8: ...duct static pressure Cooling The blower speed may be adjusted in the field to deliver the required airflow for cooling as outlined in Table 5 according to the selected model Constant Blower Switch Th...

Страница 9: ...burner from the furnace 5 Clean the secondary tubes and the primary cylinder with a stiff brush and remove debris with a vacuum cleaner 6 Before reassembling the furnace the heat exchanger and combust...

Страница 10: ...e telephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lb psi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross flue temperature F Am...

Страница 11: ...tage range Rated current Amps Minimum ampacity for w iring sizing Max w ire lenght Max fuse size Amps Control transformer External control pow er available Heating Cooling BLOWER DATA Blow er speed at...

Страница 12: ...FURNACE 20 32 cm 8 0 6 m 24 APPLICATION SIDES TOP FLUEPIPE EXTERNAL STATIC PRESSUREWITH AIR FILTER 0 2 W C 0 3 W C 0 4 W C 0 5 W C HIGH 1425 1350 1305 1250 MED HIGH 1130 1045 1000 950 MED LOW 840 810...

Страница 13: ...13 Figure 2 Model AMT1 IM2 Figure 3 Model AMT1 SM1...

Страница 14: ...14 Figure 4 Model AMT2 IM2 Figure 5 Model AMT2 SM3...

Страница 15: ...15 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2...

Страница 16: ...16 Figure 7 Wiring diagram AMT1 SM1 and AMT2 SM3 heating only...

Страница 17: ...17 Figure 8 Wiring diagram MT1 SM1 and AMT2 SM3 heating and optional cooling...

Страница 18: ...18 Figure 9 Parts list AMT1 IM2 B50054B...

Страница 19: ...EL B01133 24 ELECTRICAL PANEL INTERIOR B01209 25A ACCESS DOOR ASSEMBLY B01384 25B INSULATION ACCESS DOOR B01258 01 25C INSULATION ACCESS DOOR SIDE B01259 02 25D INSULATION ACCESS DOOR SIDE B01259 01 2...

Страница 20: ...20 Figure 10 Parts list AMT1 SM1 B50055B...

Страница 21: ...3 01 19 FRO NTPA NELA SSEM BLY B01827 01 20 INSULA TIO N FRO NTPA NEL B01722 21 THERM O DISCPLA TE B01843 22 O BSERV A TIO NDO O RA SSEM BLY B02111 23 CO RNERCO NDUIT B01818 24 CO M PA RTM ENTCO V ER...

Страница 22: ...22 Figure 11 Parts list AMT2 SM3 B50056B...

Страница 23: ...ONT PANEL B01767 19 ELECTRICAL WIRING RACEWAY B01830 20 WIRE CHANNEL B01763 21 FLOOR ASSEMBLY B01769 22A MOTOR ASSEMBLY1 3 HP Motor and motor support assembly B01890 01 22B BELLYBAND ASSEMBLY B01888 2...

Страница 24: ...24 Figure 12 Parts list AMT2 IM2 B50057C...

Страница 25: ...3B INSULATION ACCESS DOOR B01258 01 23C INSULATION ACCESS DOOR SIDE B01259 02 23D INSULATION ACCESS DOOR SIDE B01259 01 24 CORNER CONDUIT B01220 25 BURNER COMPARTMENT LEFT SIDE B01716 02 26 WIRE CHANN...

Страница 26: ...B34 SM3 AMT200B34 IM2 AMiT Fabriqu par Industries Dettson inc 3400 boulevard Industriel Sherbrooke Qu bec Canada J1L 1V8 www dettson ca INSTALLATEUR TECHNICIEN UTILISER LES RENSEIGNEMENTS DANS CE MANU...

Страница 27: ...FORMATION 9 FIGURES Figure 1 Ajustement du limiteur et r gulateur de ventilateur combin 7 Figure 2 Mod le AMT1 IM2 12 Figure 3 Mod le AMT1 SM1 12 Figure 4 Mod le AMT2 IM2 13 Figure 5 Mod le AMT2 SM3 1...

Страница 28: ...de chauffage Ne jamais laisser de chiffons ou de papier proximit de l unit AVERTISSEMENT RISQUE ENVIRONNEMENTAL Ne pas suivre cet avertissement peut polluer l environnement Retirer et recycler toutes...

Страница 29: ...avant de l appareil de chauffage central environ 152 4 mm 6 du plafond et du plancher de l espace ferm Le tableau 1 ci dessous indique les dimensions minimales requises pour les ouvertures de ventila...

Страница 30: ...ils de chauffage au combustible solide et ou CSA B139 Code d installation Cet appareil de chauffage central est homologu pour tre utilis avec un vent de type L Inspection pr alable l installation du s...

Страница 31: ...MENT L ext rieur de l unit doit poss der une mise la terre ininterrompue pour minimiser les risques de blessures corporelles si jamais un probl me lectrique se produisait Une vis verte de mise la terr...

Страница 32: ...d une trousse de test mesurer l indice de fum e et l ajuster une trace de fum e entre 0 et 1 Il est recommand d utiliser la trousse du test de fum e Bacharach ou un quivalent 2 Pour les installations...

Страница 33: ...t du ventilateur est contr l par le contr leur m canique bim tallique de ventilation et est ajust en usine pour D part 43 C 110 F et Arr t 32 C 90 F Ces ajustements doivent tre consid r s comme MAXIMU...

Страница 34: ...ut de l appareil de chauffage central 5 Nettoyer le tuyau secondaire et le cylindre principal l aide d une brosse rigide et d un aspirateur 6 Avant le r assemblage inspecter l changeur de chaleur et l...

Страница 35: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Страница 36: ...1 5 5 AFUE partir du standard CSA B212 et des lois canadiennes 84 7 83 9 83 1 SYST ME LECTRIQUE Volts Hertz Phase Tensions de fonctionnement volts Consommation Amps Amp minimum p r grosseur du fil Lon...

Страница 37: ...DESSUS LECONDUIT DERACCORDEMENT 22 86 cm 9 DEVANT FOURNAISE 20 32 cm 8 0 6 m 24 DESSUS APPLICATION C T 0 2 C E 0 3 C E 0 4 C E 0 5 C E HIGH 1425 1350 1305 1250 MED HIGH 1130 1045 1000 950 MED LOW 840...

Страница 38: ...12 Figure 2 Mod le AMT1 IM2 Figure 3 Mod le AMT1 SM1...

Страница 39: ...13 Figure 4 Mod le AMT2 IM2 Figure 5 Mod le AMT2 SM3...

Страница 40: ...14 Figure 6 Diagramme lectrique AMT1 IM2 et AMT2 IM2...

Страница 41: ...15 Figure 7 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage seulement...

Страница 42: ...16 Figure 8 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage et option climatisation...

Страница 43: ...17 Figure 9 Liste de pi ces mod le AMT1 IM2 B50054B...

Страница 44: ...UR B01716 01 23 PANNEAUM ONTAGEELECTRIQUE B01133 24 PANNEAUELECTRIQUEINTERIEUR B01209 25A ASSPORTED ACCES B01384 25B ISOLATIONPORTED ACCESS B01258 01 25C ISOLATIONCOTEPORTED ACCES B01259 02 25D ISOLAT...

Страница 45: ...19 Figure 10 Liste de pi ces mod le AMT1 SM1 B50055B...

Страница 46: ...B01723 01 19 A SSPA NNEA UA V A NT B01827 01 20 ISO LA TIO NPA NNEA UA V A NT B01722 21 PLA Q UEDETHERM O DISC B01843 22 A SSPO RTED O BSERV A TIO N B02111 23 CO NDUITDECO IN B01818 24 CO UV ERCLEDEB...

Страница 47: ...21 Figure 11 Liste de pi ces mod le AMT2 SM3 B50056B...

Страница 48: ...lation B0176 8 01 18 ISO LATIO NPAN NEAUAVANT B0176 7 19 ASSCO N DU ITELECTRIQ U E B0183 0 20 CAC HEFIL B0176 3 21 ASSPLAN CHE R B0176 9 22 A ASSM O TEU R 1 3HPC OM PLET C om prendm oteuretasse m blag...

Страница 49: ...23 Figure 12 Liste de pi ces mod le AMT2 IM2 B50057C B50057C...

Страница 50: ...et isolation B01384 23B ISOLATION PORTE D ACCESS B01258 01 23C ISOLATION COTE PORTE D ACCES B01259 02 23D ISOLATION COTE PORTE D ACCES B01259 01 24 CONDUIT DE COIN B01220 25 COTE GAUCHE COMPARTIMENT...

Отзывы: