PART 3  MAINTENANCE  

 

 
 

 

This furnace should never be operated without an air filter. 
Disposable filters should be replaced at least once a year. If 
equipped to provide cooling, filters should be replaced a minimum of 
twice a year. 
 
To avoid personal injury, make sure the power is “OFF” before 
servicing. 
 
ALWAYS KEEP THE OIL VALVE CLOSED IF THE BURNER IS 
SHUT DOWN FOR AN EXTENDED PERIOD OF TIME. 
 
 

WARNING 

Be sure to turn all power “OFF” upstream from 
the unit when servicing the furnace, unless power 
is required for specific operations. Failure to 
comply with this CAUTION can result in bodily 
harm and/or cause a fire hazard. 

 
 
For optimum performance, the oil burner nozzle should be replaced 
at least once a year. 
  
The procedure for the installation and/or replacement of a nozzle is 
outlined in the oil burner instruction manual which is supplied with 
the furnace. 
 
After replacing the nozzle, the burner should be adjusted in 
accordance with the “COMBUSTION CHECK” section of this 
manual. 
 
 

3.1) 

HEAT EXCHANGER CLEANING 

 

Normally, it is not necessary to clean the heat exchanger or flue pipe 
every year, but it is advisable to have a qualified service technician 
check the unit before each heating season to determine whether 
cleaning or replacement of parts is required. 
 
If cleaning is necessary, the following steps should be followed: 

1. 

Turn “OFF” all power upstream from the furnace

2.  Disconnect the flue pipe and breach plate. On sealed 

combustion systems do not

 

disconnect the flue pipe, remove 

the breach plate only;

 

3. 

Remove the radiator baffle; 

4.  Disconnect the oil line and remove the oil burner from the 

furnace; 

5. 

Clean the secondary tubes and the primary cylinder with a stiff 
brush and remove debris with a vacuum cleaner; 

6.  Before reassembling the furnace, the heat exchanger and 

combustion chamber should be inspected to determine if 
replacement is required; 

7. 

After cleaning, replace the radiator baffle, flue collar plate and 
oil burner; 

8. 

Readjust burner for proper operation.  

 

 

3.2) BLOWER 

REMOVAL

 

 

 
To remove the blower from the furnace: 

1. 

Turn “OFF” all power upstream from the furnace; 

2. 

Remove blower access door; 

3. 

Remove the 4 blower retaining wing-nuts; 

4. 

Slide the blower on the rails toward the rear of the unit; 

5. 

Reverse the above steps to reinstall the blower. (Refer to wiring 
diagram Figures 6, 7 and 8 of this instruction manual or the 
diagram located on the inside of the blower door to properly 
rewire the unit. 

 
 

3.3) 

BLOCKED VENT SHUT OFF (BVSO) 
CLEANING 

 

For continued safe operation, the Blocked Vent Shut-Off System 
(BVSO) needs to be inspected and maintained annually by a 
qualified service technician. 

1. 

Disconnect the power to the appliance;

 

2.  Remove the two screws holding down the BVSO assembly 

cover; 

3. 

Remove the cover; 

4.  Remove the two screws holding the control box to the heat 

transfer tube assembly. Sliding the control box in the appropriate 
direction will unlock it form the heat transfer tube assembly; 

5. 

Carefully remove any build-up from the thermal switch surface; 

 

CAUTION 

Do not dent or scratch the surface of the thermal 
switch. If the thermal switch is damaged, it must 
be replaced.  

 

6. 

Clear and remove any build-up or obstruction inside the heat 
transfer tube; 

7. 

Re-mount, lock and fasten the control box with the 2 screws 
removed in step 4; 

8. 

Re-attach the assembly cover with the screws removed in step 2; 

9. 

Re-establish power to the appliance. 

 
 

 

Содержание AMT100B34-IM2

Страница 1: ...lified service technician Printed in Canada Printed on 100 recycled paper AMT AMT S DNS 0537 Rev B AMiT AMT I Models AMT100B34 SM1 AMT100B34 IM2 AMiT AMT200B34 SM3 AMT200B34 IM2 AMiT INSTALLER SERVICE...

Страница 2: ...ment and blower regulator 8 Figure 2 Model AMT1 1M2 13 Figure 3 Model AMT1 SM1 13 Figure 4 Model AMT2 IM2 14 Figure 5 Model AMT2 SM3 14 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2 15 Figure 7 Wiring...

Страница 3: ...follow this caution may result in environmental pollution Remove and recycle all components or materials i e oil electrical and electronic components insulation etc before unit final disposal CAUTION...

Страница 4: ...nt of the furnace Table 1 indicates the minimum ventilation opening dimensions required Table 1 Minimum ventilation openings dimensions required in a closet or enclosure Input BTU h Width Height 75 00...

Страница 5: ...ly inspected This inspection should include the following a Inspection for any deterioration in the chimney or vent If deterioration is discovered the chimney must be repaired or the vent must be repl...

Страница 6: ...e primary relay When installing optional accessories on this appliance follow the manufacturer s installation instructions included with the accessory Other than wiring for the thermostat wire with a...

Страница 7: ...oper procedure for performing this operation is as follows a Start the appliance and from the test port near the BREACH PLATE VTK location or on the flue pipe just before the draft regulator chimney p...

Страница 8: ...duct static pressure Cooling The blower speed may be adjusted in the field to deliver the required airflow for cooling as outlined in Table 5 according to the selected model Constant Blower Switch Th...

Страница 9: ...burner from the furnace 5 Clean the secondary tubes and the primary cylinder with a stiff brush and remove debris with a vacuum cleaner 6 Before reassembling the furnace the heat exchanger and combust...

Страница 10: ...e telephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lb psi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross flue temperature F Am...

Страница 11: ...tage range Rated current Amps Minimum ampacity for w iring sizing Max w ire lenght Max fuse size Amps Control transformer External control pow er available Heating Cooling BLOWER DATA Blow er speed at...

Страница 12: ...FURNACE 20 32 cm 8 0 6 m 24 APPLICATION SIDES TOP FLUEPIPE EXTERNAL STATIC PRESSUREWITH AIR FILTER 0 2 W C 0 3 W C 0 4 W C 0 5 W C HIGH 1425 1350 1305 1250 MED HIGH 1130 1045 1000 950 MED LOW 840 810...

Страница 13: ...13 Figure 2 Model AMT1 IM2 Figure 3 Model AMT1 SM1...

Страница 14: ...14 Figure 4 Model AMT2 IM2 Figure 5 Model AMT2 SM3...

Страница 15: ...15 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2...

Страница 16: ...16 Figure 7 Wiring diagram AMT1 SM1 and AMT2 SM3 heating only...

Страница 17: ...17 Figure 8 Wiring diagram MT1 SM1 and AMT2 SM3 heating and optional cooling...

Страница 18: ...18 Figure 9 Parts list AMT1 IM2 B50054B...

Страница 19: ...EL B01133 24 ELECTRICAL PANEL INTERIOR B01209 25A ACCESS DOOR ASSEMBLY B01384 25B INSULATION ACCESS DOOR B01258 01 25C INSULATION ACCESS DOOR SIDE B01259 02 25D INSULATION ACCESS DOOR SIDE B01259 01 2...

Страница 20: ...20 Figure 10 Parts list AMT1 SM1 B50055B...

Страница 21: ...3 01 19 FRO NTPA NELA SSEM BLY B01827 01 20 INSULA TIO N FRO NTPA NEL B01722 21 THERM O DISCPLA TE B01843 22 O BSERV A TIO NDO O RA SSEM BLY B02111 23 CO RNERCO NDUIT B01818 24 CO M PA RTM ENTCO V ER...

Страница 22: ...22 Figure 11 Parts list AMT2 SM3 B50056B...

Страница 23: ...ONT PANEL B01767 19 ELECTRICAL WIRING RACEWAY B01830 20 WIRE CHANNEL B01763 21 FLOOR ASSEMBLY B01769 22A MOTOR ASSEMBLY1 3 HP Motor and motor support assembly B01890 01 22B BELLYBAND ASSEMBLY B01888 2...

Страница 24: ...24 Figure 12 Parts list AMT2 IM2 B50057C...

Страница 25: ...3B INSULATION ACCESS DOOR B01258 01 23C INSULATION ACCESS DOOR SIDE B01259 02 23D INSULATION ACCESS DOOR SIDE B01259 01 24 CORNER CONDUIT B01220 25 BURNER COMPARTMENT LEFT SIDE B01716 02 26 WIRE CHANN...

Страница 26: ...B34 SM3 AMT200B34 IM2 AMiT Fabriqu par Industries Dettson inc 3400 boulevard Industriel Sherbrooke Qu bec Canada J1L 1V8 www dettson ca INSTALLATEUR TECHNICIEN UTILISER LES RENSEIGNEMENTS DANS CE MANU...

Страница 27: ...FORMATION 9 FIGURES Figure 1 Ajustement du limiteur et r gulateur de ventilateur combin 7 Figure 2 Mod le AMT1 IM2 12 Figure 3 Mod le AMT1 SM1 12 Figure 4 Mod le AMT2 IM2 13 Figure 5 Mod le AMT2 SM3 1...

Страница 28: ...de chauffage Ne jamais laisser de chiffons ou de papier proximit de l unit AVERTISSEMENT RISQUE ENVIRONNEMENTAL Ne pas suivre cet avertissement peut polluer l environnement Retirer et recycler toutes...

Страница 29: ...avant de l appareil de chauffage central environ 152 4 mm 6 du plafond et du plancher de l espace ferm Le tableau 1 ci dessous indique les dimensions minimales requises pour les ouvertures de ventila...

Страница 30: ...ils de chauffage au combustible solide et ou CSA B139 Code d installation Cet appareil de chauffage central est homologu pour tre utilis avec un vent de type L Inspection pr alable l installation du s...

Страница 31: ...MENT L ext rieur de l unit doit poss der une mise la terre ininterrompue pour minimiser les risques de blessures corporelles si jamais un probl me lectrique se produisait Une vis verte de mise la terr...

Страница 32: ...d une trousse de test mesurer l indice de fum e et l ajuster une trace de fum e entre 0 et 1 Il est recommand d utiliser la trousse du test de fum e Bacharach ou un quivalent 2 Pour les installations...

Страница 33: ...t du ventilateur est contr l par le contr leur m canique bim tallique de ventilation et est ajust en usine pour D part 43 C 110 F et Arr t 32 C 90 F Ces ajustements doivent tre consid r s comme MAXIMU...

Страница 34: ...ut de l appareil de chauffage central 5 Nettoyer le tuyau secondaire et le cylindre principal l aide d une brosse rigide et d un aspirateur 6 Avant le r assemblage inspecter l changeur de chaleur et l...

Страница 35: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Страница 36: ...1 5 5 AFUE partir du standard CSA B212 et des lois canadiennes 84 7 83 9 83 1 SYST ME LECTRIQUE Volts Hertz Phase Tensions de fonctionnement volts Consommation Amps Amp minimum p r grosseur du fil Lon...

Страница 37: ...DESSUS LECONDUIT DERACCORDEMENT 22 86 cm 9 DEVANT FOURNAISE 20 32 cm 8 0 6 m 24 DESSUS APPLICATION C T 0 2 C E 0 3 C E 0 4 C E 0 5 C E HIGH 1425 1350 1305 1250 MED HIGH 1130 1045 1000 950 MED LOW 840...

Страница 38: ...12 Figure 2 Mod le AMT1 IM2 Figure 3 Mod le AMT1 SM1...

Страница 39: ...13 Figure 4 Mod le AMT2 IM2 Figure 5 Mod le AMT2 SM3...

Страница 40: ...14 Figure 6 Diagramme lectrique AMT1 IM2 et AMT2 IM2...

Страница 41: ...15 Figure 7 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage seulement...

Страница 42: ...16 Figure 8 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage et option climatisation...

Страница 43: ...17 Figure 9 Liste de pi ces mod le AMT1 IM2 B50054B...

Страница 44: ...UR B01716 01 23 PANNEAUM ONTAGEELECTRIQUE B01133 24 PANNEAUELECTRIQUEINTERIEUR B01209 25A ASSPORTED ACCES B01384 25B ISOLATIONPORTED ACCESS B01258 01 25C ISOLATIONCOTEPORTED ACCES B01259 02 25D ISOLAT...

Страница 45: ...19 Figure 10 Liste de pi ces mod le AMT1 SM1 B50055B...

Страница 46: ...B01723 01 19 A SSPA NNEA UA V A NT B01827 01 20 ISO LA TIO NPA NNEA UA V A NT B01722 21 PLA Q UEDETHERM O DISC B01843 22 A SSPO RTED O BSERV A TIO N B02111 23 CO NDUITDECO IN B01818 24 CO UV ERCLEDEB...

Страница 47: ...21 Figure 11 Liste de pi ces mod le AMT2 SM3 B50056B...

Страница 48: ...lation B0176 8 01 18 ISO LATIO NPAN NEAUAVANT B0176 7 19 ASSCO N DU ITELECTRIQ U E B0183 0 20 CAC HEFIL B0176 3 21 ASSPLAN CHE R B0176 9 22 A ASSM O TEU R 1 3HPC OM PLET C om prendm oteuretasse m blag...

Страница 49: ...23 Figure 12 Liste de pi ces mod le AMT2 IM2 B50057C B50057C...

Страница 50: ...et isolation B01384 23B ISOLATION PORTE D ACCESS B01258 01 23C ISOLATION COTE PORTE D ACCES B01259 02 23D ISOLATION COTE PORTE D ACCES B01259 01 24 CONDUIT DE COIN B01220 25 COTE GAUCHE COMPARTIMENT...

Отзывы: