1.4.2) Duct 

recommendations

 

 

The proper sizing of warm air ducts is necessary to ensure 
satisfactory furnace operation.  Ductwork should be in accordance 
with the latest editions of ANSI / NFPA-90A (Installation of Air 
Conditioning and Ventilating Systems) and NFPA-90B (Warm Air 
Heating and Air Conditioning Systems) or Canadian equivalent. 

 

The supply air ductwork should be attached to the flanged front 
opening provided at the discharge end of the furnace and the return 
air ductwork should be attached to the flanged rear opening of the 
furnace. See Figures 2, 3, 4 and 5, for the dimensions of these 
openings, based on the model selected. 

 

The following recommendations should be followed when installing 
ductwork: 

a. 

Install locking type dampers in all branches of the individual 
ducts to balance out the system. Dampers should be adjusted 
to achieve the desired static pressure at the outlet of the 
furnace; 

b. 

A flexible duct connector of non-combustible material should be 
installed on both the supply and return air sections of the unit. 
On applications where an extremely quiet operation is 
necessary, the first 3 m (10

')

 of supply and return ducts should 

be internally lined with acoustical material, if possible; 

c. 

In cases where the return air grille is located close to the fan 
inlet, there should be at least one 90

o

 air turn between the fan 

inlet and grille. Further reduction in noise levels can be 
achieved by installing acoustical air turning vanes or by lining 
the duct as described in b. above; 

d. 

When a single air grille is used, the duct between the grille and 
the furnace must be the same size as the return opening in the 
furnace. 

 

WARNING 

Return air grilles and warm air registers must not 

be obstructed. 

 

CAUTION 

When ducting supplies air to a space other than 
where the furnace is located, the return air ducts 
must be sealed and also be directed to the space 
other than where the furnace is located. Incorrect 
ductwork termination and sealing will create a 
hazardous condition that can lead to bodily harm. 

 

1.4.3)  Venting instructions (chimney installation) 

 

The furnace must be vented to the outside, in accordance with local 
codes and other authorities having jurisdiction. 
 

CAUTION 

Oil fired appliances must be connected to flues 
having sufficient draft at all times to ensure safe 
and proper combustion. 

 

For additional venting information refer to ANSI / NFPA 211 
Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances 
and/or CSA B139 Installation Code. 

 

This furnace is certified for use with a Type “L” vent. 

 

Pre-installation inspection of vent system  

 

Before installing this furnace, it is highly recommended that any 
existing vent system be completely inspected. 

 

This inspection should include the following: 

a.  Inspection for any deterioration in the chimney or vent. If 

deterioration is discovered, the chimney must be repaired or 
the vent must be replaced; 

 

b. 

Inspection to ascertain that the vent system is clear and free of 
obstructions. Any blockages must be removed before installing 
this furnace; 

c. 

Cleaning the chimney or vent if previously used for venting a 
solid fuel burning appliance or fireplace; 

d.  Confirming that all unused chimney or vent connections are 

properly sealed; 

e. 

Verification that the chimney is properly lined and sized per the 
applicable codes (refer to list of codes in section 1.2). 

 

Masonry Chimney 

 

This furnace can be vented into an existing masonry chimney. 
However, it must not be vented into a chimney servicing a solid fuel 
burning appliance. Before venting this furnace into a chimney, the 
chimney must be checked for deterioration and repaired if 
necessary. The chimney must be properly lined and sized per local 
or national codes. 

 

If the furnace is vented into a common chimney, the chimney must 
be of sufficient area to accommodate the total flue products of all 
appliances vented into the chimney. 

 

Following are the preconditions for a safe venting system: 

a. 

Ensure that the chimney flue is clear of any dirt or debris; 

b. 

Ensure that the chimney is not servicing an open fireplace; 

c. 

Never reduce the pipe size below the outlet size of the furnace; 

d. 

All pipes should be supported using the proper clamps and/or 
straps. These supports should be at least every 1.2 m (4

')

e. 

All horizontal runs of pipe should have an upward slope of at 
least 2 cm per 1 m (1/4

"

 per 1

')

f. 

All runs of pipe should be as short as possible with as few turns 
as possible; 

g. 

Seams should be tightly joined and checked for leaks; 

h. 

The flue pipe must not extend into the chimney but be flush 
with the inside wall; 

i. 

The chimney must extend 0.9 m (3

')

 above the highest point 

where it passes through a roof of a building and at least 0.6 m 
(2

')

 higher than any portion of a building within a horizontal 

distance of 3 m (10

')

. It shall also be extended at lest 1.5 m (5

')

 

above the highest connected equipment flue collar; 

j. 

Check local codes for any variances. 

 

Factory Built Chimneys 

 

The furnace may be used with an approved factory built chimney. 
Refer to chimney manufacturer’s instructions for proper installation. 
 

1.4.4) Venting 

instructions 

(Sealed Combustion System) 

 

Refer to the sealed combustion system (VTK) Instruction Manual 
(X40142). 

 

1.4.5) Oil 

burner

 

 
This furnace is supplied with a high pressure atomizing retention 
head type burner (for use with not heavier than grade 2 fuel oil). If 
the burner model is a Beckett AFG, the mounting flange is fixed to 
the burner air tube and no adjustment is required for

 

insertion 

length. If a Riello burner is used, refer to the Technical 
Specifications, Table 3 for the insertion length. 
 

Содержание AMT100B34-IM2

Страница 1: ...lified service technician Printed in Canada Printed on 100 recycled paper AMT AMT S DNS 0537 Rev B AMiT AMT I Models AMT100B34 SM1 AMT100B34 IM2 AMiT AMT200B34 SM3 AMT200B34 IM2 AMiT INSTALLER SERVICE...

Страница 2: ...ment and blower regulator 8 Figure 2 Model AMT1 1M2 13 Figure 3 Model AMT1 SM1 13 Figure 4 Model AMT2 IM2 14 Figure 5 Model AMT2 SM3 14 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2 15 Figure 7 Wiring...

Страница 3: ...follow this caution may result in environmental pollution Remove and recycle all components or materials i e oil electrical and electronic components insulation etc before unit final disposal CAUTION...

Страница 4: ...nt of the furnace Table 1 indicates the minimum ventilation opening dimensions required Table 1 Minimum ventilation openings dimensions required in a closet or enclosure Input BTU h Width Height 75 00...

Страница 5: ...ly inspected This inspection should include the following a Inspection for any deterioration in the chimney or vent If deterioration is discovered the chimney must be repaired or the vent must be repl...

Страница 6: ...e primary relay When installing optional accessories on this appliance follow the manufacturer s installation instructions included with the accessory Other than wiring for the thermostat wire with a...

Страница 7: ...oper procedure for performing this operation is as follows a Start the appliance and from the test port near the BREACH PLATE VTK location or on the flue pipe just before the draft regulator chimney p...

Страница 8: ...duct static pressure Cooling The blower speed may be adjusted in the field to deliver the required airflow for cooling as outlined in Table 5 according to the selected model Constant Blower Switch Th...

Страница 9: ...burner from the furnace 5 Clean the secondary tubes and the primary cylinder with a stiff brush and remove debris with a vacuum cleaner 6 Before reassembling the furnace the heat exchanger and combust...

Страница 10: ...e telephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lb psi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross flue temperature F Am...

Страница 11: ...tage range Rated current Amps Minimum ampacity for w iring sizing Max w ire lenght Max fuse size Amps Control transformer External control pow er available Heating Cooling BLOWER DATA Blow er speed at...

Страница 12: ...FURNACE 20 32 cm 8 0 6 m 24 APPLICATION SIDES TOP FLUEPIPE EXTERNAL STATIC PRESSUREWITH AIR FILTER 0 2 W C 0 3 W C 0 4 W C 0 5 W C HIGH 1425 1350 1305 1250 MED HIGH 1130 1045 1000 950 MED LOW 840 810...

Страница 13: ...13 Figure 2 Model AMT1 IM2 Figure 3 Model AMT1 SM1...

Страница 14: ...14 Figure 4 Model AMT2 IM2 Figure 5 Model AMT2 SM3...

Страница 15: ...15 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2...

Страница 16: ...16 Figure 7 Wiring diagram AMT1 SM1 and AMT2 SM3 heating only...

Страница 17: ...17 Figure 8 Wiring diagram MT1 SM1 and AMT2 SM3 heating and optional cooling...

Страница 18: ...18 Figure 9 Parts list AMT1 IM2 B50054B...

Страница 19: ...EL B01133 24 ELECTRICAL PANEL INTERIOR B01209 25A ACCESS DOOR ASSEMBLY B01384 25B INSULATION ACCESS DOOR B01258 01 25C INSULATION ACCESS DOOR SIDE B01259 02 25D INSULATION ACCESS DOOR SIDE B01259 01 2...

Страница 20: ...20 Figure 10 Parts list AMT1 SM1 B50055B...

Страница 21: ...3 01 19 FRO NTPA NELA SSEM BLY B01827 01 20 INSULA TIO N FRO NTPA NEL B01722 21 THERM O DISCPLA TE B01843 22 O BSERV A TIO NDO O RA SSEM BLY B02111 23 CO RNERCO NDUIT B01818 24 CO M PA RTM ENTCO V ER...

Страница 22: ...22 Figure 11 Parts list AMT2 SM3 B50056B...

Страница 23: ...ONT PANEL B01767 19 ELECTRICAL WIRING RACEWAY B01830 20 WIRE CHANNEL B01763 21 FLOOR ASSEMBLY B01769 22A MOTOR ASSEMBLY1 3 HP Motor and motor support assembly B01890 01 22B BELLYBAND ASSEMBLY B01888 2...

Страница 24: ...24 Figure 12 Parts list AMT2 IM2 B50057C...

Страница 25: ...3B INSULATION ACCESS DOOR B01258 01 23C INSULATION ACCESS DOOR SIDE B01259 02 23D INSULATION ACCESS DOOR SIDE B01259 01 24 CORNER CONDUIT B01220 25 BURNER COMPARTMENT LEFT SIDE B01716 02 26 WIRE CHANN...

Страница 26: ...B34 SM3 AMT200B34 IM2 AMiT Fabriqu par Industries Dettson inc 3400 boulevard Industriel Sherbrooke Qu bec Canada J1L 1V8 www dettson ca INSTALLATEUR TECHNICIEN UTILISER LES RENSEIGNEMENTS DANS CE MANU...

Страница 27: ...FORMATION 9 FIGURES Figure 1 Ajustement du limiteur et r gulateur de ventilateur combin 7 Figure 2 Mod le AMT1 IM2 12 Figure 3 Mod le AMT1 SM1 12 Figure 4 Mod le AMT2 IM2 13 Figure 5 Mod le AMT2 SM3 1...

Страница 28: ...de chauffage Ne jamais laisser de chiffons ou de papier proximit de l unit AVERTISSEMENT RISQUE ENVIRONNEMENTAL Ne pas suivre cet avertissement peut polluer l environnement Retirer et recycler toutes...

Страница 29: ...avant de l appareil de chauffage central environ 152 4 mm 6 du plafond et du plancher de l espace ferm Le tableau 1 ci dessous indique les dimensions minimales requises pour les ouvertures de ventila...

Страница 30: ...ils de chauffage au combustible solide et ou CSA B139 Code d installation Cet appareil de chauffage central est homologu pour tre utilis avec un vent de type L Inspection pr alable l installation du s...

Страница 31: ...MENT L ext rieur de l unit doit poss der une mise la terre ininterrompue pour minimiser les risques de blessures corporelles si jamais un probl me lectrique se produisait Une vis verte de mise la terr...

Страница 32: ...d une trousse de test mesurer l indice de fum e et l ajuster une trace de fum e entre 0 et 1 Il est recommand d utiliser la trousse du test de fum e Bacharach ou un quivalent 2 Pour les installations...

Страница 33: ...t du ventilateur est contr l par le contr leur m canique bim tallique de ventilation et est ajust en usine pour D part 43 C 110 F et Arr t 32 C 90 F Ces ajustements doivent tre consid r s comme MAXIMU...

Страница 34: ...ut de l appareil de chauffage central 5 Nettoyer le tuyau secondaire et le cylindre principal l aide d une brosse rigide et d un aspirateur 6 Avant le r assemblage inspecter l changeur de chaleur et l...

Страница 35: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Страница 36: ...1 5 5 AFUE partir du standard CSA B212 et des lois canadiennes 84 7 83 9 83 1 SYST ME LECTRIQUE Volts Hertz Phase Tensions de fonctionnement volts Consommation Amps Amp minimum p r grosseur du fil Lon...

Страница 37: ...DESSUS LECONDUIT DERACCORDEMENT 22 86 cm 9 DEVANT FOURNAISE 20 32 cm 8 0 6 m 24 DESSUS APPLICATION C T 0 2 C E 0 3 C E 0 4 C E 0 5 C E HIGH 1425 1350 1305 1250 MED HIGH 1130 1045 1000 950 MED LOW 840...

Страница 38: ...12 Figure 2 Mod le AMT1 IM2 Figure 3 Mod le AMT1 SM1...

Страница 39: ...13 Figure 4 Mod le AMT2 IM2 Figure 5 Mod le AMT2 SM3...

Страница 40: ...14 Figure 6 Diagramme lectrique AMT1 IM2 et AMT2 IM2...

Страница 41: ...15 Figure 7 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage seulement...

Страница 42: ...16 Figure 8 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage et option climatisation...

Страница 43: ...17 Figure 9 Liste de pi ces mod le AMT1 IM2 B50054B...

Страница 44: ...UR B01716 01 23 PANNEAUM ONTAGEELECTRIQUE B01133 24 PANNEAUELECTRIQUEINTERIEUR B01209 25A ASSPORTED ACCES B01384 25B ISOLATIONPORTED ACCESS B01258 01 25C ISOLATIONCOTEPORTED ACCES B01259 02 25D ISOLAT...

Страница 45: ...19 Figure 10 Liste de pi ces mod le AMT1 SM1 B50055B...

Страница 46: ...B01723 01 19 A SSPA NNEA UA V A NT B01827 01 20 ISO LA TIO NPA NNEA UA V A NT B01722 21 PLA Q UEDETHERM O DISC B01843 22 A SSPO RTED O BSERV A TIO N B02111 23 CO NDUITDECO IN B01818 24 CO UV ERCLEDEB...

Страница 47: ...21 Figure 11 Liste de pi ces mod le AMT2 SM3 B50056B...

Страница 48: ...lation B0176 8 01 18 ISO LATIO NPAN NEAUAVANT B0176 7 19 ASSCO N DU ITELECTRIQ U E B0183 0 20 CAC HEFIL B0176 3 21 ASSPLAN CHE R B0176 9 22 A ASSM O TEU R 1 3HPC OM PLET C om prendm oteuretasse m blag...

Страница 49: ...23 Figure 12 Liste de pi ces mod le AMT2 IM2 B50057C B50057C...

Страница 50: ...et isolation B01384 23B ISOLATION PORTE D ACCESS B01258 01 23C ISOLATION COTE PORTE D ACCES B01259 02 23D ISOLATION COTE PORTE D ACCES B01259 01 24 CONDUIT DE COIN B01220 25 COTE GAUCHE COMPARTIMENT...

Отзывы: