background image

 

 

CAUTION

 

When ducting supplies air to a space other than where 
the  furnace  is  located,  the  return  air  ducts  must  be 
sealed  and  also  directed  to  the  space  other  than 
where  the  furnace  is  located.  Incorrect  ductwork 
termination  and  sealing  will  create  a  hazardous 
condition which can lead to bodily harm. 

 
Install  air  conditioning  cooling  coil  (evaporator)  downstream  from  the 
supply air plenum of the furnace. If a separate evaporator and blower 
unit is used, install good sealing dampers for air flow control.  Cold air 
from  the  evaporator  coil  going  through  the  furnace  could  cause 
condensation and shorten furnace life. 
 
 

CAUTION 

Dampers (purchased locally) MUST be automatic. 

 

 

 

WARNING 

 

Poisonous carbon monoxide gas hazard. 

 

Do  NOT  draw  return  air  from  inside  a  closet  or 
utility  room.    Return  air  duct  MUST  be  sealed  to 
furnace casing. 

 

Failure  to  properly  seal  duct  can  result  in  death, 
personal injury and/or property damage. 

 
 

WARNING 

 

Poisonous carbon monoxide gas hazard. 

 

Install  evaporator  coil  on  the  supply  side  of  the 
furnace ducting. 

 

Evaporator  coil  installed  in  return  side  ducting  can 
cause  condensation  to  form  inside  heat  exchanger 
resulting in heat exchanger failure. This could result 
in death, personal injury and/or property damage. 

 

 
 
 

 
 
 

PART 2 

OPERATION 

 

 

2.1) 

SEQUENCE OF OPERATION 

 

2.1.1)  Sequence of operation - Beckett AFG and 

Riello 40-F 

 

1. 

Normally  open  contact  (T-T)  on  primary  relay  closed  when 
thermostat calls for heat; 

2. 

AFG  burner:  The  motor  starts  and  spark  is  established.  The 
pump  pressure  builds  and  the  oil  supply  mechanism  opens, 
admitting fuel to the nozzle; 

40F  burner:  Burner  motor  starts.  The  burner  motor  fan  pre-
purges  the  combustion  chamber  and  vent  for  10  seconds, 
establishing  the  combustion  air  pattern.  During  this  time  the 
solenoid  valve  holding  coil  pressure  is  approximately  100  psig. 
The solenoid valve opens, allowing oil to flow through the nozzle. 
At the same time, the burner motor ignition coil produces a spark; 

3. 

Spark ignites oil droplets; 

4. 

Cad  cell  senses  flame  and  burner  continues  to  fire.  Ignition 
transformer ceases sparking (R40-F); 

5. 

After  Fan-Limit  control  heats  up  to  the  factory  set  point,  the 
circulating air blower and electronic air cleaner starts; 

6. 

The  circulating  air  blower  and  burner  motor  remain  on  until  the 
thermostat is satisfied (AFG). The ignition transformer continues 
to spark (AFG). The solenoid valve remains open (R40-F); 

Thermostat is satisfied : 

7. 

Primary  relay  contacts  open,  solenoid  valve  closes  (R40-F), 
burner  fan  motor  shuts  down.  The  ignition  transformer  ceases 
sparking (AFG); 

8. 

The Fan-Limit control bi-metal cools down to the factory set point 
of 90

o

F (32

o

C), the circulating air blower stops. 

 

 

2.2) 

CHECKS AND ADJUSTMENTS 

 

2.2.1)  General 

 

During  initial  start-up  and  subsequent  yearly  maintenance  calls,  the 
furnace must be thoroughly tested.  
 

IMPORTANT 

The  burner  must  be  put  in  operation  for  at  least  10 
minutes  before  any  test  readings  are  taken.  For  new 
installations, set up the burner to the settings per Table 
2, p. 12 before firing. These are rough adjustments, but 
they will ensure that the burner will start and run smoke-
free in advance of fine tuning. 

 
Open  the  oil  bleed  port  screw  and  start  the  burner.  Allow  the  oil  to 
flush into a container for at least 10 seconds. Slowly close and tighten 
the bleed screw. The oil should flow absolutely free of white streaks or 
bubbles to indicate that no  air is being drawn into the suction side of 
the  oil  piping  and  pump.  Fire  the  burner.  Adjust  the  oil  pressure  as 
indicated in Table 2, p. 12. 
 

2.2.2)  Restart after burner failure 

 

1. 

Set thermostat lower than the room temperature; 

2. 

Press the reset button on the burner primary control (relay); 

3. 

Set thermostat higher than the room temperature; 

4. 

If  the  burner  motor  does  not  start  or  ignition  fails,  turn  off  the 
disconnect  switch  and  CALL  A  QUALIFIED  SERVICE 
TECHNICIAN. 

 

CAUTION 

Do not attempt to start the  burner  when  excess oil has 
accumulated,  when  the  furnace  is  full  of  vapour,  or 
when the combustion chamber is very hot. 

Содержание AMP300B34-SE2PMA

Страница 1: ...X40093 Rev L Models AMP300B34 SE2PMA OTF210G21B INSTALLER SERVICE TECHNICIAN USE THE INFORMATION CONTAINED IN THIS MANUAL FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE...

Страница 2: ...this manual can result in furnace malfunction property damage personal injury and or death WARNING Fire hazard The furnace must be installed in a level position never where it will slope toward the fr...

Страница 3: ...n the water lines if possible Open faucets in appropriate areas b Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing Contact...

Страница 4: ...ioration is discovered the chimney must be repaired or the vent must be replaced b Inspection to ascertain that the vent system is clear and free of obstructions Any blockages must be removed before i...

Страница 5: ...ts and glues l Antistatic fabric softeners for clothes dryers m Acid based masonry cleaning materials 1 6 OIL TANKS AND LINES Check your local codes for the installation of the tank and accessories A...

Страница 6: ...safety device must be installed between the flue outlet of the appliance and the draft regulator as indicated in the instructions It is further imperative that the BVSO be maintained annually For mor...

Страница 7: ...time the burner motor ignition coil produces a spark 3 Spark ignites oil droplets 4 Cad cell senses flame and burner continues to fire Ignition transformer ceases sparking R40 F 5 After Fan Limit con...

Страница 8: ...WER OFF DELAY BOARD ST9103A BLOWER ON DELAY BOARD 1158 2 2 5 Vent temperature test 1 Place a thermometer into the test hole located in the breech pipe 2 The vent temperature should be between 400 and...

Страница 9: ...peration Soot will have collected in the first sections of the heat exchangers only if the burner was started after the combustion chamber was flooded with fuel oil or if the burner has been operating...

Страница 10: ...remove any build up from the thermal switch surface 6 Clear and remove any build up or obstruction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed i...

Страница 11: ...BURNER MODEL 40 AHRI model AMP OTF 168 RF 189 RF 210 RF Heating capacity BTU h 139 000 155 000 171 000 Nozzle Delavan 1 00 70W 1 10 70W 1 25 70W Pump pressure PSIG 145 150 145 Combustion air adjustmen...

Страница 12: ...7 6 cm 3 HORIZONTAL WARM AIR DUCT WITHIN 6 FEET OF FURNACE 2 54 cm 1 7 6 cm 3 BOTTOM FURNACE HORIZONTAL OR BELOW FLUE PIPE 23 cm 9 23 cm 9 VERTICALLY ABOVE FLUE PIPE 23 cm 9 23 cm 9 FRONT FURNACE 61...

Страница 13: ...FIGURE 4 Wiring diagram AMP300B34 SE2PMA OTF210G21B 13...

Страница 14: ...14 PARTS LIST Model AMP300B34 SE2PMA OTF210G21B B50046A...

Страница 15: ...30 x 1 21 B01406 01 Blower assembly complete 22 B01794 Blower slide 23 B02820 Floor 24 B02830 Divider panel assembly 25 R02R002 High temp control 140 20F 7 26 B02791 02 Left side panel assembly 27 B0...

Отзывы: