background image

 

 

FIGURE 1 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

Checking the nozzle 

 

The burner is equipped with an appropriate size nozzle. If another size 
nozzle  or  a  replacement  is  required,  use  the  manufacturer’s  nozzle 
data shown in Table 2, p. 12. Note that all nozzle sizes are based on a 
pump pressure of 100 psi.  

 

Always  select  nozzle  sizes  by  working  back  from  the  actual  desired 
flow rate at operating pressure, and not by the nozzle marking. 
 

Checking air and turbulator settings 

 

Before starting the burner for the first time, adjust the air and turbulator 
settings  to  those  listed  in  Table  2,  p.  12.  Once  the  burner  becomes 
operational, final adjustments will be necessary. 
 

Checking the fuel supply system 

 

Fuel Specifications: 
 

NOTE: Use No.1 or No.2 Heating Oil (ASTM D396) or in Canada, use 
No.1 or No.2 Furnace Oil. 

 
Before starting the burner be sure that the fuel tank is filled with clean 
oil. 
 
 

WARNING 

 

Fire and explosion hazard. 

 

Use  only  approved  heating  type  oil  in  this  furnace.  
DO NOT USE waste oil, used motor oil, gasoline or 
kerosene. 

 

Use  of  these  will  result  in  death,  personal  injury 
and/or property damage.
 

 
 

NOTE:  You  may  notice  a  slight  odour  the  first  time  your  furnace  is 
operated.  This will soon disappear.  It is only the oil used on certain  
parts during manufacturing. 

 
 

 

1.8) 

BLOCKED VENT SHUT-OFF (BVSO

For chimney venting

 

 

WARNING 

 

It is imperative that this device be installed by a 
qualified agency. 

This  device  is  designed  to  detect  the  insufficient  evacuation  of 
combustion gases in the event of a vent blockage. In such a case the 
thermal switch will shut down the oil burner. The device will then need 
to be re-armed MANUALLY. 

 

Refer  to  the  wiring  diagrams  and  the  detailed  instructions  supplied 
with the BVSO for the installation and wiring procedures. The length of 
wires  supplied  with  the  unit  is  such  that  the  safety  device  must  be 
installed  between  the  flue  outlet  of  the  appliance  and  the  draft 
regulator, as indicated in the instructions. 

 

It  is  further  imperative  that  the  BVSO  be  maintained  annually.  For 
more details refer to the instructions supplied with the device itself, as 
well as Section 3.1.8 of this manual. 
 

CAUTION 

A  positive  pressure  venting  system  (Sealed  Combustion 
System  or  Direct  Vent)  MUST  NOT  use  the  BVSO.  Follow 
the instructions supplied with the venting system. 

 

1.9) 

INSTALLING ACCESSORIES 

 
 

WARNING 

 

Electrical shock hazard. 

 

Turn  OFF  electric  power  at  the  fuse  box  or  service 
panel before making any electrical connections and 
ensure a proper ground connection is made before 
connecting line voltage. 

 

Failure  to  do  so  could  result  in  property  damage, 
bodily injury or death. 

 
 

1.9.1)  Air conditioning 

 

An  air  conditioning  coil  may  be  installed  on  the  supply  air  side  only.  
Also,  according  to  the  coil  manufacturer’s  instructions,  a  minimum 
clearance of 6 inches must be allowed between the bottom of the coil 
drain pan, and the top of the heat exchanger. Wire the thermostat and 
condensing unit contactor as indicated in the wiring diagram (Figure 4, 
p. 14). 
 

1.9.2)  Ductwork and Filter 

 

Installation 

 

Design  and  install  the  air  distribution  system  to  comply  with  Air 
Conditioning  Contractors  of  America  manuals  or  other  approved 
methods that conform to local codes and good trade practices. 

 

Knockouts  are  provided  on  both  sides  of  the  furnace  to  cut  the 
required size opening for the installation of the return ductwork. This 
can  be  done  on  either  the  right  or  the  left  side  of  the  furnace.  See 
Figure 3, p. 13 for location and dimensions. 
 
 

NOTE:  THE BACK SHOULD NOT BE CUT OUT FOR 

RETURN AIR 

 
 
Provision  is  also made  on  this  furnace  for  a  bottom  return  air  duct. 
Knockouts  are  provided  on  the  floor  of  the  furnace  to  facilitate  the 
installation  of  the  air  filter  rack  assembly  and  return  ductwork.  (We 
recommend the use of this opening for horizontal installations).  

DNS-0864 Rev. A 

Содержание AMP300B34-SE2PMA

Страница 1: ...X40093 Rev L Models AMP300B34 SE2PMA OTF210G21B INSTALLER SERVICE TECHNICIAN USE THE INFORMATION CONTAINED IN THIS MANUAL FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE...

Страница 2: ...this manual can result in furnace malfunction property damage personal injury and or death WARNING Fire hazard The furnace must be installed in a level position never where it will slope toward the fr...

Страница 3: ...n the water lines if possible Open faucets in appropriate areas b Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing Contact...

Страница 4: ...ioration is discovered the chimney must be repaired or the vent must be replaced b Inspection to ascertain that the vent system is clear and free of obstructions Any blockages must be removed before i...

Страница 5: ...ts and glues l Antistatic fabric softeners for clothes dryers m Acid based masonry cleaning materials 1 6 OIL TANKS AND LINES Check your local codes for the installation of the tank and accessories A...

Страница 6: ...safety device must be installed between the flue outlet of the appliance and the draft regulator as indicated in the instructions It is further imperative that the BVSO be maintained annually For mor...

Страница 7: ...time the burner motor ignition coil produces a spark 3 Spark ignites oil droplets 4 Cad cell senses flame and burner continues to fire Ignition transformer ceases sparking R40 F 5 After Fan Limit con...

Страница 8: ...WER OFF DELAY BOARD ST9103A BLOWER ON DELAY BOARD 1158 2 2 5 Vent temperature test 1 Place a thermometer into the test hole located in the breech pipe 2 The vent temperature should be between 400 and...

Страница 9: ...peration Soot will have collected in the first sections of the heat exchangers only if the burner was started after the combustion chamber was flooded with fuel oil or if the burner has been operating...

Страница 10: ...remove any build up from the thermal switch surface 6 Clear and remove any build up or obstruction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed i...

Страница 11: ...BURNER MODEL 40 AHRI model AMP OTF 168 RF 189 RF 210 RF Heating capacity BTU h 139 000 155 000 171 000 Nozzle Delavan 1 00 70W 1 10 70W 1 25 70W Pump pressure PSIG 145 150 145 Combustion air adjustmen...

Страница 12: ...7 6 cm 3 HORIZONTAL WARM AIR DUCT WITHIN 6 FEET OF FURNACE 2 54 cm 1 7 6 cm 3 BOTTOM FURNACE HORIZONTAL OR BELOW FLUE PIPE 23 cm 9 23 cm 9 VERTICALLY ABOVE FLUE PIPE 23 cm 9 23 cm 9 FRONT FURNACE 61...

Страница 13: ...FIGURE 4 Wiring diagram AMP300B34 SE2PMA OTF210G21B 13...

Страница 14: ...14 PARTS LIST Model AMP300B34 SE2PMA OTF210G21B B50046A...

Страница 15: ...30 x 1 21 B01406 01 Blower assembly complete 22 B01794 Blower slide 23 B02820 Floor 24 B02830 Divider panel assembly 25 R02R002 High temp control 140 20F 7 26 B02791 02 Left side panel assembly 27 B0...

Отзывы: