2 INSTALLATION 

This furnace is a true multi-position unit, in that it will 
function in an upflow, downflow or horizontal configuration 
to the left or the right. Only a few modifications are 
required during installation to change from one position to 
another. The unit is shipped in the upflow configuration 
and instructions as to how to change to the other 
positions are included in this manual. 

 

The unit is shipped with a burner and its controls. It 
requires a 115VAC power supply to the control panel and 
thermostat hook-up as shown on the wiring diagram, one 
or more oil line connections, suitable ductwork and 
connection to a properly sized vent.  

 

All local and national code requirements governing the 
installation of oil burning equipment, wiring and the flue 
connection MUST be followed. Some of the codes that 
may apply are: 

CSA B139:

  

Installation code for oil burning 
equipment. 

ANSI/NFPA 31:

   Installation of oil burning equipment. 

ANSI/NFPA 90B:

 Warm air heating and air conditioning 

systems. 

ANSI/NFPA 211:

  Chimneys, Fireplaces, Vents and solid 

fuel burning appliances.

 

ANSI/NFPA 70:

   National Electrical Code.  

CSA C22.1 or CSA C22.10:

  

Canadian Electrical Code. 

Only the latest issues of these codes may be used. 

2.1 POSITIONING

 

THE

 

FURNACE 

WARNING 

 

Fire and explosion hazard. 

 

The furnace must be installed in a level position, never 
where it will slope toward the front. 

 

Do not store or use gasoline or any other flammable 
substances near the furnace. 

 

Non-observance of these instructions will potentially 
result in death, bodily injury and/or property damage. 

 

CAUTION 

This furnace is not watertight and is not designed for 
outdoor installation. It must be installed in such a manner 
as to protect its electrical components from water. 
Outdoor installation will lead to a hazardous electrical 
condition and to premature failure of the equipment. 

 

 

The minimum clearances from combustible material 
for each of the positions are specified in Table 4. 

 

If the furnace is installed in a basement or on a dirt floor, 
in a crawl space for example, it is recommended to install 
the unit on a cement base 2.5 cm to 5.0 cm (1" to 2") 
thick. 

The unit must be installed in an area where the ambient 
and return air temperatures are above 15°C (60°F). In 
addition, the furnace should be installed as closely as 
possible to the vent, so that the connections are direct 
and kept to a minimum. The heater should also be 
located close to the centre of the air distribution system. 

2.1.1  Installation in an enclosure 

The unit can be installed in an enclosure such as a 
closet. However, 2 ventilation openings are required for 
combustion air. The openings should be located in front 
of the furnace approximately 15 cm (6") above the floor 
and 15 cm (6") below the ceiling. Figure 1 indicates the 
minimum dimensions required and the location of the 
openings.  

 

Figure 1: Location and dimensions of ventilation air 

openings in a closet door 

 

2.2 CONFIGURATIONS 

 

2.2.1 Upflow Installation 

The return air opening may be located on either side of 
the furnace. Care should be taken not to damage the 
wires inside, while cutting the opening. Install the filter 
rack supplied with the unit according to the instructions 
provided with it. It is also recommended to install the 
blower door before handling or moving the unit. Refer to 
Figure 2 for additional details. 

 

Figure 2: Upflow installation

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

DNS-1227A 

Burner position 

Filter 20X24 

Combustible or non-
combustible floor 

Содержание AMP112SD

Страница 1: ...L FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Attention Do not tamper...

Страница 2: ...tilation air openings in a closet door 4 Figure 2 Upflow installation 4 Figure 3 Downflow installation 5 Figure 4 Horizontal installation 5 Figure 5 Thermostat wiring heating and air conditioning with...

Страница 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Страница 4: ...designed for outdoor installation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to pre...

Страница 5: ...TION The exterior of the unit must have an uninterrupted ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for tha...

Страница 6: ...Before starting the burner for the first time adjust the air and turbulator settings to those listed in this manual Once the burner becomes operational final adjustments will be required Refer to sect...

Страница 7: ...ormance Test The purpose of the following test is to check that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BV...

Страница 8: ...distance 2 10 DUCTING WARNING Poisonous carbon monoxide gas hazard DO NOT draw return air from inside a closet or utility room Return air MUST be sealed to the furnace casing Failure to properly seal...

Страница 9: ...o do so can result in death or bodily injury 2 13 1 Humidifier HUM The 120 VAC HUM terminal on the electronic board of the blower is tied directly to terminal 8 of the 9 terminal connector of the elec...

Страница 10: ...n the instructions provided with the burner 3 3 CHECKS AND ADJUSTMENTS 3 3 1 Purging The Oil Line Open the bleed port screw and start the burner Allow the oil to drain into a container for at least 10...

Страница 11: ...the obstruction and the burner should restart after a few minutes The time required for the restart also depends on the adjustment of the blower OFF delay 3 3 9 Restart After Burner Failure 1 Set the...

Страница 12: ...obstruction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed in step 4 8 Re attach the assembly cover with the screws removed in step 2 9 Re establish...

Страница 13: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Страница 14: ...ard and Canadian regulation 85 5 85 0 85 5 85 0 AFUE From ASHRAE 103 standard and US regulation 85 2 85 0 85 2 85 0 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse...

Страница 15: ...nOn D elay CFMLevel Time ShortR unOn Delay C FMLevel Time Off Delay CFMLevel Time A 1 OFF 2 OFF 0 68 13 45sec 19 60sec 38 3min B 1 ON 2 OFF 0 80 13 45sec 19 30sec 38 3min C 1 OFF 2 ON A ll 13 45sec 10...

Страница 16: ...ANDWARM AIRDUCTWITHIN6ft OFFURNACE1 5 08 cm 2 2 54cm 1 5 08 cm 2 BOTTOM FURNACE2 2 54cm 1 3 5 08 cm 2 4 BACK FURNACE OP P OSITESIDEOFTHEBURNE R 1 7 62 cm 3 7 62cm 3 7 62 cm 3 PLE NUMORHORIZONTALWARM A...

Страница 17: ...17 Figure 9 Furnace Dimensions...

Страница 18: ...18 Figure 10 Wiring Diagram 4 Speed Motor PSC...

Страница 19: ...19 Figure 11 Wiring Diagram Variable Speed Motor ECM...

Страница 20: ...20 Figure 12 Parts list with 4 speed motor PSC B50091C...

Страница 21: ...er slide included 32 B03637 02 LATERAL BAFFLE 33 B03480 01 FILTER RACK KIT 34 B03635 FLOOR 35 B03651 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 36 B03653 REAR PANEL ASSEMBLY Pane...

Страница 22: ...22 Figure 13 Parts list with variable speed motor ECM B50092C...

Страница 23: ...IDE One blower slide included 31 B03637 02 LATERAL BAFFLE 32 B03480 01 FILTER RACK KIT 33 B03635 FLOOR 34 B03651 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 35 B03653 REAR PANEL A...

Страница 24: ...DER LE DOCUMENT PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S DE L UNIT POUR R F RENCES ULT RIEURES Attention Ne pas alt rer votre unit ou ses contr les Appeler u...

Страница 25: ......

Страница 26: ...ions et localisation ouvertures de ventilation dans la porte du placard 6 Figure 2 D bit ascendant 6 Figure 3 D bit descendant 6 Figure 4 D bit horizontal 6 Figure 5 Branchement du thermostat chauffag...

Страница 27: ...v Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service ayez en main la page de la fiche technique section 5 note de ce manuel...

Страница 28: ...s de chauffage air chaud et syst me d air climatis ANSI NFPA 211 Chemin e Foyers vents et appareils de chauffage ANSI NFPA 70 Code National d lectricit CSA C22 1 or CSA C22 10 Code Canadien d lectrici...

Страница 29: ...tre install dans le m me sens peu importe l orientation de la fournaise Voir figure 3 pour plus de d tails La plaque de protection B03789 doit tre install e sur le couvercle de plastique du br leur B...

Страница 30: ...chauffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 4 INSTALLATION DU THERMOSTAT L installation d un thermostat de contr le de la temp rature d...

Страница 31: ...u br leur pour plus de d tail concernant l ajustement du d lai post purge 2 6 VACUATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone Lire et suivre toutes les instructions contenues d...

Страница 32: ...UALIFI 2 8 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone R f rer aux codes d installation des appareils au mazout ANSI NFPA 31 aux...

Страница 33: ...tallations ayant un r servoir de mazout situ sous le niveau du br leur doivent utiliser une ligne de retour de mazout vers le r servoir avec une pompe appropri e une l vation de 2 4 m 8 et plus requi...

Страница 34: ...auffage Position interrupteurs DIP 1 2 POSITION Consommation USGPH OFF OFF A 0 68 ON OFF B 0 80 OFF ON C 0 68 ON ON D 0 80 Ajustements suppl mentaires pour une l vation de temp rature de l air sup rie...

Страница 35: ...huile est ouverte 5 Le bouton Reset du br leur est bien enfoncer ou r armer 6 L ajustement d air pr liminaire du br leur est conforme aux tableaux des sp cifications de ce manuel 7 L ajustement des v...

Страница 36: ...evant du r gulateur la verticale voir les instructions incluses avec le r gulateur Ajuster le r gulateur de tirage apr s que l appareil ait fonctionn e au moins cinq minutes et r gl entre 0 025 et 0 0...

Страница 37: ...les fusibles et disjoncteur 3 V rifier si l interrupteur d alimentation principal de la fournaise est en position ON 4 Ajuster le thermostat au dessus de la temp rature ambiante 5 Si l allumage du br...

Страница 38: ...tre du r servoir Remplacer le filtre du r servoir au besoin Suivre les instructions du fabriquant Filtre secondaire Remplacer les cartouches des filtres de 10 microns ou moins une fois par ann e Suivr...

Страница 39: ...103 et des lois am ricaines 85 2 85 0 85 2 85 0 BR LEUR RIELLO MOD LE 40 BF5 vacuation directe DV Longueur d insertion du tube du br leur pouces Gicleur Delavan 0 60 70A 0 70 70A 0 60 70A 0 70 70A Pr...

Страница 40: ...On Niveau PCM Temps D lai Off Niveau PCM Temps A 1 OFF 2 OFF 0 68 13 45 sec 19 60 sec 38 3 min B 1 ON 2 OFF 0 80 13 45 sec 19 30 sec 38 3 min C 1 OFF 2 ON Tous 13 45 sec 100 0 sec 100 2 min D 1 ON 2 O...

Страница 41: ...ISE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 DESSOUS FOURNAISE 2 2 54 cm 1 3 5 08cm 2 4 ARRI RE FOURNAISE C T OPPOS DUBR LEUR 1 7 62 cm 3 7 62 cm 3 7 62 cm 3 PL NUMOU CONDUIT D AIR CHAUDHORIZONTAL 6 pi DE LA F...

Страница 42: ...19 Figure 9 Dimensions de la fournaise...

Страница 43: ...20 Figure 10 Diagramme lectrique avec moteur 4 vitesses PSC...

Страница 44: ...21 Figure 11 Diagramme lectrique avec moteur vitesse variable ECM...

Страница 45: ...22 B50091C Figure 12 Liste de pi ces avec moteur 4 vitesses PSC...

Страница 46: ...une seule glissi re 32 B03637 02 DEFLECTEUR LATERAL 33 B03480 01 KIT SUPPORT A FILTRE 34 B03635 PLANCHER 35 B03651 02 ASS PANNEAU COTE GAUCHE Comprend panneau isolation et d flecteur 36 B03653 ASS PA...

Страница 47: ...24 B50092C Figure 13 Liste de pi ces avec moteur vitesse variable ECM...

Страница 48: ...TEUR Comprend une seule glissi re 31 B03637 02 DEFLECTEUR LATERAL 32 B03480 01 KIT SUPPORT A FILTRE 33 B03635 PLANCHER 34 B03651 02 ASS PANNEAU COTE GAUCHE Comprend panneau isolation et d flecteur 35...

Отзывы: