Detroit Radiant Products LD3-15-40 Скачать руководство пользователя страница 38

38

LD3 

Series

Leak Testing

Use a soap solution or equivalent for leak testing. Leak testing solution must be non-corrosive, and be 
rinsed off immediately after the leak test. Never test for leak with an open flame. Failure to comply could 
result in personal injury, property damage or death. 

Always leak test final gas assembly for gas leaks according to the procedures outlined in NFPA 54 and 
all local codes and/or Standards.

For leak testing on pressures below 1/2 PSI

Before leak testing, close the field installed manual shut off valve shown on Figure 3.25 on the supply 
line to isolate the gas valve from the pressure. 

NOTE:

 All factory installed gas connections have passed 

an approved leak test.

For leak testing on pressures above 1/2 PSI

When leak testing with pressures above 1/2 PSI (14 inches W.C.), the unit must be isolated from the 
supply pipe. Close the field installed manual shut off valve, disconnect the supply line to the unit, and 
temporarily cap the supply line for testing purposes.

WARNING

!

Gas pressures to the appliance controls must never exceed 14 inches W.C. (1/2 PSI). 
Supply pressures greater than 14” W.C. can damage the controls, resulting in personal 
injury, property damage, or death.

WARNING

!

Testing for gas leaks with an open flame or other sources of ignition may lead 
to a fire or explosion and cause serious injury or death. Test in accordance 
with NFPA or local codes.

3.0

 Installation

 

 Leak Testing

Chart 3.9 

 Maximum capacity for Schedule 40 Metallic pipe, in CFH

Pipe 

Length

1/2”

3/4”

1”

1-1/4”

1-1/2”

2”

Nat

Prop

Nat

Prop

Nat

Prop

Nat

Prop

Nat

Prop

Nat

Prop

10 feet

132

86

278

182

520

340

1050

686

1600

1046

3050

1993

20 feet

92

60

190

124

350

229

730

477

1100

719

2100

1373

30 feet

73

48

152

99

285

186

590

386

890

582

1650

1078

40 feet

63

41

130

85

245

160

500

327

760

497

1450

948

50 feet

56

37

115

75

215

141

440

288

670

438

1270

830

60 feet

50

33

105

69

195

127

400

261

610

399

1150

752

70 feet

46

30

96

63

180

118

370

242

560

366

1050

686

80 feet

43

28

90

59

170

111

350

229

530

346

990

647

90 feet

40

26

84

55

160

105

320

209

490

320

930

608

100 feet

38

25

79

52

150

98

305

199

460

301

870

569

125 feet

34

22

72

47

130

85

275

180

410

268

780

510

150 feet

31

20

64

42

120

78

250

163

380

248

710

464

175 feet

28

18

59

39

110

72

225

147

350

229

650

425

200 feet

26

17

55

36

100

65

210

137

320

209

610

399

Содержание LD3-15-40

Страница 1: ...indoor living or sleeping quarters etc Installation of a tube heater system in residential indoor living spaces may result in property damage serious injury asphyxiation or death LD3 Series Installat...

Страница 2: ...7 Burner Control Box Suspension 19 Reflector Assembly 20 Final Heater Assembly 22 Venting 23 Combustion Air Requirements 30 Separated Combustion Systems 31 Combustion Air Supply Room Air 32 Optional U...

Страница 3: ...mber Gas Type select one Maximum Input BTU h Minimum Input BTU h Straight Length U Tube Length Standard Weight lbs Recommended Mounting Height Combustion Chamber Black Coated Radiant Emitter Tube s Bl...

Страница 4: ...is heater must be installed and serviced by trained gas installation and service personnel only This is NOT an explosion proof heater DO NOT install in explosive environments Where there is the possib...

Страница 5: ...ww drp co com parts Serial No 1311XXXXXXXXXX 0001 Gas Valve Circuit Board Wire Harness N O Switch N O VL Orifice N C Switch N C VL Orifice Diff Switch Diff VL Orifice Igniter Burner 16 Tube Ind Lights...

Страница 6: ...RNING Improper installation adjustment alteration service or maintenance can cause property damage serious injury or death Read and understand the installation operation and maintenance instructions t...

Страница 7: ...om above the upper surface of wings or of the engine enclosures of the highest aircraft that may be housed in the hangar The measurement shall be made from the wing or engine enclosure whichever is hi...

Страница 8: ...Clearances to Combustibles A critical safety factor to consider before installation is the clearances to combustibles Clearance to combustibles is defined as the minimum distance you must have betwee...

Страница 9: ...le with 2 Side Shields P N SSE Side Side Below Top Front Behind Below Top Front Behind Below Top Side Side Below Top WARNING Failure to comply with the stated clearances to combustibles may result in...

Страница 10: ...ss been evaluated Does the design meet the needs of the space Have recommended mounting heights been observed Have all clearance to combustible situations been observed Is the supply burner end of the...

Страница 11: ...12 x 12 20 30 30 50 18 30 ft 50 000 9 14 32 x 15 15 x 15 20 30 30 50 18 Optional protective guard P N PG is required when mounting below 8 feet Factory recommended mounting heights are listed as a gu...

Страница 12: ...4 tube hanger TP 19B on the tapered titanium combustion chamber s 4 O D end The spacing between the burner control box mounting brackets and the 4 tube hanger should be 2 4 4 Mark locations for hangi...

Страница 13: ...is located on the swaged end of the tube s 3 or 4 Reflector Center Support TP 1078 or TP 82 13 LD3 Series Chart 3 2 Heater Mounting Requirements and Weights Refer to page 18 for U Bend configuration d...

Страница 14: ...type of suspension anchor to hanging point 7 IF USING CHAINS Attach and close S hook P N S HOOK and 1 double loop chain P N THCS to anchor Check that it is securely attached NOTE Threaded rod and turn...

Страница 15: ...ngle with two suspension points using two optional Brass Knuckle P N BK fittings 1 double loop chains and S hooks U Tubes can be mounted from a single suspension point using an optional Single Mountin...

Страница 16: ...ch subsequent tube will utilize one 1 hanger Refer to page 22 for tube installation sequence 2 Slide tube clamps onto radiant tubes see figure 3 7 Figure 3 6 Attach Hangers Figure 3 7 Attach Tube Clam...

Страница 17: ...difficult to mate the tubes they may be installed incorrectly 4 Center tube clamps over the seam where two radiant tube sections connect If necessary rotate tube clamps so they will not interfere with...

Страница 18: ...4 Overall Dimensions for Heaters Configured With U Bend 180 3 U Bend P N DB TF1B 90 3 Elbow P N DB E6 Tube Length Dimension B Notes 15 ft N A N A 20 ft 13 0 N A 30 ft 17 8 Requires P N LV3 5EA SUB Mo...

Страница 19: ...N THCS to anchor Check that it is securely connected 4 Attach chain assemblies and S hooks to mounting brackets on the burner control box Adjust chain lengths until level and in straight alignment wi...

Страница 20: ...her using sheet metal screws except at the expansion joint see p 22 NOTE Installer to supply sheet metal screws 4 Attach reflector end caps with polished finish inward to each end of the reflector run...

Страница 21: ...downward away from sidewalls and combustibles Protective Guard Used to prevent debris or objects from becoming lodged PG between the radiant tube and reflector Required when mounting heaters below 8 f...

Страница 22: ...C B C B NOTE When securing joints on reflectors which are rotated on an angle from horizontal secure joint only on top side of reflector to allow for sufficient heater expansion and contraction 1 to...

Страница 23: ...vent pipe should be corrosion resistant galvanized steel of a thickness that meets the National Fuel Gas Code Minimum thickness for connectors varies depending on the pipe diameter Never vent the LD3...

Страница 24: ...poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the venting system are n...

Страница 25: ...minimum of 4 feet below 4 feet horizontally from or 1 foot above any window or door that may be opened or gravity air inlet into the building Vent must terminate a minimum of 4 feet above grade level...

Страница 26: ...ctures All vertically vented heaters that are Category I must be connected to a chimney or vent complying with a recognized Standard or lined masonry or concrete chimney with a material acceptable to...

Страница 27: ...at a pitch of 1 4 inch per foot Vent enclosed spaces and buildings according to the guidelines in this manual and applicable national state provincial and local codes You may either use an agency cert...

Страница 28: ...prevent blockage by snow and protect building materials from degradation by flue gases The vent cap must be a minimum of 6 inches from the sidewall of the building Vent must be a minimum of 36 inches...

Страница 29: ...alled within the common portion of the vent carrying system reduces the maximum common vent capacity by 10 Refer to NFPA 54 IFEC tables 11 2 and 11 3 for capacity The vent connector capacities allow f...

Страница 30: ...es degreasers paints paint removers lubricants pesticides etc are present in the atmosphere High humidity Contaminants such as sawdust welding smoke etc Negative building pressure Unusually tight cons...

Страница 31: ...Seal all joints with metallic tape or silicone sealant Wrap the tape two full turns around the vent pipe Slope air intake pipe inch per foot upward or downward away from the unit Do not draw air from...

Страница 32: ...n with air infiltration rates of less than 0 40 air changes per hour outside combustion air is typically needed unless the sheer size of the building allows otherwise Contact the factory for further d...

Страница 33: ...function simultaneously The minimum clearance between the air intake and the exhaust terminal is 4 feet NOTE When installing in a U Tube configuration use extra caution to separate vent gases from hea...

Страница 34: ...uidelines in this manual In the United States refer to the latest edition of the ANSI Z223 1 NFPA 54 Standard and in Canada refer to the latest edition of the CAN CGA B149 1 Standard Supply gas piping...

Страница 35: ...latest edition or CSA B149 1 and B149 2 Support all gas piping with pipe hangers metal strapping or other suitable material Do not rely on the heater to support the gas pipe When connecting piping to...

Страница 36: ...n a corrosive environment or near corrosive substances use a gas connector suitable for the environment Do not use the gas piping to electrically ground the heater Installation of the Gas Line to the...

Страница 37: ...ly pressure from the building main to the inlet of the unit Refer to the chart for the appropriate range of inlet pressures for each gas type When sizing the inlet gas pipe diameter make sure that the...

Страница 38: ...inches W C 1 2 PSI Supply pressures greater than 14 W C can damage the controls resulting in personal injury property damage or death WARNING Testing for gas leaks with an open flame or other sources...

Страница 39: ...larity must be observed when making field connections Internal Wiring Diagrams Before wiring this appliance check the existing wiring replace if necessary If any of the original wire supplied with the...

Страница 40: ...hen plugging in the heater make sure the supply cord is protected from damage and keep all cords away from the heater s surfaces and out of the clearances to combustibles zones see page 9 When routing...

Страница 41: ...t Connection with External Relay Kit Thermostat Location The location of the thermostat should be determined by the desired heating requirements and be mounted on an inside wall five 5 feet above the...

Страница 42: ...unit is properly grounded as per the National Electrical Code ANSI NFPA 70 or Canadian Electrical code CSA C22 1 Part 1 9 9 The unit is properly mounted to a permanent structure able to bear the weigh...

Страница 43: ...the burner This heater cannot be lighted manually Do not try to light the burner by hand Verify minimum inlet gas supply pressure 7 Turn on all other gas appliances that are on the same supply line I...

Страница 44: ...on the valve body see Figure 3 30 2 Remove the manifold pressure tap plug on the gas control valve see Figure 3 30 3 Connect the pressure gauge tube and manometer 4 Turn on the gas valve with the swit...

Страница 45: ...tap plug on the gas control valve 15 Leak check the re installed pressure tap plug using a soap solution or equivalent method as described in ANSI Z223 1 NFPA 54 Prior to leaving the Job Site Prior to...

Страница 46: ...ion above 6 000 ft the input rate will have to be de rated to ensure proper operation The deration is achieved by a gas orifice change Contact the factory for installations above these elevations WARN...

Страница 47: ...he lowest setting 3 Turn OFF all electrical power to the appliance 4 Turn manual shutoff clockwise to OFF 5 Wait five 5 minutes to clear out any gas If you smell gas STOP Follow the safety information...

Страница 48: ...om the second stage of the thermostat In order for high fire to engage low fire must be energized as well The thermostat determines which stage to maintain for the desired comfort level Shut Down When...

Страница 49: ...2 flashes Red Ignitor error 12 seconds 3 flashes Red Gas valve error 4 flashes Red Line voltage frq error 5 flashes Red Internal control error 6 flashes Red Pressure switch error Some LED codes have...

Страница 50: ...obstruction or correct vent lengths Replace wiring or hose connections No No No Yes Find source of electrical problem Is the igniter physically damaged No Yes Replace igniter No Check voltage at igni...

Страница 51: ...is not a negative pressure experienced at the area of intake e g high winds attic space tightly sealed building No Repair thermostat or thermostat wiring Yes Remove obstruction Is the draft inducer i...

Страница 52: ...within 1 2 seconds No Does the burner stay on for approximately 8 10 seconds and then shut off No Yes Turn on gas supply line No Purge gas line No Check inlet pressure and limit switches Check circui...

Страница 53: ...followed Yes Replace the appropriate pressure switch after verifying There is continuity across the thermal fuse Heater fan blowers squirrel cage intake and exhaust are clean and free from dirt and ob...

Страница 54: ...4 3097A 3044 3098A 3008 3002A 3099A 76 212 1070A 5 3062 3063 826 3001B 3004 3014 3115 3003A 1325 851C 3252 31D 68B 3010 83 3380 3033F 3096A 333 321 217 3093 70A 222 85 828 3094A 84 331 3023 70 245 205...

Страница 55: ...105 Reflector End Cap Aluminum TP 3023 Snap in Bushing TP 106 Reflector End Cap Clips TP 3024 8 x 1 2 SMS Point Tip TP 112 5 Reflector Aluminum TP 3029 Thermostat Terminal Board Two Stage TP 113 Refle...

Страница 56: ...personnel To check gas tightness of the safety shut off valves turn off the manual valve upstream of the appliance combination control Remove the hex head plug on the inlet side of the combination co...

Страница 57: ...ificantly depending on the environment Dirt and dust can be vacuumed or wiped with a soap and water solution Use metal polish if the reflectors are severely dirty Contact service personnel if repairs...

Страница 58: ...roit Radiant Products Company has made a diligent effort to provide product information and illustrate the products in this literature accurately however such information and illustrations are for the...

Страница 59: ...59 LD3 Series Notes 5 0 Maintenance...

Страница 60: ...the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles Signs must either be posted adjacent to the heater thermostats or in the absence of such...

Отзывы: