Actions in the event of an alarm.
When in alarm mode, the following actions can be taken:
•
PRESS THE MUTE CONTROL PANEL KEY: The buzzer will be muted and the muted
buzzer indicator will be activated.
•
PRESS THE RESET KEY: The unit will return to standby mode. We do not recommend
resetting the unit until the cause of the alarm has been resolved.
•
PRESS THE ACTIVATE SOUNDERS KEY: This will override the programmed timer
and the sounders will be activated immediately. If the sounders are activated, it will
not have any effect.
•
PRESS THE MUTE SOUNDERS KEY: If the sounders are active, they will be
deactivated. If the time programmed for the activation timer has not elapsed, this will
be overridden.
NOTE:
The key must be turned to the ON position when pressing
any key for it to have any effect, except for the
MUTE CONTROL
PANEL
key.
6.4.3. Fault mode
The unit is in fault mode when there is any fault in the unit or the system. Faults are
indicated as follows:
•
GENERAL FAULT INDICATOR ACTIVE: This will flash on and off.
•
ACTIVE FAULT INDICATORS: These will flash on and off, depending on the type of
fault (zone, power supply, sounders).
•
AUDIBLE INDICATOR ACTIVE: Intermittently.
•
FAULT OUTPUT ACTIVATION.
Actions in the event of a fault.
When in fault mode, the following actions can be taken:
•
PRESS THE MUTE CONTROL PANEL KEY: The buzzer will be muted and the muted
buzzer indicator will be activated.
•
PRESS THE RESET KEY: The unit will return to standby mode. See
SECTION 9
, which
contains a list of the most common faults and how to fix them.
NOTE:
The control panel has self-resettable faults. If the control
panel is in fault mode and said fault is fixed, this fault will cease to
be indicated without any intervention.