29
95-8547
9.2
APPENDIX C
ATEX APPROVAL
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 02 ATEX 132195X
Increased Safety Model
Flameproof Model
0539
II 2 G
II 2 D
0539
II 2 G
II 2 D
Ex db eb
IIC
T6...T5
Ex db IIC
T6...T5
Ex tb
IIIC
T80°C
Ex tb
IIIC
T80°C
T6 (Tamb = –50°C to +60°C)
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C)
T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
Compliance with:
EN 60079-0: 2012+A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-31: 2009
EN 60529: 1991+A1:2000+A2:2013
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm
2
.
The flame detector model X5200UVIR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d,” or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e.” They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Ultraviolet Infrared (UVIR) flame detector type X5200 must be electrically connected to earth
ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
• The EOL resistor can only be used within the flameproof terminal compartment.
• EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
• The Ultraviolet Infrared (UVIR) flame detector type X5200 is to be installed in places where there is a low risk of
mechanical damage.
• See the “Maintenance” section of this manual for guidance on minimizing the risk from electrostatic discharge.
• Flameproof joints are not intended to be repaired. See the “Device Repair and Return” section of this manual for
more information on conducting repairs.