95-8547
9.2
20
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 15.
RESPONSE TIME—
32 inch methane plume: < 10 seconds.
1 foot x 1 foot n-Heptane: < 15 seconds.
(See Appendix A for details.)
SOURCE TUBE—
Contains radioactive isotope Krypton 85 (Kr
85
)
Calculated Activity: 14,800 Becquerels (0.4μCi).
Note: Not applicable to model X5200G
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless Steel (316/
CF8M Cast).
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
DIMENSIONS—
See Figure 16
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm
2
wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
Important:
18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C (14°F)
and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
SHIPPING WEIGHT (Approximate)—
Aluminum:
7 pounds (3.2 kilograms).
Stainless Steel:
14.6 pounds (6.7 kilograms).
Mounting Arm (AL): 6 pounds (2.75 kilograms).
Mounting Arm (SS): 14 pounds (6.4 kilograms).
WARRANTY PERIOD—
3 years
CERTIFICATION—
®
For complete approval details, refer to the appropriate
Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
10.2
(25.9)
4.8
(12.2)
4.7
(11.9)
B2223
Figure 16—Dimensions in Inches (cm)
0
°
15
°
30
°
45
°
15
°
30
°
45
°
VIEWING ANGLE
A1288
100
90
80
70
60
50
40
30
20
10
DETECTION
DISTANCE
(PERCENT)
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
Figure 15—Detector Cone of Vision