Det-Tronics X3301 Скачать руководство пользователя страница 16

95-8577

14

5.3

COMMAND MENU

The Command Menu allows the operator to initiate a manual oi test and also to perform various reset/

clear functions.

1) Start Passive 

oi

 

    A 

passive 

oi test command checks the cleanliness of the detector’s 

      

       

    optical surfaces. This confirms the ability of the detector to respond 

      

       

    correctly to an IR signal. Fire and fault relays as well as 0–20 mA 

      

       

    current loop output are unaffected by this test. A red LED signals a 

      

       

    successful test and a yellow LED signals a failed test. The event log will 

  

  

       indicate 

either 

“Man 

oi Pass” or “Man oi Flt."

2) Start Active 

oi

  

CAUTION

 

An active 

oi

 test generates an actual Fire Alarm Output. All fire 

 

response equipment must be bypassed/disabled prior to testing to 

 

prevent unwanted output actuation.

  

  

       An 

active 

oi test performs an oi test with all detector outputs fully 

      

       

    operational. Fire and fault relays as well as the 0-20 mA loop are “live."

 

If the test is successful: 

Fire relay = Alarm

 

 

Fault relay = no fault

 

 

Current output is 20 mA

 

 

LED turns red

 

 

General log indicates “Man oi Pass”

 

 

Alarm log indicates "Fire Alarm"

 

If the test is unsuccessful: 

Fire relay = No Alarm

 

 

 

Fault relay = Fault

 

 

 

Current output is 2 mA

 

 

 

LED turns yellow

 

 

 

Fault log indicates “Man oi Flt”

3) Clear 

oi

 Fault

    

    If the cause of the fault has not been corrected, subsequent 

oi

 faults will 

  

  

       occur.

4) Reset Latches

   

    Latching relays are reset and LED turns green.

5) Master Reset

     

    This function re-initializes the microprocessor, resets the operating 

      

       

    software, and initiates a hardware reset for both the sensor and the HART 

      

       

    interface. Latched relays are reset.

6) Clear Data Log

  

    This function resets the HART data log history. To view the logs, go to 

      

       

    “Device Info Menu” and select “History Menu."

7) HART Cmd Menu

    This menu performs various diagnostic and/or service functions.

Command Menu

1)  Start Passive Oi
2)  Start Active Oi
3)  Clear Oi Fault
4)  Reset Latches
5)  Master Reset
6)  Clear Data Log
7)  HART Cmd Menu

X3301 Root Menu

1)  Fire  (Yes/No)
2)  Fault  (Yes/No)
3)  Device Info Menu
4)  Command Menu
5)  Device Setup Menu

Содержание X3301

Страница 1: ...5 3 Rev 1 16 95 8577 Addendum HART Communication with the X3301 Multispectrum IR Flame Detector...

Страница 2: ...ure 4 X3301 Root Menu 5 Device Info Menu 5 General Info Menu 6 HART Info Menu 7 HART PV Menu 8 Condensed Status 9 Status Info Menu 10 Hardware Menu 11 oi Menu 12 Detector Settings 13 History Menu 13 C...

Страница 3: ...an connect to the X3301 at any wiring termination point in the analog output signal loop Connect the HART Communicator in parallel with the X3301 analog signal or load resistor The HART connections ar...

Страница 4: ...4 VDC Vin Vin 250 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 mA mA mA REF 29 28 27 26 25 24 23 22 21 X3301 IR DETECTOR 24 VDC C2261 Vin Vin Figure 3 X3301 Detector Wired for Isolated 0 to 20 mA Curr...

Страница 5: ...rammed into the HART Communicator 3 Select Det Tronics and review the list of models to determine if the X3301 DDs are installed in your Communicator If the X3301 DDs have not been programmed into the...

Страница 6: ...ures 6 oi Cal Act 7 oi Cal Flt 8 Man oi Act 9 Man oi Flt Detector Settings 1 Fire Relay L NL 2 Fire Relay NE NDE 3 Fault Relay L NL 4 Fault Relay NE NDE 5 Aux Relay L NL 6 Aux Relay NE NDE 7 Sensitivi...

Страница 7: ...logs 4 Command Menu This menu allows the operator to initiate a manual oi test and to perform various reset clear functions 5 Device Setup Menu This menu allows various setup configuration and calibra...

Страница 8: ...e Setup Menu 1 Manufacturer Det Tronics 2 Model X3301 3 Serial Number Serial number of device 4 Part Number Manufacturer s part number for this device 5 Mfg Date Date of manufacture shown as XX XX XX...

Страница 9: ...e overall field device 4 Tag Text that is associated with the field device installation This text can be used by the operator in any way Max of eight character input 5 Long tag Text that is associated...

Страница 10: ...or X3301 2 PV Not implemented for X3301 3 PV Sensor Unit Not implemented for X3301 4 PV USL Not implemented for X3301 5 PV LSL Not implemented for X3301 6 PV Minimum Span Not implemented for X3301 7 P...

Страница 11: ...Menu X3301 Root Menu 1 Fire Yes No 2 Fault Yes No 3 Device Info Menu 4 Command Menu 5 Device Setup Menu 1 Xmtr Addstatus 0 Fire Alarm oi Cal Active Manual oi Active Warm up 2 Xmtr Addstatus 1 Spare 3...

Страница 12: ...a fire alarm status analog output is at 20 mA fire alarm relay is actuated and LED is red 3 Auto oi Flt Y N Automatic oi Fault Check viewing windows and oi reflector plate for cleanliness 4 Dim Detect...

Страница 13: ...Hdwr Flt Y N 8 Int Comm Flt 9 Incompatible Flt 10 Voltage Fault Y N 11 Hardware Menu 12 Oi Menu 1 Heater Pwr Actual heater power 0 100 Heater prevents condensation and icing on the detector optics 2...

Страница 14: ...ed oi test resets the counter 5 Cons oi Fails Set allowable number of consecutive oi failures to produce a fault 6 oi Cal Act oi calibration is in progress 7 oi Cal Flt An oi calibration fault has occ...

Страница 15: ...of the three categories will be kept in non volatile memory When the log is full the oldest event will be overwritten The most recent event will be displayed first 1 Alarm Log Scroll through 32 Alarm...

Страница 16: ...e test is successful Fire relay Alarm Fault relay no fault Current output is 20 mA LED turns red General log indicates Man oi Pass Alarm log indicates Fire Alarm If the test is unsuccessful Fire relay...

Страница 17: ...E SETUP MENU This menu allows various setup configuration and calibration functions When Write Protect is off these menus allow the operator to reconfigure or write new variables to the device 1 Confi...

Страница 18: ...e all Alarm outputs connected to the detector 2 Thoroughly clean the sensor and oi reflector for each of the three sensors Check each of the three oi source openings for contaminants and clean as need...

Страница 19: ...Detector will output 1 mA 2 Final asmbly num A number that is used for identification purposes and is associated with the overall field device 3 Tag Text that is associated with the field device inst...

Страница 20: ...3 RTC Hours 0 to 23 4 RTC Date 1 to 31 5 RTC Month 1 to 12 6 RTC Year 0 to 99 Real Time Clock 1 RTC Seconds 2 RTC Minutes 3 RTC Hours 4 RTC Date 5 RTC Month 6 RTC Year Device Setup Menu 1 Configurati...

Страница 21: ...5 8577 Corporate Office 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com All trademarks are the property of their respective owners 2020 Detector Electronics Corporation All rights...

Отзывы: