HARDWARE MENU
Hardware Menu
1) Heater Pwr
2) Htr Setpoint
3) Temperature
4) Temp Setpoint
5) Temp Rnge Flt
6) Voltage
7) Voltage Fault
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X3301 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Status Info Menu
1) Warm Up (Y/N)
2) Fire (Y/N)
3) Auto Oi Flt (Y/N)
4) Dim Detect Flt (Y/N)
5) Det Disable Flt (Y/N)
6) Snsr Hdwr Flt (Y/N)
7) HIB Hdwr Flt (Y/N)
8) Int Comm Flt
9) Incompatible Flt
10) Voltage Fault (Y/N)
11) Hardware Menu
12) Oi Menu
1) Heater Pwr
Actual heater power (0-100%). Heater prevents condensation and icing
on the detector optics.
2) Htr Setpoint
Maximum amount of heater power allowed (in percent of full power).
3) Temperature
Actual internal temperature of detector.
4) Temp Setpoint
Internal target temperature that the heater will attempt to maintain (in degrees C).
5) Temp Rnge Flt
Detector integral temperature out of range — Operating range: –40°F to
+167°F (–40°C to +75°C).
6) Voltage
Actual detector supply voltage must be 18 to 30 Vdc.
7) Voltage Fault
Supply voltage is out of range. Operating voltage must be 18 to 30 Vdc.