95-8577
12
5.3
oi
MENU
1) Left
oi
Percentage of calibrated
oi
test signal returned by the left sensor. Reading
should be 90-100%. If reading is below 90%, go to “Device Setup,” select
“Calibration," and perform
oi
Calibration.
2) Middle
oi
Percentage of calibrated
oi
test signal returned by the middle sensor. Reading
should be 90-100%. If reading is below 90%, go to “Device Setup,” select
“Calibration," and perform
oi
Calibration.
3) Right
oi
Percentage of calibrated
oi
test signal returned by the right sensor. Reading
should be 90-100%. If reading is below 90%, go to “Device Setup,” select
“Calibration,” and perform
oi
Calibration.
4)
oi
Fail Count
Number of consecutive
oi
failures counted (one passed
oi
test resets the
counter).
5) Cons
oi
Fails
Set (allowable) number of consecutive
oi
failures to produce a fault.
6)
oi
Cal Act
oi
calibration is in progress.
7)
oi
Cal Flt
An
oi
calibration fault has occurred.
8) Man
oi
Act
A manual
oi
test is in progress.
9) Man
oi
Flt
The detector has failed the last manual
oi
test.
oi
Menu
1) Left
oi
2) Middle
oi
3) Right
oi
4)
oi
Fail Count
5) Cons
oi
Fails
6)
oi
Cal Act
7)
oi
Cal Flt
8) Man
oi
Act
9) Man
oi
Flt
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X3301 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Status Info Menu
1) Warm up (Y/N)
2) Fire (Y/N)
3) Auto
oi
Flt (Y/N)
4) Dim Detect Flt (Y/N)
5) Det Disable Flt (Y/N)
6) Snsr Hdwr Flt (Y/N)
7) HIB Hdwr Flt (Y/N)
8) Int Comm Flt
9) Incompatible Flt
10) Voltage Fault (Y/N)
11) Hardware Menu
12)
oi
Menu