![Det-Tronics X3301 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/det-tronics/x3301/x3301_addendum_2487472012.webp)
95-8577
10
5.3
STATUS INFO MENU
This menu (read-only) shows extensive status information about the detector.
Device Info Menu
1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu
X3301 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
Status Info Menu
1) Warm Up (Y/N)
2) Fire (Y/N)
3) Auto Oi Flt (Y/N)
4) Dim Detect Flt (Y/N)
5) Det Disable Flt (Y/N)
6) Snsr Hdwr Flt (Y/N)
7) HIB Hdwr Flt (Y/N)
8) Int Comm Flt
9) Incompatible Flt
10) Voltage Fault (Y/N)
11) Hardware Menu
12) Oi Menu
1) Warm Up (Y/N)
Device is in the power-up time delay (warm-up) mode.
2) Fire (Y/N)
Indicates “Y” if the device is in a fire alarm status — analog output is at 20 mA,
fire alarm relay is actuated, and LED is red.
3) Auto
oi
Flt (Y/N)
Automatic
oi
Fault. Check viewing windows and
oi
reflector plate for
cleanliness.
4) Dim Detect Flt (Y/N)
Diminished Detection Fault. Excessive background IR radiation. Eliminate
IR interference and/or re-aim/orient detector.
5) Det Disable Flt (Y/N)
Flame detector function has been disabled. Check viewing windows for
cleanliness and/or presence of excessive background IR signal.
6) Snsr Hdwr Flt (Y/N)
Sensor hardware fault.
7) HIB Hdwr Flt (Y/N)
HART Interface Board hardware fault.
8) Int Comm Flt
Internal communication fault.
9) Incompatible Flt
Sensor module firmware version is not compatible with HART Interface
Board.
10) Voltage Fault (Y/N)
Detector operating voltage is out of tolerance.
11) Hardware Menu
Refer to sub-menu.
12)
oi
Menu
Refer to sub-menu.