1 Belt
3
7
12
Belt Deflection Force
2 Belts
7
12
3 Belts
12
2 Belts
5 - 6
8 - 9
New Belt Force (lbs.)
Used Belt Force (lbs.)
1 Belt
2 - 2.5
5 - 6
9 - 10
3 Belts
8 - 9
Figure 18 - Belt Deflection Force Table
•
Inspect the air filters and coils to assure they are clean. If necessary, clean the coils
and install new filters.
•
Check the field and factory piping for leaks. The internal piping may have been
damaged during shipping.
•
Purge any air, dirt, or debris from water lines (if used) to avoid clogging the internal
passages of optional heating coils or water side heat exchangers.
•
Check the drain pan and the condensate piping. Test the drain and prime the p-trap
by pouring water into the drain pan.
•
Verify that all service valves in the refrigeration lines are fully open.
3.2
Outdoor Air Applications
3.2.1 Outdoor Air Option Equipped Units
Construction codes often require you to introduce outdoor air into a commercial
building while it is occupied. Desert Aire dehumidifiers can be factory-configured to
help you comply with these codes. Several factory-installed options, which are
available by special order, can include flanging for an outdoor air duct connection and
a fresh air intake box with air filters and a damper.
Desert Aire - LC/LV Manual