16
VAPOR BARRIER
AUX. HEATING
WINDOW
ANODIZED ALUMINUM
FLOOR DIFFUSERS
(SIZE FOR PROPER
AIR FLOW)
SUPPLY PIPING
LOOP SYSTEM
POOL
P.C.D. COATED SPIRAL
GALVANIZED PIPE
ANODIZED ALUMINUM
RETURN AIR GRILLE
LOCATE AS HIGH AS
POSSIBLE
RETURN AIR DUCT
FILTER RACK
FLEXIBLE DUCT
CONNECTIONS
POOL DECK
CONDENSATE PIPING
AUX. HEATING
ANODIZED ALUMINUM
RETURN AIR GRILLE
LOCATE AS HIGH AS
POSSIBLE
RETURN AIR DUCT
FILTER RACK
FLEXIBLE DUCT
CONNECTIONS
CONDENSATE PIPING
Figure 7 - Under-Floor Duct Layout
2.3 Condensate Drain Piping
The condensate drain connection may be on the side or the bottom of the dehumidifier,
depending on the size and style of cabinet used. Use concrete blocks or steel dunnage to
raise the dehumidifier high enough above the floor to provide clearance for the field-supplied
condensate drain trap.
Note:
While the supply blower runs, the drain pan area inside the dehumidifier operates at a
negative pressure. Your unit requires a p-trap in the condensate drain pipe to prevent
condensate from being drawn into the cabinet of the dehumidifier.
Desert Aire - LC/LV Manual