46
3.3 Low Suction Pressure Alarm
This is a Manual Reset Alarm. The Low Suction Pressure Alarm will only be activated
when the suction pressure falls below the suction pressure cutout point three times in
a one hour period. The refrigeration circuit affected will stop and not restart until the
suction pressure rises above 60.0 psig and the alarm is reset manually. The red Alarm
LED on the display will stay lit until the alarm is reset.
The suction pressure trip setpoint is normally 58.0 psig. When the compressor is
started and for the first 90 seconds of the compressor running, the suction pressure
trip setpoint is set to 22.0 psig. This is to avoid any nuisance tripping due to low
ambient conditions. The first and second conditions of the suction pressure falling
below the suction pressure trip setpoint in a one hour period will stop the compressor
but not activate the alarm. The compressor will restart when the suction pressure rises
above 60.0 psig.
3.4 High Discharge Pressure
This is a Manual Reset Alarm. The Discharge Pressure is activated when the
discharge pressure rises above the high pressure cutout point, 575 psig. The
refrigerant circuit affected will stop and not restart until the alarm condition is reset
manually. The red Alarm LED on the display will stay lit until the alarm is reset.
3.5 Compressor OL
This is a Manual Reset Alarm. The Compressor Overload is activated when the
compressor motor overload device indicates an overloaded condition. In this state, the
refrigerant circuit affected will stop and not restart until the alarm condition is reset
manually. Typically, the motor starting hardware will need to be reset along with the
control system reset. The red Alarm LED on the display will stay lit until the alarm is
reset.
3.6 Temperature Sensor Failure
This is an Automatic Reset Alarm. The Temperature Sensor Failure Alarm is activated
when the supply or intake air temperature sensors are in a shorted or open condition.
In this state, the refrigeration circuits will stop and not restart until the alarm condition
is cleared. The red Alarm LED on the display will stay lit until the alarm is reset.
3.7 Low Voltage Monitor Tripped
This is an Automatic Reset Alarm. The optional Low Voltage Monitor is required to
activate this alarm. The Low Voltage Monitor Tripped is activated when the monitor
senses a below normal voltage – low enough to damage the equipment. The unit will
stop and not restart until this condition is reset. The red Alarm LED on the display will
stay lit until the alarm is reset.
Desert Aire - CM3550 Manual
Содержание CM3550 Series
Страница 2: ...2 ...
Страница 5: ...5 Desert Aire CM3550 Manual Product Warning for the State of California ...
Страница 6: ...6 Desert Aire CM3550 Manual ...
Страница 34: ...34 Figure 47 Figure 48 Figure 49 Figure 50 Desert Aire CM3550 Manual ...
Страница 44: ...44 Desert Aire CM3550 Manual ...
Страница 57: ...57 Desert Aire CM3550 Manual ...